| Plan Review Stops For Permit 05031840 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-04-07 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-08-30 |
Time |
15:13 |
Sent To |
M |
|
| Notes |
| 2005-04-07 00:00:00 | SEE ELECTRICAL PLAN REVIEWERS NOTE ABOUT | | | NAME ON PLANS. | | | KITCHEN SINK MISSING FROM RISER DIAGRAM | | | AND RISER DIAGRAM IS 180 DEG. FROM FLOOR | | | PLAN PLEASE CORRECT. | | | PUBLIC SEWER SYSTEM IS STUB OUT AT | | | PROPERTY LINE SEPTIC TANK IS NOT | | | PERMITED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
N |
Date |
2005-10-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-10-19 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-10-19 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2005-10-19 00:00:00 | RESTAMP PLANS ALL SHHETS EXCEPT | | | ELECTRICAL E-1 WHICH DOES NOT MATCH | | | APPROVED SET. ALSO RESTAMP ALL PRODUCT | | | APPROVALS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-09-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-09-12 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-09-12 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2005-09-12 00:00:00 | PROCESS AND PRINT PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-08-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-08-30 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-08-30 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-07-27 |
Time |
09:19 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2005-07-27 |
Time |
08:26 |
Sent To |
PC |
|
| Notes |
| 2005-07-27 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05031840 | | | ADD: 4119 SHELLY RD | | | CONT: TANCO | | | TEL: (561)798-3190 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | 1) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | | | | | | | FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) TRUSS ABCHOR | | | B) FIXED WINDOWS LOW PRESSURE | | | C) SOFFIT INDICATE WHICH SYSTEM WILL BE | | | USED WITH APPROPRIATE PRESSURES | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-05-04 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-05-04 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2005-05-04 00:00:00 | DENIED | | | | | | 1)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) FAC 61G15-23.002 REQUIRE THE | | | ENGINEER'S LICENSE NUMBER ON EACH SIGNED | | | AND SEALED SHEET OF THE DRAWINGS. | | | | | | 3)THE ROOF SHEATHING NAILING | | | REQUIREMENTS ON SHEET 2 DO NOT INCLUDE | | | THE NAIL SPACING FOR ZONE 3, WHICH | | | INCLUDES THE OUTSIDE CORNERS OF HIP | | | ROOFS. SEE TABLE BELOW. | | | | | | TABLE 2306.1 PALM BEACH COUNTY | | | AMENDMENTS | | | ROOF SHEATHING NAILING REQUIREMENTS | | | | | | ZONE 1 & 28D COMMON | | | 6" EDGES & 6" INTERMEDIATE | | | | | | ZONE 38DCOMMON | | | 4" EDGES & 6" INTERMEDIATE | | | | | | 4) THE INTERNAL PRESSURE COEFFECIENT ON | | | SHEETS 3 AND 4 IS MISSING THE NEGATIVE | | | SIGN. | | | | | | 5) PRODUCT APPROVALS SUBMITTED | | | WITH PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE | | | AT WWW.FLORIDABUILDING.ORG. PRODUCTS | | | WITH STATEWIDE APPROVAL ARE REQUIRED TO | | | BE SUBMITTED WITH A COVER SHEET THAT | | | LISTS THE PRODUCT IDENTITY NUMBER FROM | | | THE STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. | | | | | | 6) SUBMIT FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR THE ALUMINUM SOFFIT. | | | | | | 7) SUBMIT 2 COPIES OF A SURVEY SHOWING | | | THE LOCATION OF THE STRUCTURE ON THE | | | PROPERTY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-27 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-27 |
Time |
09:32 |
Sent To |
PC |
|
| Notes |
| 2006-07-27 00:00:00 | CHANGES ON PLANS OK'D ,DATED AND | | | INITIALED . |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-07-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-22 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-22 |
Time |
12:08 |
Sent To |
PC |
|
| Notes |
| 2006-07-22 00:00:00 | *** REDLINED PLANS *** | | | | | | TO BE REVISED BEFORE FINAL/ C.O. | | | | | | 1) NOTE: PLEASE SEE DINING RM CIRUIT | | | SHOWN AT 1000VA WHEN 1500VA MIN IS | | | REQUIRED PER 210.52B1,210.11C1,220.16 | | | | | | 2) NOTE: PLEASE SEE CU CIRCUIT SHOWS | | | 1000VA ON ONE PHASE AND 1500 VA ON THE | | | OTHER. THIS IS NOT POSSIBLE. PLEASE | | | ADJUST LOADS AND VA. | | | 408.4, 240.4, ETC | | | 106.1.2 FBC. | | | | | | 3) NOTE: PLEASE SEE ITEMS SHOWN AS | | | 1-POLE/2-POLE?? | | | | | | 4) NOTE: PLEASE VERIFY THE LOCATION OF | | | SD REQUIRED IN THE IMMEDICATE VICINITY | | | OUTSIDE BEDRMS#2, AND #3. SEE NFPA-72 | | | 11.5.1.1,11.8.3. | | | | | | 5) NOTE: PLEASE SEE GD OPENER SHOWS | | | 1000VA ON LOAD CALCULATIONS, YET SHOWS | | | 1200VA ON PANEL SCHEDULE? PLEASE | | | CORRELATE AND ADJUST. | | | 408.4, 106.1.2 | | | | | | 6) NOTE: VERIFY DEN CIRCUIT AS THIS | | | SHOWS 15A BRKR AND #12 AWG. THIS IS OK, | | | HOWEVER IF SHOWN THIS WAY THEN THIS WILL | | | BE VERIFIED. | | | | | | 7) NOTE: PLEASE SEE THE DISHPOSAL AND | | | DISHWASHER IS ONLY TO VERIFY IF THESE | | | ARE BOTH ON SEPARATE RECEPTS. IF BOTH | | | ARE FED TO ONE RECEPTS, THEN THIS RECEPT | | | MUST BE FED FROM A TWO POLE BREAKER. | | | PLEASE ONLY REVISED PANEL SCHEDULE FOR | | | 2-POLE BRKR IF INDEED ONE DEVICE/RECEPT | | | FEEDS BOTH. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE FINAL CO. IF THERE ARE ANY | | | QUESTIONS, PLEASE DO NOT HESITATE TO | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-18 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-18 |
Time |
07:26 |
Sent To |
PC |
|
| Notes |
| 2006-07-18 00:00:00 | ********* UNSAT *********** | | | | | | 1) NOTE: PLEASE CORRELATE ALL ITEMS | | | INDICATED ON LOAD CALCUALITONS WITH | | | PANEL SCHEDULE AND ITEMS ON PANEL | | | SCHEDULE WITH LOAD CALCUALTIONS. | | | 408.4,310.16,220.31 ETC | | | | | | 2) NOTE: PLEASE SEE ALL CIRCUITS ON | | | PANEL SCHEDULE. PLEASE CORRELATE ALL | | | LOADS WITH THE CORRECT OCP AND CONDUCTOR | | | SIZES. PLEASE SEE THERE ARE NUMEROUS | | | ITEMS WHICH DO NOT CORRELATE. | | | 60A OCP ON #10, | | | LOADS EXCEEDING OCP AND WIRE SIZE. | | | 8KW ON #12, | | | 5KW ON #12, | | | WIRE SHOWN AS #154? | | | PLEASE SEE MIN VA FOR SM APPLIANCE | | | CIRCUITS TO BE 1500VA MIN. | | | PLEASE LABEL SMALL APPLIANCE | | | CIRCUITS(KITCHEN OUTLETS0?? | | | | | | ** PLEASE KNOW, THIS SEEMS TO BE A | | | MISPRINTING OF THESE ITEMS. | | | PLEASE BE SURE TO GO THROUGH ALL | | | CIRCUITS WHICH ARE REQUIRED TO BE 20A | | | FOR WASHER, SM APPLIANCE, LAUNDRY , | | | DINING RM ETC AND BE SURE THE WIRE SIZE | | | CORRELATES ETC. | | | | | | 310.16,240.4,408.4, 210.52B1, 210.11C1, | | | 220.16 ETC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-07 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-07 |
Time |
12:40 |
Sent To |
PC |
|
| Notes |
| 2006-07-07 00:00:00 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE CORRELATE ALL CIRCUITING | | | ON PANEL SCHEDULE WITH THE ACTUAL | | | CIRCUIT NUMBERS. PLEASE SEE 2-POLE | | | CIRCUITS SHOULD INDEED TAKE THE SPACE OF | | | TWO CIRCUITS SPACES ON PANEL SCHEDULE. | | | PLEASE KNOW, ALL CIRCUITS FOR ROOMS AND | | | AREAS SHALL BE INDICATE ON PANEL | | | SCHEDULE SPECIFIC TO THE ROOM ETC. | | | IE; LTS BRM, RECEPTS MASTER BEDRM, BATH | | | #2 LTS. ETC | | | | | | 2) NOTE: PLEASE SEE SD IN MSTER BEDRM IS | | | REQUIRED TO BE LOCATED WITHIN 12" OF THE | | | HIGHTEST POINT ON A FLAT CEILING. | | | NFPA-72 11.8.3 | | | | | | 3) NOTE: PLEASE BE SURE PLANS CONTAIN | | | THE PRINTED NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR PLANS/DEISGN. | | | FBC ADMIN SECT 104.2.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-06-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-24 |
Time |
07:24 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-06-24 |
Time |
07:17 |
Sent To |
P |
|
| Notes |
| 2005-06-24 00:00:00 | ********* NOTES REDLINED ************ | | | | | | MISSING RECEPTS PER 21.52, 210.52E, | | | | | | MISSING DEDICATED BATH(S) CIRCUIT(S) PER | | | 210.52D,210.11C3, MUST BE 20A, #12. | | | | | | CIRCUIT #'S ON PANEL SCHEDULE DO NOT | | | CORRELATE WITH 2-POLE CIRCUITS. | | | | | | SUB PANEL NOT INCLUDED IN SCOPE OF WORK. | | | IF INSTALLED, PLEASE REVISE RISER AND | | | PROVIDE PANEL SCHEDULE | | | | | | | | | THE ABOVE ITEMS WERE REDLINED ON PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-04-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-06 |
Time |
10:11 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2005-04-06 |
Time |
10:11 |
Sent To |
M |
|
| Notes |
| 2005-04-06 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLEASE INCLUDE INFORMATION FOR | | | MAIN. IS PANEL A MCB ? IS MAIN LOCATED | | | WITH METER? | | | 215.5,240.4B,225.30 ETC. | | | | | | 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 3)NOTE: PLEASE SEE IF MAIN IS NOT | | | LOCATED AT METER, PLEASE SEE 250.6, | | | 250.24, AN EQUIPMENT GROUNDING CONDUCTOR | | | IS NOT INSTALLED FROM METER TO FIRST | | | MEANS OF DISCONNECT. | | | PLEASE SEE RISER SHOWS AN EQUIPMENT | | | GROUNDING CONDCUTOR FROM METER TO MAIN. | | | | | | 4)NOTE: PLEASE SEE RISER INDICATES A | | | POSSIBLE SUB-PANEL IF REQUIRED. IF THIS | | | IS INSTALLED, PLANS BE NEED TO BE | | | REVISED TO REFLECT ACTUAL INSTALLATION | | | TAKEN. | | | PLEASE ALSO SEE PANEL IS SHOWN WITH #5 | | | AS FEEDERS. PLEASE SEE AWG'S AVAILABLE, | | | THIS IS NOT A SIZE. PLEASE SEE 310.16 | | | | | | 5)NOTE: PLEASE SEE MISSING RECEPTS ALONG | | | KITCHEN COUNTERSPACE PER 210.52C1 | | | PLEASE SHOW ALL RECEPTS SERVING KITCHEN | | | COUNTERSPACE AS GFI/GFI PROTECTED PER | | | 210.8A-6 | | | | | | | | | 6)NOTE: PLEASE CORRELATE PANEL SCHEDULE | | | AND LOAD CALCAULTIONS. PLEASE SEE THERE | | | ARE NUMEROUS ITEMS THAT DO NOT | | | CORRELATE. | | | IE: WELL PUMNP, DISPOSAL, FRIG, A/C | | | UNITS, DISHWASHER, WASHER/LANUDRY, | | | RANGE, ETC. | | | | | | 7)NOTE: PLEASE ALSO SEE MANY "MISPRINTS" | | | ON PANEL SCHEDULE. PLEASE SEE 2-POLE | | | CIRCUITS, SHOWING A REDUCED AWG AND OCP | | | ON "B" PHASE. | | | | | | 8)NOTE: PLEASE CORRELATE PLANS, PANEL | | | SCHEDULE AND LOAD CALCULATIONS FOR | | | RANGE, OVENS. | | | PLEASE SEE PLANS INDICATE DOUBLE OVENS, | | | YET THIS IS NOT ON PANEL SCHEDULE OR | | | LOAD CALCS. PLEASE SEE PLANS INDICATE A | | | SEPARATE COOKTOP ALSO, YET THIS IS NOT | | | ON PANEL SCHEDULE OR LOAD CALCS. | | | PLEASE SEE PANEL SCHEDULE SHOWS 13KW2-P | | | 60A FOR RANGE??? | | | PLEASE SEE LOAD CALCS SHOWS 8KW? | | | ETC. | | | | | | 9)NOTE: PLEASE SEE PLANS FOR MISSING | | | RECEPTS PER 210.52 | | | | | | 10)NOTE: PLEASE SEE MISSING DISCONNECT | | | FOR A/C COND UNIT PER 440.11 | | | PLEASE SHOW. | | | | | | 11)NOTE: PLEASE SEE FBC 104.2.1, WHICH | | | REQUIRES THE PRINTED NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR PLANS. | | | PLEASE THE PLANS ONLY NEED THE PRINTED | | | NAME. | | | | | | 12)NOTE: PLEASE SEE ONE SET OF PLANS HAS | | | BEEN REDLINED AT LOCATIONS FOR THE ABOVE | | | COMMENTS. PLEASE SEE THESE LOACTIONS | | | SHOWN ON PLANS. | | | | | | 13)NOTE: PLEASE REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETED SETS FOR | | | REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE SET OF OLD/VOIDED | | | SHEETS FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-27 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-27 |
Time |
09:14 |
Sent To |
E |
|
| Notes |
| 2006-07-27 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2006-07-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-22 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-22 |
Time |
11:58 |
Sent To |
E |
|
| Notes |
| 2006-07-22 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2006-07-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-17 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-17 |
Time |
13:08 |
Sent To |
E |
|
| Notes |
| 2006-07-17 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-07-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-05 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-05 |
Time |
14:39 |
Sent To |
E |
|
| Notes |
| 2006-07-05 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2005-10-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-12 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-12 |
Time |
16:34 |
Sent To |
B |
|
| Notes |
| 2005-10-12 00:00:00 | TO "RMCDOUGAL" DESK/RESTAMP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2005-09-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-08 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-08 |
Time |
18:23 |
Sent To |
P |
|
| Notes |
| 2005-09-08 00:00:00 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-09-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-02 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-02 |
Time |
14:26 |
Sent To |
Z |
|
| Notes |
| 2005-09-02 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-08-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-25 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-25 |
Time |
11:37 |
Sent To |
P |
|
| Notes |
| 2005-08-25 00:00:00 | TO "P" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-08-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-18 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-18 |
Time |
15:33 |
Sent To |
Z |
|
| Notes |
| 2005-08-18 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-20 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-20 |
Time |
16:12 |
Sent To |
E |
|
| Notes |
| 2005-06-20 00:00:00 | TO DVP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-20 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-20 |
Time |
11:56 |
Sent To |
E |
|
| Notes |
| 2005-06-20 00:00:00 | TO DVP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-06-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-14 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-14 |
Time |
16:56 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-06 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-06 |
Time |
09:09 |
Sent To |
E |
|
| Notes |
| 2005-04-06 00:00:00 | TO "SFR""E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-05-04 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-04-01 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2005-04-01 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-08-30 |
Time |
15:13 |
Rev Time |
0.50 |
| Received By |
prafter |
Date |
2005-07-21 |
Time |
09:22 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2005-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-05-03 |
Time |
16:14 |
Rev Time |
0.50 |
| Received By |
prafter |
Date |
2005-04-08 |
Time |
11:08 |
Sent To |
B |
|
| Notes |
| 2005-04-08 00:00:00 | MECH. PLAN REVIEW. | | | PROVISO: PROVIDE FOR DRYER VENTING TO | | | EXT. OF BUILDING. | | | | | | PAT RAFTER 805/6728 0R 805/6719 PATTY | | | KRAUSS. | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-09-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-10 |
Time |
06:36 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-09-10 |
Time |
06:36 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-08-29 |
Time |
08:52 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-08-29 |
Time |
08:52 |
Sent To |
B |
|
| Notes |
| 2005-08-29 00:00:00 | DENIED; | | | SECOND REQUEST. | | | RISER DIAGRAM DOES NOT REFLECT THE FLOOR | | | PLAN. BATHROOM # 3 IS MISSING FROM RISER | | | DIAGRAM. SHOW KITCHEN SINK AS A SINK NOT | | | A LAV. | | | PLUMBIG PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-28 |
Time |
14:25 |
Rev Time |
0.68 |
| Received By |
kstevens |
Date |
2005-06-28 |
Time |
14:25 |
Sent To |
M |
|
| Notes |
| 2005-06-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT 1 SANITARY RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN. BATH #3 IS NOT | | | SHOWN ON THE RISER DIAGRAM. SANT. PIPING | | | SHALL REFLECT THE INSTALLATION OF THE | | | PIPING. SEE ATTACHED SHEET FOR EXAMPLE | | | OF A RISER DIAGRAM THAT REFLECT THE | | | FLOOR PLAN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-04-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-04-07 |
Time |
18:15 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-04-07 |
Time |
18:02 |
Sent To |
M |
|
| Notes |
| 2005-04-07 00:00:00 | NAME OF PERSON RESPOSABLE FOR DRAWING | | | NEED TO PRINT NAME ON DRAWINGS. | | | NO SEPTIC TANK PERMITED PUBLIC SEWER AT | | | PROERTY LINE | | | PLUMBING RISER IS 180 DEGREES FROM FLOOR | | | PLAN AND MISSING KITCHEN SINK PLEASE FIX | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2005-09-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-08 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-08 |
Time |
16:04 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2005-08-23 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-08-23 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-08-23 |
Time |
17:22 |
Sent To |
I |
|
| Notes |
| 2005-08-23 00:00:00 | DENIED, | | | 1. PROPOSED DRIVEWAY HAS EXCEEDED 1000SQ | | | FT OR 75% OF LANDSCAPE WITHIN THE 25FT | | | FRONT SETBACK. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2005-06-17 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-06-17 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-06-17 |
Time |
18:41 |
Sent To |
I |
|
| Notes |
| 2005-06-17 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE THE DIMENSION OF THE | | | PROPOSED DRIVEWAY WIDTH & LENGTH. | | | WITHOUT THE DIMENSION CANNOT CALCULATE | | | THE REQUIRED SQ FT ALLOWED. | | | | | | **MUST HAVE 1000SQ FT OR 75% OF | | | LANDSCAPE WITHIN THE FRIST 25FT FRONT | | | SETBACK** | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-04-05 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-04-05 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-04-05 |
Time |
09:39 |
Sent To |
I |
|
| Notes |
| 2005-04-05 00:00:00 | DENIED, | | | 1. MUST PROVIDE TWO COPY OF SURVEY | | | SHOWING THE WORK, WITH SETBACKS | | | (FRONT/SIDE/REAR). | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|