Plan Review Details - Permit 05031840
Plan Review Stops For Permit 05031840
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-08-30 Cont ID  
Sent By jleech Date 2005-04-07 Time 18:05 Rev Time 0.00
Received By rmcdouga Date 2005-08-30 Time 15:13 Sent To M
Notes
2005-04-07 00:00:00SEE ELECTRICAL PLAN REVIEWERS NOTE ABOUT
 NAME ON PLANS.
 KITCHEN SINK MISSING FROM RISER DIAGRAM
 AND RISER DIAGRAM IS 180 DEG. FROM FLOOR
 PLAN PLEASE CORRECT.
 PUBLIC SEWER SYSTEM IS STUB OUT AT
 PROPERTY LINE SEPTIC TANK IS NOT
 PERMITED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2005-10-19 Cont ID  
Sent By rmcdouga Date 2005-10-19 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2005-10-19 Time 07:10 Sent To  
Notes
2005-10-19 00:00:00RESTAMP PLANS ALL SHHETS EXCEPT
 ELECTRICAL E-1 WHICH DOES NOT MATCH
 APPROVED SET. ALSO RESTAMP ALL PRODUCT
 APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-12 Cont ID  
Sent By rmcdouga Date 2005-09-12 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2005-09-12 Time 14:12 Sent To  
Notes
2005-09-12 00:00:00PROCESS AND PRINT PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-30 Cont ID  
Sent By rmcdouga Date 2005-08-30 Time 15:14 Rev Time 0.00
Received By rmcdouga Date 2005-08-30 Time 15:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-27 Cont ID  
Sent By jwitmer Date 2005-07-27 Time 09:19 Rev Time 0.77
Received By jwitmer Date 2005-07-27 Time 08:26 Sent To PC
Notes
2005-07-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031840
 ADD: 4119 SHELLY RD
 CONT: TANCO
 TEL: (561)798-3190
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ABCHOR
 B) FIXED WINDOWS LOW PRESSURE
 C) SOFFIT INDICATE WHICH SYSTEM WILL BE
 USED WITH APPROPRIATE PRESSURES
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-04 Cont ID  
Sent By rmcdouga Date 2005-05-04 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2005-05-04 Time 07:12 Sent To  
Notes
2005-05-04 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) FAC 61G15-23.002 REQUIRE THE
 ENGINEER'S LICENSE NUMBER ON EACH SIGNED
 AND SEALED SHEET OF THE DRAWINGS.
  
 3)THE ROOF SHEATHING NAILING
 REQUIREMENTS ON SHEET 2 DO NOT INCLUDE
 THE NAIL SPACING FOR ZONE 3, WHICH
 INCLUDES THE OUTSIDE CORNERS OF HIP
 ROOFS. SEE TABLE BELOW.
  
 TABLE 2306.1 PALM BEACH COUNTY
 AMENDMENTS
 ROOF SHEATHING NAILING REQUIREMENTS
  
 ZONE 1 & 28D COMMON
 6" EDGES & 6" INTERMEDIATE
  
 ZONE 38DCOMMON
 4" EDGES & 6" INTERMEDIATE
  
 4) THE INTERNAL PRESSURE COEFFECIENT ON
 SHEETS 3 AND 4 IS MISSING THE NEGATIVE
 SIGN.
  
 5) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 6) SUBMIT FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR THE ALUMINUM SOFFIT.
  
 7) SUBMIT 2 COPIES OF A SURVEY SHOWING
 THE LOCATION OF THE STRUCTURE ON THE
 PROPERTY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-07-27 Cont ID  
Sent By dpalmer Date 2006-07-27 Time 09:32 Rev Time 0.00
Received By dpalmer Date 2006-07-27 Time 09:32 Sent To PC
Notes
2006-07-27 00:00:00CHANGES ON PLANS OK'D ,DATED AND
 INITIALED .

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-07-22 Cont ID  
Sent By dpalmer Date 2006-07-22 Time 12:37 Rev Time 0.00
Received By dpalmer Date 2006-07-22 Time 12:08 Sent To PC
Notes
2006-07-22 00:00:00*** REDLINED PLANS ***
  
 TO BE REVISED BEFORE FINAL/ C.O.
  
 1) NOTE: PLEASE SEE DINING RM CIRUIT
 SHOWN AT 1000VA WHEN 1500VA MIN IS
 REQUIRED PER 210.52B1,210.11C1,220.16
  
 2) NOTE: PLEASE SEE CU CIRCUIT SHOWS
 1000VA ON ONE PHASE AND 1500 VA ON THE
 OTHER. THIS IS NOT POSSIBLE. PLEASE
 ADJUST LOADS AND VA.
 408.4, 240.4, ETC
 106.1.2 FBC.
  
 3) NOTE: PLEASE SEE ITEMS SHOWN AS
 1-POLE/2-POLE??
  
 4) NOTE: PLEASE VERIFY THE LOCATION OF
 SD REQUIRED IN THE IMMEDICATE VICINITY
 OUTSIDE BEDRMS#2, AND #3. SEE NFPA-72
 11.5.1.1,11.8.3.
  
 5) NOTE: PLEASE SEE GD OPENER SHOWS
 1000VA ON LOAD CALCULATIONS, YET SHOWS
 1200VA ON PANEL SCHEDULE? PLEASE
 CORRELATE AND ADJUST.
 408.4, 106.1.2
  
 6) NOTE: VERIFY DEN CIRCUIT AS THIS
 SHOWS 15A BRKR AND #12 AWG. THIS IS OK,
 HOWEVER IF SHOWN THIS WAY THEN THIS WILL
 BE VERIFIED.
  
 7) NOTE: PLEASE SEE THE DISHPOSAL AND
 DISHWASHER IS ONLY TO VERIFY IF THESE
 ARE BOTH ON SEPARATE RECEPTS. IF BOTH
 ARE FED TO ONE RECEPTS, THEN THIS RECEPT
 MUST BE FED FROM A TWO POLE BREAKER.
 PLEASE ONLY REVISED PANEL SCHEDULE FOR
 2-POLE BRKR IF INDEED ONE DEVICE/RECEPT
 FEEDS BOTH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL CO. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-07-18 Cont ID  
Sent By dpalmer Date 2006-07-18 Time 07:37 Rev Time 0.00
Received By dpalmer Date 2006-07-18 Time 07:26 Sent To PC
Notes
2006-07-18 00:00:00********* UNSAT ***********
  
 1) NOTE: PLEASE CORRELATE ALL ITEMS
 INDICATED ON LOAD CALCUALITONS WITH
 PANEL SCHEDULE AND ITEMS ON PANEL
 SCHEDULE WITH LOAD CALCUALTIONS.
 408.4,310.16,220.31 ETC
  
 2) NOTE: PLEASE SEE ALL CIRCUITS ON
 PANEL SCHEDULE. PLEASE CORRELATE ALL
 LOADS WITH THE CORRECT OCP AND CONDUCTOR
 SIZES. PLEASE SEE THERE ARE NUMEROUS
 ITEMS WHICH DO NOT CORRELATE.
 60A OCP ON #10,
 LOADS EXCEEDING OCP AND WIRE SIZE.
 8KW ON #12,
 5KW ON #12,
 WIRE SHOWN AS #154?
 PLEASE SEE MIN VA FOR SM APPLIANCE
 CIRCUITS TO BE 1500VA MIN.
 PLEASE LABEL SMALL APPLIANCE
 CIRCUITS(KITCHEN OUTLETS0??
  
 ** PLEASE KNOW, THIS SEEMS TO BE A
 MISPRINTING OF THESE ITEMS.
 PLEASE BE SURE TO GO THROUGH ALL
 CIRCUITS WHICH ARE REQUIRED TO BE 20A
 FOR WASHER, SM APPLIANCE, LAUNDRY ,
 DINING RM ETC AND BE SURE THE WIRE SIZE
 CORRELATES ETC.
  
 310.16,240.4,408.4, 210.52B1, 210.11C1,
 220.16 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 14:18 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 12:40 Sent To PC
Notes
2006-07-07 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PANEL SCHEDULE WITH THE ACTUAL
 CIRCUIT NUMBERS. PLEASE SEE 2-POLE
 CIRCUITS SHOULD INDEED TAKE THE SPACE OF
 TWO CIRCUITS SPACES ON PANEL SCHEDULE.
 PLEASE KNOW, ALL CIRCUITS FOR ROOMS AND
 AREAS SHALL BE INDICATE ON PANEL
 SCHEDULE SPECIFIC TO THE ROOM ETC.
 IE; LTS BRM, RECEPTS MASTER BEDRM, BATH
 #2 LTS. ETC
  
 2) NOTE: PLEASE SEE SD IN MSTER BEDRM IS
 REQUIRED TO BE LOCATED WITHIN 12" OF THE
 HIGHTEST POINT ON A FLAT CEILING.
 NFPA-72 11.8.3
  
 3) NOTE: PLEASE BE SURE PLANS CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS/DEISGN.
 FBC ADMIN SECT 104.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-24 Cont ID  
Sent By dpalmer Date 2005-06-24 Time 07:24 Rev Time 0.50
Received By dpalmer Date 2005-06-24 Time 07:17 Sent To P
Notes
2005-06-24 00:00:00********* NOTES REDLINED ************
  
 MISSING RECEPTS PER 21.52, 210.52E,
  
 MISSING DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D,210.11C3, MUST BE 20A, #12.
  
 CIRCUIT #'S ON PANEL SCHEDULE DO NOT
 CORRELATE WITH 2-POLE CIRCUITS.
  
 SUB PANEL NOT INCLUDED IN SCOPE OF WORK.
 IF INSTALLED, PLEASE REVISE RISER AND
 PROVIDE PANEL SCHEDULE
  
  
 THE ABOVE ITEMS WERE REDLINED ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-06 Cont ID  
Sent By dpalmer Date 2005-04-06 Time 10:11 Rev Time 0.75
Received By dpalmer Date 2005-04-06 Time 10:11 Sent To M
Notes
2005-04-06 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE INCLUDE INFORMATION FOR
 MAIN. IS PANEL A MCB ? IS MAIN LOCATED
 WITH METER?
 215.5,240.4B,225.30 ETC.
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SEE IF MAIN IS NOT
 LOCATED AT METER, PLEASE SEE 250.6,
 250.24, AN EQUIPMENT GROUNDING CONDUCTOR
 IS NOT INSTALLED FROM METER TO FIRST
 MEANS OF DISCONNECT.
 PLEASE SEE RISER SHOWS AN EQUIPMENT
 GROUNDING CONDCUTOR FROM METER TO MAIN.
  
 4)NOTE: PLEASE SEE RISER INDICATES A
 POSSIBLE SUB-PANEL IF REQUIRED. IF THIS
 IS INSTALLED, PLANS BE NEED TO BE
 REVISED TO REFLECT ACTUAL INSTALLATION
 TAKEN.
 PLEASE ALSO SEE PANEL IS SHOWN WITH #5
 AS FEEDERS. PLEASE SEE AWG'S AVAILABLE,
 THIS IS NOT A SIZE. PLEASE SEE 310.16
  
 5)NOTE: PLEASE SEE MISSING RECEPTS ALONG
 KITCHEN COUNTERSPACE PER 210.52C1
 PLEASE SHOW ALL RECEPTS SERVING KITCHEN
 COUNTERSPACE AS GFI/GFI PROTECTED PER
 210.8A-6
  
  
 6)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND LOAD CALCAULTIONS. PLEASE SEE THERE
 ARE NUMEROUS ITEMS THAT DO NOT
 CORRELATE.
 IE: WELL PUMNP, DISPOSAL, FRIG, A/C
 UNITS, DISHWASHER, WASHER/LANUDRY,
 RANGE, ETC.
  
 7)NOTE: PLEASE ALSO SEE MANY "MISPRINTS"
 ON PANEL SCHEDULE. PLEASE SEE 2-POLE
 CIRCUITS, SHOWING A REDUCED AWG AND OCP
 ON "B" PHASE.
  
 8)NOTE: PLEASE CORRELATE PLANS, PANEL
 SCHEDULE AND LOAD CALCULATIONS FOR
 RANGE, OVENS.
 PLEASE SEE PLANS INDICATE DOUBLE OVENS,
 YET THIS IS NOT ON PANEL SCHEDULE OR
 LOAD CALCS. PLEASE SEE PLANS INDICATE A
 SEPARATE COOKTOP ALSO, YET THIS IS NOT
 ON PANEL SCHEDULE OR LOAD CALCS.
 PLEASE SEE PANEL SCHEDULE SHOWS 13KW2-P
 60A FOR RANGE???
 PLEASE SEE LOAD CALCS SHOWS 8KW?
 ETC.
  
 9)NOTE: PLEASE SEE PLANS FOR MISSING
 RECEPTS PER 210.52
  
 10)NOTE: PLEASE SEE MISSING DISCONNECT
 FOR A/C COND UNIT PER 440.11
 PLEASE SHOW.
  
 11)NOTE: PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
 PLEASE THE PLANS ONLY NEED THE PRINTED
 NAME.
  
 12)NOTE: PLEASE SEE ONE SET OF PLANS HAS
 BEEN REDLINED AT LOCATIONS FOR THE ABOVE
 COMMENTS. PLEASE SEE THESE LOACTIONS
 SHOWN ON PLANS.
  
 13)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETED SETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 09:14 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 09:14 Sent To E
Notes
2006-07-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 11:58 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 11:58 Sent To E
Notes
2006-07-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-07-17 Cont ID  
Sent By adarroug Date 2006-07-17 Time 13:08 Rev Time 0.00
Received By adarroug Date 2006-07-17 Time 13:08 Sent To E
Notes
2006-07-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-07-05 Cont ID  
Sent By adarroug Date 2006-07-05 Time 14:39 Rev Time 0.00
Received By adarroug Date 2006-07-05 Time 14:39 Sent To E
Notes
2006-07-05 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 16:34 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 16:34 Sent To B
Notes
2005-10-12 00:00:00TO "RMCDOUGAL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 18:23 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 18:23 Sent To P
Notes
2005-09-08 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 14:26 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 14:26 Sent To Z
Notes
2005-09-02 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-08-25 Cont ID  
Sent By adarroug Date 2005-08-25 Time 11:37 Rev Time 0.00
Received By adarroug Date 2005-08-25 Time 11:37 Sent To P
Notes
2005-08-25 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 15:33 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 15:33 Sent To Z
Notes
2005-08-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 16:12 Rev Time 0.00
Received By shill Date 2005-06-20 Time 16:12 Sent To E
Notes
2005-06-20 00:00:00TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 11:56 Rev Time 0.00
Received By shill Date 2005-06-20 Time 11:56 Sent To E
Notes
2005-06-20 00:00:00TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-14 Cont ID  
Sent By shill Date 2005-06-14 Time 16:56 Rev Time 0.00
Received By shill Date 2005-06-14 Time 16:56 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 09:09 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 09:09 Sent To E
Notes
2005-04-06 00:00:00TO "SFR""E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-04 Cont ID  
Sent By rmcdouga Date 2005-05-04 Time 12:48 Rev Time 0.00
Received By rmcdouga Date 2005-04-01 Time 14:07 Sent To  
Notes
2005-04-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By rmcdouga Date 2005-08-30 Time 15:13 Rev Time 0.50
Received By prafter Date 2005-07-21 Time 09:22 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-08 Cont ID  
Sent By rmcdouga Date 2005-05-03 Time 16:14 Rev Time 0.50
Received By prafter Date 2005-04-08 Time 11:08 Sent To B
Notes
2005-04-08 00:00:00MECH. PLAN REVIEW.
 PROVISO: PROVIDE FOR DRYER VENTING TO
 EXT. OF BUILDING.
  
 PAT RAFTER 805/6728 0R 805/6719 PATTY
 KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-09-10 Cont ID  
Sent By jleech Date 2005-09-10 Time 06:36 Rev Time 0.50
Received By jleech Date 2005-09-10 Time 06:36 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-08-29 Cont ID  
Sent By jleech Date 2005-08-29 Time 08:52 Rev Time 0.50
Received By jleech Date 2005-08-29 Time 08:52 Sent To B
Notes
2005-08-29 00:00:00DENIED;
 SECOND REQUEST.
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN. BATHROOM # 3 IS MISSING FROM RISER
 DIAGRAM. SHOW KITCHEN SINK AS A SINK NOT
 A LAV.
 PLUMBIG PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-06-28 Cont ID  
Sent By kstevens Date 2005-06-28 Time 14:25 Rev Time 0.68
Received By kstevens Date 2005-06-28 Time 14:25 Sent To M
Notes
2005-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT 1 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. BATH #3 IS NOT
 SHOWN ON THE RISER DIAGRAM. SANT. PIPING
 SHALL REFLECT THE INSTALLATION OF THE
 PIPING. SEE ATTACHED SHEET FOR EXAMPLE
 OF A RISER DIAGRAM THAT REFLECT THE
 FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-04-07 Cont ID  
Sent By jleech Date 2005-04-07 Time 18:15 Rev Time 0.50
Received By jleech Date 2005-04-07 Time 18:02 Sent To M
Notes
2005-04-07 00:00:00NAME OF PERSON RESPOSABLE FOR DRAWING
 NEED TO PRINT NAME ON DRAWINGS.
 NO SEPTIC TANK PERMITED PUBLIC SEWER AT
 PROERTY LINE
 PLUMBING RISER IS 180 DEGREES FROM FLOOR
 PLAN AND MISSING KITCHEN SINK PLEASE FIX
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2005-09-08 Cont ID  
Sent By mmclean Date 2005-09-08 Time 16:04 Rev Time 0.00
Received By mmclean Date 2005-09-08 Time 16:04 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2005-08-23 Cont ID  
Sent By mmclean Date 2005-08-23 Time 17:22 Rev Time 0.00
Received By mmclean Date 2005-08-23 Time 17:22 Sent To I
Notes
2005-08-23 00:00:00DENIED,
 1. PROPOSED DRIVEWAY HAS EXCEEDED 1000SQ
 FT OR 75% OF LANDSCAPE WITHIN THE 25FT
 FRONT SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2005-06-17 Cont ID  
Sent By mmclean Date 2005-06-17 Time 18:41 Rev Time 0.00
Received By mmclean Date 2005-06-17 Time 18:41 Sent To I
Notes
2005-06-17 00:00:00DENIED,
 1. NEED TO PROVIDE THE DIMENSION OF THE
 PROPOSED DRIVEWAY WIDTH & LENGTH.
 WITHOUT THE DIMENSION CANNOT CALCULATE
 THE REQUIRED SQ FT ALLOWED.
  
 **MUST HAVE 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FRIST 25FT FRONT
 SETBACK**
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-05 Cont ID  
Sent By mmclean Date 2005-04-05 Time 09:39 Rev Time 0.00
Received By mmclean Date 2005-04-05 Time 09:39 Sent To I
Notes
2005-04-05 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SURVEY
 SHOWING THE WORK, WITH SETBACKS
 (FRONT/SIDE/REAR).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720