Plan Review Details - Permit 05031856
Plan Review Stops For Permit 05031856
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-10 Cont ID  
Sent By rbrown Date 2005-08-10 Time 15:08 Rev Time 0.00
Received By rbrown Date 2005-08-10 Time 15:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-01 Cont ID  
Sent By rbrown Date 2005-08-01 Time 08:11 Rev Time 0.00
Received By rbrown Date 2005-08-01 Time 08:11 Sent To  
Notes
2005-08-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.2THE ARCHITECTURAL PLAN,
 SUBMITTED FOR LOCATION OF THE GATES,
 DOES NOT HAVE A TITLE BLOCK SHOWING THE
 TITLE/ADDRESS OF THE PROJECT, THE NAME
 OF THE PERSON RESPONSIBLE FOR THE
 DESIGN, THE SIGNATURE OF THAT PERSON AND
 THE DATE.THERE IS ALOT OF UNNECESSARY
 INFORMATION ON THE SUBMITTED PLAN.IT
 IS STRONGLY RECOMMENDED THAT THE
 LOCATION PLAN JUST SHOWS THE OUTLINE OF
 THE BUILDING, PROPERTY LINE, PARKING
 GARAGE ENTRY/EXIT LANES, THE GATE
 LOCATION AND ANY OTHER INFORMATION/NOTES
 APPLICABLE TO INSTALLATION OF THE GATES.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-23 Cont ID  
Sent By rbrown Date 2005-06-23 Time 08:55 Rev Time 0.00
Received By rbrown Date 2005-06-23 Time 08:55 Sent To Z
Notes
2005-06-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 61G1-16.004FL. ADMIN. CODE.IT
 APPEARS THAT THE ARCHITECT'S PLANS
 SUBMITTED WITH THIS PERMIT APPLICATION
 ARE BEING USED ONLY TO LOCATE THE GATES.
 THE LOCATION PLANS SHALL NOT INCLUDE AN
 ARCHITECT'S TITLE BLOCK IF THEY ARE NOT
 SIGNED AND SEALED.ALSO, SUCH PLANS
 MUST BE MARKED "FOR GATE LOCATION
 PURPOSES ONLY".ALTERNATIVELY, THE
 SUBMITTED PLANS MUST DATED AND BEAR THE
 ORIGINAL SIGNATURE AND SEAL AND THE
 PRINTED NAME OF THE ARCHITECT SEALING
 THE PLANS.
 THIS COMMENT WAS ALSO MADE IN THE FIRST
 ELECTRICAL PLAN REVIEW BUT NOT ADDRESSED
 ON THE RESUBMITTED PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-23 Cont ID  
Sent By rbrown Date 2005-06-23 Time 08:50 Rev Time 0.00
Received By rbrown Date 2005-06-23 Time 08:50 Sent To  
Notes
2005-06-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 NO BUILDING PLAN REVIEW WAS CARRIED OUT
 AT FIRST ROUND OF REVIEWS BECAUSE PLANS
 WERE HELD IN ZONING.
  
 ELECTRICAL REVIEW COMMENT #2 WOULD HAVE
 APPLIED TO THE BUILDING PLAN REVIEW ALSO
 AND WAS NOT ADDRESSED ON THE RESUBMITTED
 PLANS.SEE REVIEW #2.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-08-03 Cont ID  
Sent By dpalmer Date 2005-08-03 Time 17:49 Rev Time 0.50
Received By dpalmer Date 2005-08-03 Time 17:49 Sent To  
Notes
2005-08-03 00:00:00STAMPED ALL GATE MOTOR SPEC SHEETS.
 STAMPED ELECTRICAL DETAIL/DISCONNECT
 SHEETS.
 OK.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-07-12 Cont ID  
Sent By dpalmer Date 2005-07-12 Time 18:39 Rev Time 0.25
Received By dpalmer Date 2005-07-12 Time 18:36 Sent To  
Notes
2005-07-12 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE NOTE #1 FROM FIRST
 REVIEW.
 PLEASE PROVIDE A DRAWING OF WIRING/POWER
 FOR MOTOR(S). PLEASE SHOW REQUIRED
 DISCONNECTING MEANS.
 IT IS NOTED ON BLDG LAYOUT OF CIRCUIT
 SIZE AND WHERE CIRCUIT IS COMING FROM,
 HOWEVER ABOVE WAS NOT SUBMITTED.
 PLEASE ALSO SEE FBC 104.2.1, WHICH
 REQUIRES ALL PLANS, DRAWINGS,TO HAVE THE
 PRINTED NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLANS.
  
 PLEASE CALL TO GO VER ABOVE COMMENT.
  
 SPECS SUBMITTED FOR GATE MOTORS ETC ARE
 OK.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-06 Cont ID  
Sent By dpalmer Date 2005-06-06 Time 10:55 Rev Time 0.30
Received By dpalmer Date 2005-06-06 Time 10:55 Sent To  
Notes
2005-06-06 00:00:00****** UNSAT 2ND REVIEW ******
  
 1)NOTE: PLEASE SEE SAME NOTES FROM
 PREVIOUS REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-13 Cont ID  
Sent By dpalmer Date 2005-04-13 Time 19:28 Rev Time 0.30
Received By dpalmer Date 2005-04-13 Time 19:28 Sent To  
Notes
2005-04-13 00:00:00*********** UNSAT ***********
  
 1)NOTE: PELASE SEE THERE IS NOT ENOUGH
 ELECTRICAL INFORMATION FOR REVIEW.
 CIRCUITS ? DISCONNECTING MEANS FOR
 MOTORS? ETC.
 WHERE ARE FEEDS COMING FROM?
  
 2)NOTE: PLEASE SEE PLANS SUBMITTED FOR
 REVIEW ARE COPIES OF PLANS OF BLDG WHICH
 CONTAIN FULL TITLE BLOCKS FOR ARCH'S AND
 ENGINEER'S OF RECORD. THESE
 PLANS/DRAWINGS MAY NOT BE USED UNLESS
 SIGNED, DATED AND SEALED BY THE ARCH'S
 AND ENGINEERS OF RECORD. FS
 471.025,481.221
  
 3)NOTE: PLEASE SEE SPECS SUBMITTED FOR
 GATE CONTROLLERS NEED TO SHOW LISTINGS
 FROM A NRTL.
  
 4)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR POSSIBLE NOTES FOR POWER FAILURE AND
 FAIL SAFE OPERATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-07-29 Cont ID  
Sent By mwennerg Date 2005-07-29 Time 13:17 Rev Time 0.00
Received By mwennerg Date 2005-07-29 Time 13:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-06-07 Cont ID  
Sent By mwennerg Date 2005-06-07 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2005-06-07 Time 11:06 Sent To  
Notes
2005-06-07 00:00:00****DENIED****
  
 PLEASE NOTE THAT COMMENTS FROM PREVIOUS
 FIRE REVIEW HAVE NOT BEEN ADDRESSED.
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-04-14 Cont ID  
Sent By mwennerg Date 2005-04-14 Time 10:55 Rev Time 0.00
Received By mwennerg Date 2005-04-14 Time 10:55 Sent To  
Notes
2005-04-14 00:00:001) PLEASE PROVIDE ADDITIONAL INFORMATION
 REGARDING THE GATE DRIVER AND FAILSAFE
 MECHANISM.
  
 2) WHAT MEANS OF OPERATION WILL BE USED
 TO OPEN AND CLOSE THE GATES?
  
 3) WHAT PROVISIONS HAVE BEEN MADE TO
 PROVIDE FOR EMERGENCY ACCESS INTO THE
 PARKING GARAGE?
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 11:06 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 11:06 Sent To  
Notes
2005-08-02 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#8

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 15:14 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 15:14 Sent To  
Notes
2005-07-06 00:00:00TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 09:54 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 09:54 Sent To  
Notes
2005-06-24 00:00:00PLANS SENT TO ANGELLA FOR ZONING REVIEW.
  
  
  
2005-05-23 00:00:00TO "COMM" BD#8
2005-05-13 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 08:34 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 08:34 Sent To  
Notes
2005-05-06 00:00:00PLANS/APPLICATION COULD NOT BE FOUND.
 ASKED ZONING REVIEWER TO CHECK IF THEY
 WERE TAKEN BACK BY ZONING FOR FURTHER
 REVIEW.
  
 PLANS/APPLICATION RETURNED TO R BROWN BY
 ERIC SCHNIEDER, ZONING REVIEWER.
2005-04-20 00:00:004/20/05-TO RBROWN DESK
2005-04-06 00:00:00TO "COMM" BD#34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date 2005-04-01 Time 09:21 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 09:21 Sent To Z
Notes
2005-04-01 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2005-06-24 Cont ID  
Sent By sgraham Date 2005-06-24 Time 15:54 Rev Time 0.00
Received By sgraham Date 2005-06-24 Time 15:53 Sent To I
Notes
2005-06-24 00:00:00GATES MUST REMAIN OPEN DURING THE HOURS
 RETAIL SPACES ARE OPEN.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-05 Cont ID  
Sent By mmclean Date 2005-04-05 Time 15:48 Rev Time 0.00
Received By mmclean Date 2005-04-05 Time 15:48 Sent To I
Notes
2005-04-05 00:00:00DENIED,
 1. MUST PROVIDE PLANS FOR HOW THE
 VEHICLE WILL BE STACKED.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720