Plan Review Details - Permit 05031751
Plan Review Stops For Permit 05031751
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-06-29 Cont ID  
Sent By jleech Date 2005-06-29 Time 17:44 Rev Time 0.50
Received By jleech Date 2005-06-29 Time 17:44 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-04-14 Cont ID  
Sent By kstevens Date 2005-04-14 Time 08:20 Rev Time 0.50
Received By kstevens Date 2005-04-14 Time 08:15 Sent To  
Notes
2005-04-14 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
  
 1) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1.
 2) SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - PLEASE SHOW
 THE DISTANCE TO THE MOST REMOTE OUTLET
 IN THE RESIDENCE. (EXISTING GAS LINE)
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-15 Time 14:56 Rev Time 0.00
Received By shill Date 2005-06-15 Time 14:56 Sent To G
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date 2005-04-01 Time 10:55 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 10:55 Sent To G
Notes
2005-04-01 00:00:00TO "G" BOX