Plan Review Details - Permit 05031516
Plan Review Stops For Permit 05031516
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2005-04-19 Cont ID  
Sent By jwitmer Date 2005-04-19 Time 08:14 Rev Time 1.11
Received By jwitmer Date 2005-04-19 Time 08:14 Sent To  
Notes
2005-04-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031516
 ADD: 515 N FLAGLER DR# 1600
 CONT:HOLT-LEE CONST
 TEL: (954)270-1895
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION:DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) 412.6.1 ALL ELEVATORS ON ALL FLOORS
 SHALL OPEN INTO ELEVATOR LOBBIES WHICH
 ARE SEPERATED FROM THE REMAINDER OFTHE
 BUILDING BY A 1-HOUR FIRE RATED
 CONSTRUCTION WITH 20-MINUTE OPENING
 PROTECTIVES. SEE 412.6.2 FOR ALLOWABLE
 OPENINGS REQUIRED FOR ACCESS.
  
 4) 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.SEE EXISTING DOORS AT
 SERVER AND ROOM 1619. SEE
 DISPROPORTIONATE COST 11-4.1.6(2)
  
 5) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DETAIL 06 ON PAGE A-3.0 INDICATES
 CONSTRUCTION OF A SOFFIT BUT NO MENTION
 OF THE FASTENING ATTACHMENT TO THE
 STRUCTURAL DECK ABOVE? OR TYPE OF DECK?
  
 6) TI-1 DETAIL# 3 INDICATES WOOD
 SUB-BUCKS NO MENTION OF FIRE RETARANT
 TREATED WOOD, 609.2.1.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-19 Cont ID  
Sent By jwitmer Date 2005-04-19 Time 08:42 Rev Time 1.11
Received By jwitmer Date 2005-04-19 Time 08:42 Sent To  
Notes
2005-04-19 00:00:00SEE AD STOP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-30 Cont ID  
Sent By dpalmer Date 2005-03-30 Time 17:01 Rev Time 0.40
Received By dpalmer Date 2005-03-30 Time 17:01 Sent To  
Notes
2005-03-30 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SEE PLANS SUBMITTED FOR
 ELECTRICAL IN BOTH SETS ARE SIGNED,
 HOWEVER NEITHER SET IS SEALED.
 PLEASE SEE FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-04-11 Cont ID  
Sent By mwennerg Date 2005-04-11 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2005-04-11 Time 14:15 Sent To  
Notes
2005-04-11 00:00:001) FIRE EXTINGUISHERS ARE TO BE SPACED
 SO AS NOT TO EXCEED 75 FEET TRAVEL
 DISTANCE TO REACH AN EXTINGUISHER.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 11:14 Sent To  
Notes
2005-03-29 00:00:00TO "COMM" BD#13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-11 Cont ID  
Sent By pkrauss Date 2005-04-11 Time 07:35 Rev Time 0.55
Received By pkrauss Date 2005-04-11 Time 07:18 Sent To  
Notes
2005-04-11 00:00:00PROVISO:
 PLAN SHEET M-2, CONDENSING UNIT DETAIL;
 CLEARANCE FOR THE CONDENSING UNIT
 LOCATED ON THE ROOF SHALL COMPLY WITH
 2001 FBC TABLE 1511.7.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-04-23 Cont ID  
Sent By kstevens Date 2005-04-23 Time 14:08 Rev Time 0.75
Received By kstevens Date 2005-04-23 Time 14:08 Sent To  
Notes
2005-04-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) WATER HEATER REQUIRES A PAN PER
 SECTION 504.8
 2) PAN DRAIN SHALL EXTEND FULL-SIZE AND
 TERMINATE OVER A SUITABLY LOCATED
 INDIRECT WASTE RECEPTOR. SECTION 504.8.
 THE SANT TRAP OF THE SINK IS NOT
 APPROVED. SECTIONS 802.3 & 802.3.2.
 3) THE RELIEF VALVE SHALL DISCHARGE
 FULL SIZE TO A SAFE PLACE OF DISPOSAL,
 SHALL NOT SHALL NOT HAVE ANY TRAPPED
 SECTIONS, AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS THE WATER HEATER. SECTION
 504.7.
 4) WHERE DEVICES SUCH AS FILTERS
 DISCHARGE NONPOTABLE WATER TO THE
 BUILDING DRAINAGE SYSTEM, THE DISCHARGE
 SHALL BE THROUGH AN INDIRECT WASTE PIPE.
 SECTION 802.1.4 - SUBMIT A DETAIL
 SHOWING HOW THIS WILL BE ACCOMPLISHED.
 5) SHT P-1 AIR HAMMER ARRESTORS ARE
 REQUIRED AT THE DISHWASHER AND THE ICE
 MAKER, AND SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS. SECTION 604.9
 5) SHT A-3.0 DETAIL 01 INDICATE
 COMPLIANCE WITH SECTIONS 11-4.24.6 &
 11-4.24.7, EXPOSED PIPES AND SURFACES
 AND FAUCETS.
 6) WATER HEATERS SHALL BE LOCATED AND
 CONNECTED SO AS TO PROVIDE ACCESS FOR
 OBSERVATION, AMINTENANCE, SERVICING AND
 REPLACEMENT. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]