Plan Review Details - Permit 05031638
Plan Review Stops For Permit 05031638
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-28 Cont ID  
Sent By alange Date 2005-06-28 Time 08:00 Rev Time 1.50
Received By alange Date 2005-06-28 Time 06:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By alange Date 2005-05-20 Time 14:37 Rev Time 2.50
Received By alange Date 2005-05-20 Time 11:29 Sent To  
Notes
2005-05-20 00:00:00DENIED
  
 1.COMPLETE ENERGY CALCS AND SIGN
 OWNER/AGENT.
  
 2.SUBMIT 2 COPIED OF PRODUCT APPROVALS
 FOR LINTELS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 4.PLANS CALL OUT FOR IMPACT GLASS.
 PGT WINDOW PRODUCT APPROVALS ARE FOR
 NON-IMPACT GLASS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-22 Cont ID  
Sent By dpalmer Date 2006-02-22 Time 19:31 Rev Time 0.00
Received By dpalmer Date 2006-02-22 Time 19:16 Sent To PC
Notes
2006-02-22 00:00:00REDLINED 210.11C3, POOL BATH, 20A , #12
 TO VIF.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 17:45 Rev Time 0.30
Received By dpalmer Date 2005-07-06 Time 17:29 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-23 Cont ID  
Sent By dpalmer Date 2005-06-23 Time 09:27 Rev Time 1.00
Received By dpalmer Date 2005-06-23 Time 09:06 Sent To M
Notes
2005-06-23 00:00:00************* UNSAT **************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDDRESSED AND
 NEW NOTES DUE TO CHANGES IN PLANS.
  
 1)NOTE: PLEASE SEE SEE 2 MCB PANELS ARE
 NOW INDICATED ON RISER, HOWEVER ONLY ONE
 PANEL "A" IS SHOWN ON PLANS. PLEASE
 LOCATION OF PANEL "B". PLEASE SEE 230.72
 FOR GROUPING OF MAINS.
 PLEASE SEE PANELS ARE INDICATED AS 42
 CIRCUIT ON RISER, HOWEVER PANEL
 SCHEDULES INDICATE 30 CIR?
  
 2)NOTE: PLEASE SEE SIZE OF GROUNDING
 ELECTRODE CONDUCTOR IS MISSING. PLEASE
 SEE 250.50,250.66 FOR SIZING. #2 MIN.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULES ARE
 NOW SHOWN, HOWEVER PLEASE SEE LOADS FOR
 EACH ARE NOT SHOWN. PLEASE SHOW LOAD FOR
 EACH. 220,215.5
 PLEASE ALSO COIRRELATE PANEL SCHEDULES
 AND LOAD CALCULATIONS. PLEASE SEE THERE
 ARE ITEMS LISTED ON LOAD CALCS, BUT NOT
 ON PANEL SCHEDULE AND ITEMS ON PANEL
 SCHEDULES, BUT NOT ON LOAD CALCS.
 PLEASE SEE REDLINED SET.
 COOKTOP,OVEN, SMALL APPL
  
 4)NOTE: PLEASE SEE NEC 220.31 ETC FOR
 MIN LOADS TO BE INDICATED. PLEASE SEE
 ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%. POOL PUMP, POOL HEAT PUMP,,
 215.3,230.42 ETC.
  
 5)NOTE: PLEASE SEE TANKLESS WATER
 PRODUCT CUT SHEETS STILL NEED TO SHOW
 SOME SORT OF LISTINGS FROMA NRTL.
 110.3 PLEASE SEE A MIAMI-DADE PRODUCT
 APPROVAL IS NOT ON THE LIST OF A NRTL.
 NATIONALLY RECOGNIZED TESTING
 LABORATORY; UL, CSA, ETL, MET, TUV, ETC
 ** NOTE, IF LOCATED UNDER SINK, ALL MIN
 CLEARENCE SHALL BE MAINTAINED AND IF OCP
 IS PROVIDED IN RFEQUIRED DISCONNECTING
 MEANS, CLEARENCE PER 110.26 SHALL BE IN
 EFFECT. A DISC IS REQUIRED, HOWEVER NOT
 OCP AT THAT LOCATION.
 PLEASE ALSO SEE TANKLESS WATER HEATER IS
 SHOWN ON A 30A 120V CIRCUIT, THIS WOULD
 BE 50+ AMPS. PLEASE CORRELATE KW RATING
 WITH SPEC SHEETS, PLEASE ALSO SEE IF
 THIS UNIT IS INDEED 220V PLEASE ADJUST
 PANEL SCHEDULE.
 PLEASE SEE SOME SHEETS STILL SHOW UNIT
 IN CLOSET.
  
 6)NOTE:PLEASE SEE RECEPTS STILL MISSING
 UNDER 210.52 THESE HAVE BEEN REDLINED
 FOR ALL LOCATIONS.
  
 7)NOTE: PLEASE VERIFY KITCHEN AREA WHICH
 APPEARS TO HAVE A COUNTERSPACE W/OUT A
 GFI. ?? 210.52C1
  
 8)NOTE: PLEASE SEE 210.11C1,220.16
 210.52B WHICH REQUIRES A MIN OF TWO
 SMALL APPLIANCE CIRCUITS. PLEASE SEE
 ONLY ONE IS SHOWN ON LOAD CALCS AND
 PANEL SCHEDULE DOES NOT INDICATE SM APPL
 ??KITCHEN OUTLETS??
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO SETS. ONE COPY OF OLD SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED ON PLANS FOR LOCATIONS OF
 NOTES.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-01 Cont ID  
Sent By dpalmer Date 2005-04-01 Time 16:56 Rev Time 0.75
Received By dpalmer Date 2005-04-01 Time 16:45 Sent To M
Notes
2005-04-01 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT COMPLETED PLANS:
 PANEL SCHEDULE(S) SHOWING ALL MIN
 REQUIRED CIRCUITING PER 2002 NEC.
 PLEASE INCLUDE OCP/AWG'S ETC.
 215.5
  
 2)NOTE: PLEASE SEE RISER SHOWS AN
 ADDITIONAL 150A MCB PANELAND MENTIONS
 "IF REQUIRED" PLEASE CLARIFY.
 PLEASE ALSO INCLUDE THIS PANEL"B" ON
 PLANS IF IT WILL BE USED/INSTALLED.
 UNABLE TO VERIFY THIS DUE TO PREVIOUS
 COMMENT.
 PLEASE SEE BOTH OF THESE 150A MCB PANELS
 ARE SHOWN WITH #10 AWG. PLEASE SEE THIS
 BEING A POSSIBLE MISPRINT.
 310.15B6,215.5
  
 3)NOTE: PLEASE SEE NUMEROUS RECEPTS
 SHOWN ON PLANS WHICH ARE NOT SHOWN AS
 GFI, OR GFI PROTECTED.
 PLEASE SEE 210.8 FOR GARAGE, FRONT/ REAR
 OUTSIDE, 6' OF SINKS, ETC ETC.
  
 ** THIS IS ONLY A NOTE**
 PLEASE SEE THERE IS ONLY ONE RECEPT
 SHOWN ON OUTSIDE/REAR SMALL PATIO.
  
 4)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52 IN LIV RM.
  
 5)NOTE: PLEASE SUBMIT MANUFACTURE SPEC
 SHEETS FOR "TANKLESS WATER " SHOWN IN
 CLOTHES CLOSET. PLEASE SEE THIS IS NOT
 PERMITTED IN CLOSET PER 422.17
 PLEASE BE SURE PAPERWORK INCLUDE NRTL
 LISTING.
  
 6)NOTE: PLEASE SEE PLANS SHOWS A PANEL
 FOR "STRUCTURE WIRING"??
 PLEASE SUBMIT INFORMATION ON THIS
 SYSTEM, INCLUDING ALL SPECS FROM
 MANUFACTURE. MUST SUBMIT ALL INFORMATION
 UNDER THESE PLANS OR SEPARATE PERMIT
 WILL BE REQUIRED.
  
 7)NOTE: PLEASE INCLUDE LOAD CALCULATIONS
 AS REQUIRED UNDER 220.31, ETC.
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 215.5
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 13:06 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 13:06 Sent To E
Notes
2006-02-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 14:59 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 14:59 Sent To E
Notes
2005-07-06 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 13:50 Rev Time 0.00
Received By shill Date 2005-06-20 Time 13:50 Sent To E
Notes
2005-06-20 00:00:00TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date 2005-04-01 Time 14:14 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 14:14 Sent To E
Notes
2005-04-01 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-20 Cont ID  
Sent By alange Date 2005-05-20 Time 14:38 Rev Time 0.00
Received By alange Date 2005-03-29 Time 15:47 Sent To  
Notes
2005-03-29 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-24 Cont ID  
Sent By pkrauss Date 2005-06-24 Time 15:25 Rev Time 0.35
Received By pkrauss Date 2005-06-24 Time 14:30 Sent To B
Notes
2005-06-24 00:00:00PROVISO:
 PLANS APPROVED BY PAT RAFTER 4-5-05.
 FIREPLACE INSTALLATION SHALL COMPLY WITH
 MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-05 Cont ID  
Sent By prafter Date 2005-04-05 Time 10:53 Rev Time 0.45
Received By prafter Date 2005-04-05 Time 10:53 Sent To P
Notes
2005-04-05 00:00:00MECH. PLAN REVIEW.
  
 FIRE PLACE MANF. PRODUCT APPROVAL
 INFORMATION REQUIRED FOR FIRE PLACE.
  
 PAT RAFTER 805/6728 OR 805/6719 PATTY
 KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-04-07 Cont ID  
Sent By jleech Date 2005-04-07 Time 17:35 Rev Time 0.25
Received By jleech Date 2005-04-07 Time 17:35 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-31 Cont ID  
Sent By mmclean Date 2005-03-31 Time 16:24 Rev Time 0.00
Received By mmclean Date 2005-03-31 Time 16:24 Sent To I
Notes
2005-03-31 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/SCREEN ENCLOSURE/DECK/SPA