Plan Review Details - Permit 05031875
Plan Review Stops For Permit 05031875
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-02 Cont ID  
Sent By jwitmer Date 2005-05-02 Time 08:23 Rev Time 1.25
Received By jwitmer Date 2005-05-02 Time 07:57 Sent To PC
Notes
2005-05-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031875
 ADD: 1411 N FLAGLER # 3900
 CONT: THE WEITZ CO
 TEL: (561)951-2677
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENEID
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, THE
 HALLWAY RIGHT OF THE DOUBLE DOORS
 INDICATES A 1 HR RATING ONLY ON 1 SIDE
 OF THE HALLWAY NO RATING , NOR DOES THE
 WALL CONTINUE TO THE DECK ABOVE?
 419.3.9.5 ALL SMOKE PARTITIONS,
 HORIZONTAL EXITS, AND EXIT PASSAGEWAY
 PARTITIONS SHALL BE CONSTRUCTED PRIOR TO
 THE THE CONSTRUCTION OF INTERVENING
 WALLS.
  
 3) HALLWAY TO THE LEFT OF THE DOUBLE
 DOORS, THE CEILING IS NOT INDICATED NOR
 IS THE RATING OF THE DOUBLE DOORS.
 ?419.3.9.7 WHERE IT IS NOT POSSIBLE TO
 INSPECT SMOKE PARTITIONS
 BECAUSE OF THE FIRE TESTED MEMBRANE,
 FIRE-RATED ACCESS PANELS SHALL BE
 INSTALLED ADJACENT TO EACH SIDE OF
 THE SMOKE PARTITIONS AT INTERVALS
 NOT EXCEEDING 30 FEET (9.00 METERS)
 AND IN SUCH LOCATIONS AS NECESSARY
 TO VIEW ALL SURFACES OF THE
 PARTITION.
  
 4) 704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) INDICATE THE LOCATION OF EXIT LIGHTS:
 ?1016.1.1 ILLUMINATION OF MEANS OF
 EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY
 BUILDING AND STRUCTURE.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS, RAMPS, ESCALATORS,
 WALKWAYS AND EXIT PASSAGEWAYS LEADING
 TO A PUBLIC WAY.
  
 6) ?435.4.4 POSTING OF AIRBORNE
 RADIOACTIVITY AREAS. THE LICENSEE SHALL
 POST EACH AIRBORNE RADIOACTIVITY AREA
 WITH A CONSPICUOUS SIGN OR SIGNS
 BEARING THE RADIATION SYMBOL AND THE
 WORDS "CAUTION, AIRBORNE
 RADIOACTIVITY AREA" OR "DANGER,
 AIRBORNE RADIOACTIVITY AREA."
  
 ?435.4.5 POSTING OF AREAS OR ROOMS IN
 WHICH LICENSED MATERIAL IS USED OR
 STORED. THE LICENSEE SHALL POST EACH
 AREA OR ROOM IN WHICH THERE IS USED
 OR STORED AN AMOUNT OF LICENSED
 MATERIAL EXCEEDING 10 TIMES THE QUANTITY
 OF SUCH MATERIAL SPECIFIED IN STATE OF
 FLORIDA OFFICE OF RADIATION CONTROL
 RADIOACTIVE MATERIAL REQUIRING
 LABELING, MAY 2000, WHICH IS HEREIN
 INCORPORATED BY REFERENCE AND WHICH IS
 AVAILABLE FROM THE DEPARTMENT, WITH
 A CONSPICUOUS SIGN OR SIGNS BEARING
 THE RADIATION SYMBOL AND THE WORDS
 "CAUTION, RADIOACTIVE MATERIAL(S)" OR
 "DANGER, RADIOACTIVE MATERIAL(S)."
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-04 Cont ID  
Sent By dpalmer Date 2005-04-04 Time 13:38 Rev Time 0.50
Received By dpalmer Date 2005-04-04 Time 13:37 Sent To  
Notes
2005-04-04 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE TO
 BE SUBMITTED.
 PLEASE INDICATE SIZE OF PANEL AND LOAD
 ON PANEL.
 215.5,220
  
 2)NOTE: PLEASE VERIFY EXISTING RECEPTS
 SHOWN WITHIN6' OF SINKS FOR GFI
 PROTECTION.. 210.8
  
 3)NOTE: PLEASE INCLUDE CIRCUITING FOR
 EM/EXT LTS PER 700.12E.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-04-13 Cont ID  
Sent By mwennerg Date 2005-04-13 Time 14:06 Rev Time 0.00
Received By mwennerg Date 2005-04-13 Time 14:06 Sent To  
Notes
2005-04-13 00:00:001) PLEASE PROVIDE THE LOCATIONS OF
 EMERGENCY LIGHTING FACILITIES OF ALL
 AREAS INCLUDING THE CLASSROOMS.
  
 2) PLEASE PROVIDE REASONING FOR THE
 CLASSROOMS SHOWING NO EXIT SIGNS.
  
 3) FIRE EXTINGUISHERS SHALL BE LOCATED
 NOT TO EXCEED A 75' TRAVEL DISTANCE.
  
 4) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 5) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date   Time 16:47 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 16:47 Sent To  
Notes
2005-04-01 00:00:00TO "COMM" BD#7

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-27 Cont ID  
Sent By hmoser Date 2005-04-27 Time   Rev Time 0.00
Received By hmoser Date 2005-04-27 Time 15:57 Sent To  
Notes
2005-04-27 00:00:00MECHANICAL DENIED
 1) SUBMIT PLANS WITH MECHANICAL
 APPLICATION
 2) PLEASE SUBMIT FRESH AIR CALCULATIONS
 WITH PLANS
 3) PLEASE SUBMIT EQUIPMENT SCHEDULE WITH
 PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By kstevens Date 2005-04-26 Time 10:01 Rev Time 1.25
Received By kstevens Date 2005-04-26 Time 10:01 Sent To  
Notes
2005-04-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) SUBMIT A SANITARY RISER DIAGRAM
 SHOWING ALL PIPE SIZES, VENTING, POINT
 OF CONNECTION ECT. ALSO SUBMIT A WATER
 RISER DIAGRAM SHOWING ALL PIPES SIZES,
 VALVES, WATER HAMMER ARRESTORS, WHERE
 REQUIRED BY SECTION 604.9 AND POINT OF
 CONNECTION. SECTION 104.3.1.1. THESE
 RISER DIAGRAM SHALL BE IN ISOMETRIC
 FORM.
 2) DARK ROOM SINK, MORE INFORMATION IS
 REQUIRED. A DILUTION SINK MAY BE
 REQUIRED FOR CHEMICALS USED IN THIS
 PROCESS. CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE MANAGER, (561)
 837-4074 OR E-MAIL [email protected] FOR
 DETERMINATION. SUBMIT SHEET FROM RODNEY
 COMPO WITH PLANS WHEN RESUBMITTING.
 3) ALL DEVICES, APPURTENANCES,
 APPLIANCES AND APPARATUS INTENDED TO
 SERVE SOME SPECIAL FUNCTION, SUCH AS
 STERILIZATION, DISTILLATION, PROCESSING,
 COOLING OR STORAGE OF ICE OR FOODS AND
 THAT CONNECT TO EITHER THE WATER SUPPLY
 OR DRAINAGE SYSTEM, SHALL BE PROVIDED
 AGAINST BACKFLOW, FLOODING, FOULING,
 CONTAMINATION OF THE WATER SUPPLY SYSTEM
 AND STOPPAGE OF THE DRAIN. SECTION 422.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]