Plan Review Details - Permit 05031504
Plan Review Stops For Permit 05031504
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-04 Cont ID  
Sent By jwitmer Date 2006-01-04 Time 15:57 Rev Time 16.00
Received By jwitmer Date 2006-01-03 Time 15:57 Sent To PC
Notes
2006-01-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031504
 ADD: 2323 N FLAGLER DR BLDG. "E"
 BARCELONA SQUARE I
  
 CONT:FIRST BLDG CORP OF FLORIDA
 TEL:(954)561-4900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 NOTE IF A COMMENT IS MADE ON A
 PARTICULAR SHEET THIS COMMENT MAY NOT
 APPEAR ON OTHER SHEET.LOOK FOR COMMENTS
 BY OTHER PLAN REVIEW DISCIPLINES THAT
 MAY BE WRITTEN ON THE APPLICATION,
 PLANS, OR ATTACHED SEPARETLY. WHEN
 RESUBMITTING PLANS PLEASE CLEARLY
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT . THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)COMMENT# 6 FROM THE PEVIOUS REVIEW,
 SHEET A2.01, A2.02 REFERNCES THE TERM
 "TOWNHOUSE", THE LEGAL TERM (DEFINITION)
 IS A SINGLE FAMILY DWELLING CONSTRUCTED
 IN A SERIES OF ATTACHED UNITS WITH
 PROPERTY LINES SEPERATING EACH UNIT. SEE
 DEFINITIONS. THE TRM HAS BEEN REMOVED
 FROM THE ARCHITECTURAL SHEETS BUT NOT
 THE LIFE SAFETY NOR THE M-E-P SHEETS.
  
 3) COMMENT# 9 FROM THE PREVIOUS REVIEW,
 THE PRIMARY ENTRY DOOR OF COVERED
 DWELLING UNITS IS PART OF PUBLIC AND
 COMMON USE SPACES, THEREFORE, IT MUST BE
 ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE,
 I.E., MEET THE ANSI REQUIREMENTS OF
 4.13 DOORS. ANSI 4.13.9 LEVER OR OTHER
 EASY USE DOOR HARDWARE.
 THE UNITS LOCATED ON THE S.W. CORNER
 DO NOT HAVE AN ACCESSIBLE ROUTE TO THE
 WEST LOBBY SINCE THERE ARE STAIRS AND NO
 ACCESSIBLE RAMP.
  
 4) COMMENT# 37 & 38 FROM THE PREVIOUS
 REVIEW, DEAL WITH PRODUCT APPROVALS,
 4A) EXTERIOR LOUVERED DOORS NO REPORTS
 WERE SUBMITTED.
 4B) GLAZED DOORS, ARCH FRENCH DOORS,
 THE PRODUCT APPROVALS SUBMITTED HAVE
 DESIGN PRESSURES OF +62.6/ -64.0. THE
 REPORT DOES NOT INDICATE SIDELIGHTS.
 WHEN LOOKING AT THE ELEVATIONS THE
 SIDELIGHT IS CLEARLY LOCATED IN THE END
 ZONES REQUIRING THE HIGHER PRESSURES.
 A STRUCTURAL MULLION WITH THE REQUIRED
 VALUES FOR THE END ZONE COULD SEPERATE
 THE SIDELIGHT AND DOOR FRAME. THE
 DESIGNER WILL NEED TO INDICATE HOW THEY
 WILL TRANSFER THE LOADS OR THE
 CONTRACTOR WILL NEED TO PROVIDE PRODUCT
 TESTING REPORTS FOR THE PATIO DOORS WITH
 THE HIGHER ASSOCIATED PRESSURES.
 4C) THE REPORT SUBMITTED ARCH FRENCH
 DOORS IS FOR SMALL MISSLE HOW WILL YOU
 DEAL WITH THE DOORS LOCATED IN THE END
 ZONE REQUIRING SHUTTERS 30' TO GRADE.
 4D) PGT FIXED WINDOWS, THE WINDOWS
 LOCATED IN THE END ZONES WILL NEED TO
 MEET THE REQUIRED -122.4 SEE BOTTOM OF
 THE TYPE "C" WINDOWS AND THE WINDOWS
 NEXT TO GLASS DOORS LOCATED IN THE END
 ZONE.
 4E) SUNSHINE WINDOWS SINGLE HUNG LOCATED
  
 IN THE END ZONES WILL REQUIRE DESIGN
 PRESSURES OF +98/ -168.3.
  
 5) COMMENT# 43 FROM THE PREVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6)PLEASE PROVIDE A SQ FTBREAKDOWN OF
 THE FLOOR AREAS PER FLOOR TO PARKING,
 A/C AND POOL DECK. THE CALCULATED AREA
 THAT I CAME UP WITH IS 338,379 SQ FT.
 THIS WILL TRANSLATE INTO A CALCULATED
 VALUE OF $26,289,000.00 WHICH WILL
 EFFECT PERMIT FEES AND RADON FEES.
  
 7) SEE MECHANICAL COMMENT# 6 AS TO
 NOXIOUS EXHAUST TERMINATING OVER THE
 EXIT AND WITHIN 10' OF WINDOWS.
  
 8) NOTE: A SEPERATE PERMIT WILL BE
 REQUIRED FOR AWNINGS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-18 Cont ID  
Sent By jwitmer Date 2005-04-18 Time 13:09 Rev Time 18.00
Received By jwitmer Date 2005-04-14 Time 13:50 Sent To  
Notes
2005-04-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031504
 ADD: 2323 N FLAGLER DR
 CONT:FIRST BLDG CORP OF FLORIDA
 TEL:(954)561-4900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE IF A COMMENT IS MADE ON A
 PARTICULAR SHEET THIS COMMENT MAY NOT
 APPEAR ON OTHER SHEET.
  
 LOOK FOR COMMENTS BY OTHER PLAN REVIEW
 DISCIPLINES THAT MAY BE WRITTEN ON THE
 APPLICATION, PLANS, OR ATTACHED
 SEPARETLY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NESSARY.
 A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND,
 WILL HELP EXPEDITE YOUR PERMIT . THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 4) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 5) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6) SHEET A2.01, A2.02 REFERNCES THE TERM
 "TOWNHOUSE", THE LEGAL TERM (DEFINITION)
 IS A SINGLE FAMILY DWELLING CONSTRUCTED
 IN A SERIES OF ATTACHED UNITS WITH
 PROPERTY LINES SEPERATING EACH UNIT. SEE
 DEFINITIONS.
  
 7) SHEET A2.00 DOESN'T INDICATE THE
 STRUCTURAL WALL LINE ON THE WEST END OF
 THE LOWER PARKING PLAN, 104.2.1.2*
 ADDITIONAL INFORMATION REQUIRED.
  
 8) A2.01 DOESN'T INDICATE BARRIERS IN
 THE STAIRWELLS THAT LEAD TO BELOW GRADE.
 SEE 1005.6.6 A STAIRWAY IN A SMOKEPROOF
 ENCLOSURE SHALL NOT CONTINUE BELOW THE
 GRADE LEVEL UNLESSS AN APPROVED BARRIER
 IS PROVIDED AT THE GROUND LEVEL TO
 PREVENT PERSONS FROM ACCIDENTALLY
 CONTINUING INTO THE BASEMENT.
  
 9) THE PRIMARY ENTRY DOOR OF COVERED
 DWELLING UNITS IS PART OF PUBLIC AND
 COMMON USE SPACES, THEREFORE, IT MUST BE
 ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE,
 I.E., MEET THE ANSI REQUIREMENTS OF
 4.13 DOORS. ANSI 4.13.9 LEVER OR OTHER
 EASY USE DOOR HARDWARE.
 THE UNITS 110-116 HAVE STAIRS ON THE
 ENTERNAL HALLWAYS MAKING THEM
 INACCESSIBLE TO THE HANDICAPPED.
  
 10) 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE FOLLOWING:
 SHEETA2.01 CORRIDOR 133, THE DOOR
 LEADING INTO CORRIDOR 132 SHOULD HAVE A
 REVERSED SWING, DIRECTION OF TRAVEL IN A
 EXIT.
  
 11A) CORRIDOR 132 (SHEET A4.04)
 INDICATES THAT THERE IS A ENTRANCE INTO
 UNIT# 116, THIS CORRIDOR IS AN EXTENSION
 OF THE 2 HR RATED STAIRWAY, A EXIT
 PASSAGE SHALL HAVE THE SAME RATING AS
 THE STAIRWAY, 1005.6.5A SMOKEPROOF
 ENCLOSURE SHALL EXIT INTO A PUBLIC WAY
 OR INTO AN EXIT PASSAGE, YARD OPEN COURT
 OR OPEN SPACE HAVING DIRECT ACCESS TO A
 PUBLIC WAY. THE EXIT PASSAGE SHALL BE
 WITHOUT OTHER OPENINGS AND SHALL HAVE
 WALLS,FLOORS, AND CEILING OF 2-HR FIRE
 RATING.
  
 11B) THIS SAME CORRIDOR ALSO HAS A
 STORAGE ROOM DOOR THAT OPENS INTO THIS
 2HR EXIT PASSAGE, 1005.6.5.
  
 11C) A4.04, CORRIDOR# 132, THE DOOR
 SCHEDULE FOR THE FIRST FLOOR (A9.02)
 INDICATES DOORS 10,11) TO HAVE THE WRONG
 NUMBER IDENTIFYING THEM, AND RATING.
  
 11D) A9.02 DOOR SCHEDULE FOR THE
 TOWNHOUSE AND FIRST FLOOR LEVEL ARE
 NUMBERED THROUGH TO 30, THERE OTHER
 MISSING NUMBERED WITH AN IDENTIFYING
 NUMBER HIGHER THAN THIS.
  
 11E) THE TOWNHOUSE ENTRY DOORS ARE NOT
 IDENTIFIED & NOT INCLUDED IN THE DOOR
 SCHEDULE NOR RATING.
  
 12) SHEET A2.01 CORRIDOR# 138:
 1003.2.7.2 WHERE CHANGES IN ELEVATION OF
 12 IN.(305 MM) OR LESSOCCUR IN
 EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH ?1013
 SHALL BE PROVIDED.
  
 13) SHEET A4.01:
 A) ALL TOWNHOUSE ENTRY DOORS LEADING
 FROM THE GARAGE TO THE UNITS ARE NOT
 INCLUDED ON DOOR SCHEDULE NOR RATING.
  
 B) DOOR #21 IN DOOR SCHEDULE IS
 INDICATING BEING INSTALLED IN THE MECH
 ROOM, NO FIRE RATING TABLE 705.1.2
  
 C) TRASH ROOM DOORS #22 TO BE 3/4 HR
 RATING, T ABLE 705.1.2 SAME WITH #23
  
 D)STAIR TOWER DOOR #31 NOT LISTED IN
 DOOR SCHEDULE, NO RATING
  
 E) POWDER ROOM & CLOSET DOORS ARE NOT
 IDENTIFIED.
  
 F) BOTTOM LEFT CORNER "BARRIER CABLES"
 SEE DETAIL 7/A8.02 WRONG REFRENCE?
 SAME REFRENCE ON A4.02
  
 G) SEE 11-4.1.3(8)(D) ENTRANCES THAT ARE
 NOT ACCESSIBLE SHALL HAVE DIRECTIONAL
 SIGNAGE COMPLYING WITH 11-4.30.1,
 11-4.30.2, 11-4.30.3 & 11-4.30.5.
  
 H) A4.01 UNIT# 111, COMMON TO QUITE A
 FEW UNITS, ANSI 4.13.6. THERE IS TO BE
 18" CLEAR ON THE LATCH SIDE OF THE DOOR
 (PULL SIDE) FOR ACCESSIBLE DOORS.THIS IS
 FOR DOORS LOCATED IN COMMON AREAS ALSO.
 NOTE USABLE DOORS SHALL REQUIRE A CLEAR
 32 INCHES.USABLE DOORS ARE SECONARY
 ENTRANCE DOORS OR DOORS THAT ALLOW FOR
 PASSAGE WITHIN THE DWELLING UNIT.
  
  
 14) SHEET A4.03
 A) STAIRWELL NOT LABELED, MAYBE #5: THIS
 SHALL APPLY TO ALL STAIRS, AT THE BOTTOM
 OF LANDINGS UNDER THE STAIR CARRIAGE,
 11-4.4.2 HEAD ROOM, IF VERTICAL
 CLEARENCE OF AN AREA ADJOINING AN
 ACCESSIBLE ROUTE IS REDUCED TO LESS THAN
 80"INCHESA BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE
 PROVIDED.
  
 B) PROVIDE ADDITIONAL INFORMATION ON
 TECTUM FINALE PANELS, PROVIDE FIRE
 RATINGS,
  
 C) CORRIDOR 132 DOESN'T PROVIDE VERTICAL
 ACCESSIBILITY, NO RAMP. 11-4.1.2
 VERTICAL ACCESSIBILITY, NOTHING IN THIS
 CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, SSTRUCTURE OR
 FACILITY FROM THE DUTY TO PROVIDE
 VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE OR BELOW THE OCCUPIAABLE GRADE
 LEVEL.
  
 D) CORRIDOR #132 DOOR #02 MISSING THE
 1 1/2 HR RATING, TABLE 705.2.1.
  
 15) SHEET A4.05:
 A) INDICATES 2 UNITS THAT
 DO NOT MEET THE ACCESSIBILTY
 REQUIREMENTS FOR FAIR HOUSING.SEE 1.21
 BUILDINGS WITH ELEVATORS.
  
 B) SHEET A4.04/ A4.05 INDICATE STAIRS
 WITHIN THE 1ST FLOOR, NOT THE STAIRS TO
 THE SECOND FLOOR OF THE UNIT. THE FIRST
 FLOOR IS TO BE ACCESSIBLE.FAIR HOUSING
 INDICATES ON PAGE 1.22 THAT UNITS THAT
 ARE SERVICED BY AN ELEVATOR ARE TO BE
 ACCESSIBLE FOR THAT FLOOR.ELEVATORS MUST
 PROVIDE ACCESS TO PRIMARY ENTRY DOORS OF
 TWO-STORY DWELLING IN ELEVATOR BUILDINGS
 SEE FAIR HOUSING GUIDELINES ON PAGE 4.4
 CHANGES IN LEVEL. WITHIN SINGLE STORY
 DWELLING UNITS( AND ON THE PRIMARY ENTRY
 LEVEL OF A MULTISTORY DWELLING UNITS IN
 BUILDINGS WITH ELEVATORS) THE MAXIMUM
 VERTICAL FLOOR LEVEL CHANGE IS 1/4 INCH,
 EXCEPT WHEN A TAPERED THRESHOLD IS USED
 ,THE MAXIMUM HEIGHT IS 1/2 INCH.
  
 16)SHEET A4.06
 A) PLANS INDICATE A 1/2 INCH DIFFERENCE
 IN GRADE AT THE ENTRANCE TO EACH
 DWELLING UNIT, THE DETAILS ON A9.10
 STOREFRONT DETAIL "B" INDICATE A 3/4"
 CHANGE IN GRADE PLUS THE THRESHOLD.SEE
 FAIR HOUSING THRESHOLDS AT EXTERIOR
 DOORS FOR CORRECTION OF THRESHOLDS.
  
 B) PLANS FOR STAIRWELL RAILINGS/
 GAURDRAILS INDICATE DETAILS ON A8.01
 DETAIL# 1, THE BOTTOM RAIL ON THE STAIRS
 SHALL COMPLY WITH:
 1015.3(1) A 6 INCH SPHERE SHALL NOT PASS
 THROUGH THE TRIANGLE OPENING FORMED BY A
 TREAD , RISER AND THE BOTTOM OF A
 GUARDRAIL.
  
 17) SHEET A4.07
 A) DISCREPANCY BETWEEN A2.01.1 & A4.07
 SHEET A2.01.1 EAST OF STAIRWELL# 4
 INDICATES A STORAGE AREA, A4.07 DOESN'T
 INDICATE STORAGE AREA, THE SECOND ISSUE
 IS ON A4.07 THE AREA EAST OF THIS HAS A
 DOORWAY WITH NO ROOM IDENTIFICATION,
 PLANS INDICATE THE USE OF TECTUM FINALE
 PANELS PROVIDE FIRE AND SMOKE
 DEVELOPMENT INFORMATION.
  
 B) THIS SAME AREA INDICATES SOME TYPE OF
  
 OPENINGS IN THE INTERIOR AS WELL AS
 EXTERIOR WALLS BUT NO INFO? CHECKING
 ELEVATIONS IS THIS AREA FOR VENTILATION
 IN BOTH WALLS?
  
 18) A4.11 VS A9.02 STAIRWELL AND
 ELEVATOR LOBBY DOOR FIRE RATINGS AND
 STYLE ARE REVERSED IN THE DOOR SCHEDULE.
  
 19) A4.13 VS A9.02 STAIRWELL #1 DOOR IS
 LABELED 3/4 HR IN DOOR SCHEDULE.
  
 20) A4.14 INDICATES A 1/2 INCH CHANGE IN
 GRADE, FAIR HOUSING MAX 1/4".
  
 21) A4.16 INDICATES A DOOR # 20 TO A
 MECHANICAL ROOM MISSING ON A9.02 DOOR
 SCHEDULE.
  
 22) A4.21/ A4.23 HAVE ELEVATOR LOBBIES,
 THE WINDOW IN THE LOBBY DOESN'T INDICATE
  
 ANY FIRE RATING, SEE 412.6(1)1HR WALLS
 REQUIRE 20-MINUTE OPENING PROTECTIVES.
  
 23) A4.31 THERE ARE RATED WALLS 1 & 2 HR
 THAT DO NOT INDICATE WHICH SYSTEM SHOULD
 BE USED?
  
 24) A4.34:
 A) THE COMMUNITY ROOM, FAIR HOUSING
 INDICATES THAT THE ACCESSIBLE
 ROUTE TO THE SUN DECK IS DISCREMINTORY
 BECAUSE OF THE TRAVEL DISTANCE REQUIRED
 IF YOU ARE HANDICAPPED.
  
 25) A4.35:
 A) PLANS INDICATE THAT THE SECONARY
 ENTRY DOOR ( TERRACE) FROM UNITS ONTO
 THE PATIO BUT NOT ACCESSIBILE BECAUSE OF
 THE STEPSONTO THE SUN DECK.THIS IS
 DISCRIMINATING AGAINST THE HANDICAPPED
 BECAUSE THE HANDICAPPED HAVE TO USE
 ANOTHER ROUTE.
 CONTACTED BARBRA CHANDLIER/ FAIR HOUSING
  
 B) THE SECOND ISSUE WITH THIS ROUTE IS
 THE GATE HAS TO BE A MINIMUM OF 32"
 CLEAR FOR A SECONARY EXTERIOR DOORWAY.
 PAGE 3.10
  
 C) HANDRAILS WILL BE REQUIRED FOR A
 CHANGE IN GRADE OVER 6".
  
 26) A4.36 THE PLANS APPEAR TO HAVE (2)
 COLUMNS IN THE ROOM ,1 IN THE MIDDLE OF
 A DOORWAY UNIT 303?
  
 27) A4.43 UNIT 405 IT APPEARSTHAT 2
 COLUMNS APPEAR AS COMMENT ABOVE.
  
 28) A4.46 THE KEY PLAN DOES NOT MATCH
 THE CONFIGURATION OF THE BUILDING, THIS
 IS THE SOUTHWEST CORNER OF THE BUILDING
  
 29) A4.53 SAME COMMENT AS 26 ROOM 505.
  
 30) A4.63 SAME COMMENT AS 26 ROOM 605.
  
 31) A4.65 SAME COMMENT AS 26 ROOM 603.
  
 32 A4.72 SAME COMMENT AS 26 ROOM 705.
  
 33) A4.74 SAME COMMENT AS 26 ROOM 703.
  
 34) A4.71/ A4.72/ A2.07:
 A) 1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED, REDUCED
 TO 1/3 THE DIAGONAL FOR FIRE SPRINKLERED
 SPRINKLERS.
  
 35)A8.01/DETAILS 7&8,A8.03 /12
 ARCHITECTURAL TRIM
 TYPE I, II CONSTRUCTION OR MORE THAN
 40', SHALL BE SECURED TO THE WALL WITH
 METAL OR APPROVED FASTENERS.WHEN TRIM IS
 LOCATED ALONG THE TOP OF EXTERIOR WALLS,
 IT SHALL BE COMPLETELY BACKED BY THE
 EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIOR WALLS. 1404.1.
  
 A36) THIS BUILDING HAS BEEN TRATED AS A
 BIG SQUARE AS FAR AS WIND ZONES!
 1606.2.2.1/1606.2.2.2 MEMBERES THAT ARE
 BOTH PART OF THE MAIN FORCE RESISTING
 SYSTEM AND AS COMPONENTS AND CLADDING
 SHALL BE DESIGNED FOR EACH SEPERATE LOAD
 CASE. LOOKING AT A3.03 THE SOUTH
 ELEVATION THE INTERNAL ZONE HAS BEEN
 TAKEN FOR THE COMPLETE SOUTH SIDE WITH
 THE EXCEPTION OF THE EXTREME END ZONES
 TAKEN AS 16'-0". THERE IS NO
 CONSIDERATION FOR THE SOCALLED INTERIOR
 END ZONES SEE UNITS 601 & 624 FOR
 EXAMPLE. THE WIND ALSO WILL PRESSURIZE
 ONTO THE NORTH WALL AT THE POOL DECK.
 REVISIT PRESSURE ZONES. NO MENTION OF A
 PRESSURE DIFFERENCE AT THE ROOF TOP
 CABANAS CONSIDERED WHICH ZONE?
  
 37)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 38)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR DOORS GLAZED OR NOT
 B) WINDOWS FIXED OR MOVABLE, STOREFRONT
 C) LOUVERS
 D)STORM SHUTTERS
 E) EXTERIOR RAILINGS
 F) EFIS SYSTEMS
 G) SKYLIGHTS IF USED
 H) ROOFING ASSEMBLIES
  
 39) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 40) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 41) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 42) PLANS DO NOT INDICATE WHERE FAIR
 HOUSING INFORMATION CAN BE FOUND, CLEAR
 FLOOR SPACE FOR KITCHEN APPLIANCES
 BATHROOMS, NOR WHCICH UNITS ARE "A" OR
 "B" UNITS. ALSO MISSING IS INFORMATION
 FOR BACKING FOR BATHROOMS AND LOCATIONS.
  
 43) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-10 Cont ID  
Sent By btrobaug Date 2005-11-10 Time 15:16 Rev Time 0.00
Received By   Date   Time   Sent To M
Notes
2005-11-16 00:00:00 
 PROVISO
  
 ALL DWELLING UNIT EWH CIRCUITS IN ALL
 DWELLING PANELS ARE IN VOILATION OF
 422.11(E). THE OCP IS TOO LARGE FOR THE
 INDICATED LOADS.
  
 ALTHOUGH THIS WAS DISCUSSED, AFTER DOING
 THE MATH AGAIN ON THIS REVIEW I STILL
 CONTEND THE OCP'S ARE INCORRECT.IG:
 PANEL A1 EWH LISTED @ 3000VA/208V(SINGLE
 PHASE)=14.42AMPS X 150%(422.11(E))=21.6
 OR 22AMPS. PER 422.11(E)(3)25AMP BREAKER
 WOULD BE PERMITTED. THE PANEL SCHEDULE
 INDICATES A 40 AMP BREAKER.
  
 PLEASE CORRECT THE PANEL SCHEDULES ON
 THE NEXT REVISION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-04 Cont ID  
Sent By btrobaug Date 2005-05-04 Time 14:03 Rev Time 8.00
Received By btrobaug Date 2005-04-12 Time 12:23 Sent To  
Notes
2005-05-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THAT THE ADDRESS ON THE
 APPLICATION IS NOT THE ADDRESS OF RECORD
 FOR THE PCN ON CITY RECORDS.
  
 2} PLEASE SEE NO REFERENCE WAS MADE
 REGARDING THE FAIR HOUSING ACT. NOTE
 COMPLIANCE WITH SAME.
  
 3} THE PANEL SCHEDULE SHOWS "MSBHE" AS
 HAVING A 1000 AMP MAIN BREAKER. THE
 RISER DIAGRAM SHOWS A 1000 AMP MAIN
 AHEAD OF THE ATS. ARE THESE THREE PIECES
 OF EQUIPMENT AN INTEGRAL PART OF THE
 MAIN GEAR, OR ALL SEPARATE PIECES OF
 EQUIPMENT? PLEASE PROVIDE SPECS ON THE
 GEAR.
  
 4} IF "MSBHE" IS FED THROUGH THE ATS
 FROM THE 1000 AMP EMERGENCY MAIN, AND
 DOES NOT HAVE A GFI PROTECTED MAIN
 BREAKER INTERNALLY, THE BREAKER ON THE
 GENERATOR WOULD BE REQUIRED TO BE GFI
 PER 240.13 NEC.
  
 5} IF THE EMERGENCY MAIN SHOWN ON THE
 RISER IS A SEPERATE PIECE OF EQUIPMENT
 AS MENTIONED, GIVE AIC RATING.
  
 6} INDICATE THE AIC RATING OF THE
 DWELLING UNIT MAINS AN METER CENTER
 EQUIPMENT PER 110.9.
  
 7} INDICATE THE CONDUIT AND CONDUCTOR
 SIZE AND TYPE FROM THE GENERATOR TO THE
 ATS.
  
 8} THE DOMESTIC BOOSTER PUMP CONTROLLER
 ON THE RISER IS SHOWN FED FROM "WL1E",
 BUT LISTED ON "EH1E" SCEDULE, CIRCUITS
 14,16&18. PLEASE CORRELATE.
  
 9} THE JOCKEY PUMP IS ALSO SHOWN AS FED
 FROM "WL1E", BUT APPEARS ON "EH1E"
 SCHEDULE, PLEASE CORRELATE.
  
 10} PLEASE REMOVE REFERENCES TO THE 1999
 NEC FROM NOTES (SEE APARTMENT KEY NOTES)
 AND REFERENCE THE 2002 NEC CURRENTLY
 BEING USED.
  
 11} ELECTRICAL ROOMS MEANS OF EGRESS
 MUST COMPLY WITH 110.26(C)(2). SEE
 DOORSWING SHEET E4.00(INCORRECTLY MARKED
 AS E3.0.1 ON SHEET E2.01.3 NOTES).
  
 THE FOLLOWING COMMENTS REGARD THE PANEL
 SCHEDULES BEGINNING ON SHEET E6.01.
  
 1} PANEL "WL1" CIRCUITS 31,35 EWH-2 OCP
 DOES NOT CORRELATE WITH E0.01 EQ
 SCHEDULE.
  
 2} "WH8E" SHEET E6.02,CIRCUITS 14,16,18
 OCP DOES NOT CORRELATE WITH EQUIPMENT
 SCHEDULE.
  
 3} ALL DWELLING UNIT EWH CIRCUITS IN ALL
 DWELLING PANELS ARE IN VOILATION OF
 422.11(E). THE OCP IS TOO LARGE FOR THE
 INDICATED LOADS.
  
 4} THE HEAT PUMP CIRCUITS IN ALL
 DWELLING PANELS WITH THE EXCEPTION OF
 "A4", DO NOT CORRELATE WITH THE
 EQUIPMENT SCHEDULE MAX OCP.
  
 THE FOLLOWING COMMENTS REGARD THE FLOOR
 PLANS BEGINNING ON SHEET E3.01.
  
 1} THE RECEPTACLES SHOWN OUTSIDE THE
 UNIT(S)ON CIRCUIT "T1-6" ARE ON THE
 SMALL APPLIANCE CIRCUIT IN VIOLATION OF
 210.52(B)(2).
  
 2} ALL UNITS RECEPTACLE PLACEMENT
 (CIRCUIT #8) FOR THE MICROWAVE, THOUGH
 PLACED WITHIN 2' OF THE SINK, DO NOT
 COUNT FOR SPACING PER 210.52(C)(1) SMALL
 APPLIANCE REQUIREMENT FOR SPACING AS
 CIRCUIT #8 IS NOT A SMALL APPLIANCE
 CIRCUIT. A SMALL APPLIANCE RECEPTACLE
 MUST BE ADDED TO COMPLY, ALL UNITS.
  
 3} ALL BALCONY RECEPTACLES, ALL UNITS
 ARE ON A SMALL APPLIANCE CIRCUIT IN
 VIOLATION OF 210.52(B)(2) EXCEPT CIRCUIT
 T1-7 SHEET E3.05 WHICH IS ON THE BATH
 RECEPTACLE CIRCUIT IN VIOLATION OF
 210.11(C)(3).
  
 4} REFERENCE SHEET E3.02. DWG 2&3 E3.02.
 2 BEDROOM @ STAIR.A RECEPTACLE MUST BE
 ADDED TO THE PENINSULAR TO COMPLY WITH
 210.52(C)(4).
  
 5} 4 E3.02 2 BEDROOM 8TH FLOOR PLAN.
 210.52(C)(4) AND BEDROOM NEEDS
 RECEPTACLE PER 210.52(A)(2).
  
 6} SHEET E3.03 CUT1,3 BEDROOM UNIT RCP
 PLAN. ADD RECEPTACLE IN THE MASTER
 BEDROOM PER 210.52(A)(1).
 2/3 BEDROOM UNIT W/SKYLOFT RCP PLAN. ADD
 A SMOKE DETECTOR @ STAIRWELL PER 905.2.2
 FBC.
  
 7} TOWNHOUSE UNIT 4 NEEDS A RECEPTACLE
 BETWEEN THE STOVE AND FRIDGE,
 210.11(C)(1) COUNTERTOP SPACING,4 E3.04.
 ALSO NOTE THAT AN ISLAND RECEPTACLES
 MUST BE ADDED IF THERE IS COUNTERTOP
 SEPARATION (SINK), SEE 210.52(C)(4) AND
 EXCEPTION. CALL ME WITH QUESTIONS.
  
 8} A RECEPTACLE MUST BE ADDED FOR
 SPACING REQUIREMENTS 210.52(A), MASTER
 BEDROOM, 2' REQ.
  
 9} REFERENCE SHEET E3.04. SEC.3. TWO
 BEDROOM@ LOBBY. MASTER BEDROOM
 RECEPTACLES, ADD 1 AND ADD OR RELOCATE
 ONE, SEE REVIEWED PLAN.210.52(A).
  
 10} CIRCUIT #T1-28 E3.05, SEC'S 1&2, IS
 INDICATED AS A CIRCUIT # ON TWO
 RECEPTACLES. THIS IS LISTED AS A
 LIGHTING CIRCUIT ON THE SCHEDULE. PLEASE
 CORRELATE.
  
 11} AGAIN REGARDING THE ISLAND IN THESE
 TWO UNITS, SEE 210.52(A)(4) REGARDING
 RECEPTACLE SPACING, ONE MUST BE ADDED.
 ALSO SEE EXCEPTION 210.52(C)(5)(B) FOR
 OVERHANG.
  
 12} SHEET E3.06 SEC.2, 2ND LEVEL FLOOR
 PLAN, ADD A RECEPTACLE IN BEDROOM #2,
 210.52(A)(2), SEE PLAN. ISLAND
 RECEPTACLE COMMENTS APPLY AS WELL.
 CIRCUIT T-28 HAS RECEPTALES IN LIVING
 ROOM(S).
  
 13} SHEET E3.07 CENTER FLOOR PLAN MASTER
 BEDROOM NEEDS A RECEPTACLE TO COMPLY
 210.52(A)(2).
  
 14} SEE FIRE REVIEW FOR COMMENTS ON
 EMERGENCY EGRESS LIGHTING IN CORREDORS
 AND COMMON AREAS. SEE A.7.9.2.2 NFPA
 101.
  
 15} PLEASE SEE REQUIREMENTS FOR CURBS @
 FLOOR PENETRATIONS RE: BUSWAYS. ARTICLE
 368.6 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-04-04 Cont ID  
Sent By mamini Date 2005-04-04 Time 08:53 Rev Time 1.00
Received By mamini Date 2005-04-04 Time 08:53 Sent To  
Notes
2005-04-04 00:00:00PASSED WITH PROVISOS:
 1. NOTE THAT A BACKFLOW PREVENTER IN
 DOMESTIC WARER LINE IS REQUIRED.
 2. EROSION AND SEDIMENTATION CONTORL
 DEVICES SHALL BE IN PLACE PRIOR TO
 BEGINNING ANY CONSTRUCTION ACTIVITIES,
 AND MUST BE MAINTAINED THROUGHOUT.
  
 IF ANY QUESTION PLEASE CONTACT 805-7623
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-11-18 Cont ID  
Sent By mwennerg Date 2005-11-18 Time 09:51 Rev Time 0.00
Received By mwennerg Date 2005-11-18 Time 09:51 Sent To  
Notes
2005-11-18 00:00:00******DENIED******
  
 PLEASE NOTE THAT THE FIRST FIRE REVIEW
 CONSISTS OF 33 COMMENTS. ONLY 11
 RESPONSES HAVE BEEN RESUBMITTED. PLEASE
 ADDRESS ALL COMMENTS WHICH WILL HELP TO
 EXPEDITE THE REVIEW PROCESS.
  
 COMMENTS ADDRESSED:
  
 10) SHT FP000 APPEARS TO HAVE BEEN
 REMOVED.
  
 21) OK
  
 22) OK
  
 23) SEE #10
  
 24) SEE #10
  
 27) OK
  
 29) OK
  
 30) OK
  
 31) OK
  
 32) OK
  
 33) OK
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-04 Cont ID  
Sent By mwennerg Date 2005-05-04 Time 16:03 Rev Time 0.00
Received By mwennerg Date 2005-05-04 Time 16:03 Sent To  
Notes
2005-05-04 00:00:001) ALL LIFE SAFETY MUST COMPLY WITH NFPA
 101, 2003 EDITION.
  
 2) THE PARKING GARAGE SHALL MAINTAIN A 2
 HOUR SEPARATION FROM OTHER AREAS OF THE
 BUILDING AND COMPLY WITH NFPA 88A.
  
 3) THE DOOR APPEARS TO BE MISSING AT THE
 STAIRWELL ADJACENT TO THE OFFICE. 1ST
 LEVEL TOWNHOUSE/PARKING.
  
 4) THE DOOR SWING INTO STAIR #4 APPEARS
 TO BE AGAINST THE PATH OF TRAVEL.
  
 5) ARE ALL MAXIMUM TRAVEL DISTANCES IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION?
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 7) SINCE THE BUILDING EXCEEDS 75' IN
 HEIGHT, IT MUST COMPLY WITH BUILDING AND
 FIRE CODE REQUIREMENTS FOR HIGHRISE
 BUILDINGS.
  
 8) THE LOWER PARKING PLAN SHOWS ONLY ONE
 EXIT AT STAIR #4. PLEASE EXPLAIN.
  
 9) THE DOORS TO THE ELETRIC ROOMS
 APPEAR TO OBSTRUCT THE CORRIDORS GREATER
 THAN 1/2 THE TOTAL WIDTH.
  
 10) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30' IN HEIGHT.
  
 11) TWO UNITS ON THE SOUTH SIDE OF THE
 BUILDING HAVE 300 ADDRESSES ON THE 4TH
 FLOOR.
  
 12) TWO UNITS ON THE SOUTH SIDE OF THE
 BUILDING HAVE 500 ADDRESSES ON THE 6TH
 FLOOR.
  
 13) ALL SHAFTS THAT ARE LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE MARKED
 SHAFTWAY IN 6" LETTERS.
  
 14) TACTILE SIGNAGE IS REQUIRED AT EXIT
 DOORS.
  
 15) AN ADDRESS NUMBER IS REQUIRED THAT
 IS A MINMUM OF 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND.
  
 16) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 17) SIGNS ARE REQUIRED IN THE STAIRWELLS
 INDICATING TOP, BOTTOM, FLOOR NUMBER,
 ROOF ACCESS AND THE IDENTITY.
  
 18) PLEASE PROVIDE MORE DETAILS ON THE
 AWNINGS IN REGARDS TO OVERHANG HEIGHT
 AND FIRE RETARDANT INFORMATION.
  
 19) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS FOR THE POOL DECK AREA.
  
 20) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION OF THE WALLS AND
 CEILINGS.
  
 21) THE ELEVATOR/FIRE ALARM NOTES MAKES
 REFERENCE TO FLOORS 2-25. PLEASE MAKE
 CORRECTION.
  
 22) EMERGENCY LIGHTING FACILITIES ARE
 MISSING FROM ALL COMMON AREAS AND OTHER
 LOCATIONS ROUTINELY INHABITED BY HUMANS
 WITH THE EXCEPTION OF THE STAIRWELLS.
  
 23) IF THE TOTAL NUMBER OF SPRINKLERS
 EXCEEDS 1000, A MINIMUM OF 24 SPARE
 SPRINKLERS IS REQUIRED, NOT 6.
  
 24) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS.
  
 25) LOCKING KNOX BOX CAPS ARE REQUIRED
 FOR THE FIRE DEPARTMENT CONNECTIONS.
  
 26) KNOX BOXES WILL BE REQUIRED.
  
 27) THE FIRE ALARM SYSTEM SHALL MEET THE
 MONITORING REQUIREMENTS FOR CENTRAL
 STATION SERVICE.
  
 28) PLEASE DISPLAY ANY EXISTING OR NEW
 FIRE HYDRANTS IN THE VICINITY OF THE
 BUIDING.
  
 29) HIGHRISE BUILDINGS ARE REQUIRED TO
 HAVE TWO FIRE DEPARTMENT CONNECTIONS.
  
 30) THE FIRE DEPARTMENT CONNECTIONS CAN
 BE NO FURTHER THAN 150' FROM THE CLOSEST
 FIRE HYDRANT.
  
 31) THE FIRE PROTECTION DRAWINGS DON'T
 SHOW FIRE SPRINKLER PROTECTION IN ALL
 THE LIVING UNITS.
  
 32) THE FIRE ALARM SYSTEM SHALL BE CLASS
 A STYLE D OR FULLY ADDRESSABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR9%61) 835-2910 OR 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-27 Cont ID  
Sent By adarroug Date 2006-03-27 Time 08:52 Rev Time 0.00
Received By adarroug Date 2006-03-27 Time 08:51 Sent To B
Notes
2006-03-27 00:00:00TO "JWITMER' DESK-CHANGE OF CONTRACTOR

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 09:45 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 09:45 Sent To  
Notes
2005-10-14 00:00:00TO "COMM" BD#40
2005-10-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 14:25 Rev Time 0.00
Received By shill Date 2005-06-10 Time 14:25 Sent To M
Notes
2005-06-10 00:00:00ROUTED TO PK DESK (LAST REVIEW), TAKEN
 OFF OF BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-05 Cont ID  
Sent By jwitmer Date 2005-06-09 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2005-03-25 Time 16:30 Sent To  
Notes
2005-03-25 00:00:00TO "COMM" BD#59/"COMM" RACK 6 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-03 Cont ID  
Sent By pkrauss Date 2005-12-30 Time 11:18 Rev Time 0.00
Received By pkrauss Date 2005-12-30 Time 08:37 Sent To  
Notes
2005-12-30 00:00:00DENIED:
 PLEASE PROVIDE ADDITIONAL CLARIFICATION
 TO THE RESPONSES GIVEN TO COMMENTS FROM
 REVIEW DATED 6-9-05.
  
 COMMENT #3 PLAN SHEET AC0.02 GENERAL FAN
 NOTE #16, PLEASE REVISE NOTE TO INDICATE
 THE CARBON MONOXIDE SENSOR SHALL
 ACTIVATE GARAGE FAN AT A MAXIMUM OF 25
 PPM IN ACCORDANCE WITH 2001 FMC 403.4.
 PLEASE INDICATE THIS ON REFERENCES TO CO
 SENSORS.TESTING WILL BE REQUIRED AT
 FINAL INSPECTION.
  
 COMMENT #5 RESPONSE STATES EXHAUST &
 MAKEUP AIR CANNONT BE TAKES TO THE
 OUTDOORS.PLEASE PROVIDE CO SENSORS
 INSIDE THESE VARIOUS ROOMS.
  
 COMMENT #6 NOXIOUS EXHAUST TERMINATING
 WITHIN 10 FT OFF FRESH AIR INTAKES.
 RESPONSE ONLY ADDRESSED SOME OF THE
 ISSUES.PLAN SHEET AC2.01.2 SEF-9 IS
 TERMINATING OVER AN EXIT DOOR AS IS
 GEF-6 WHICH AS 12,500 CFM OF
 NOXIOUS/TOXIC EXHAUST TERMINATING ABOVE
 A DOOR.EXHAUST SHALL NOT TERMINATE
 ONTO WALKWAYS - 2001 FMC 401.5.1.
  
 COMMENT #10PLAN SHEET AC0.003 &
 RESPONSE TO COMMENT #10, INDICATE O.A.
 FOR THE RESIDENCE BY INFILTRATION BY THE
 'CRACK METHOD'.SHOULD THIS REFER TO
 THE MAXIMUM INFILTRATION RATES GIVEN IN
 CHAPTER 13 OF THE FBC, THE INFILTRATION
 RATE MAY NOT ALLOW THE MAXIMUM THEREFORE
 IS SPECULATIVE AS IS THE 50 CFM FROM THE
 CORRIDOR.
  
 COMMENT #12 INFORMATION ON THE
 GENERATOR.RESPONSE STATES SUB-BASE
 FUEL TANK.PLEASE CLARIFY DIESEL FUEL.
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA.PLEASE NOTE WINDOW IN THE UNIT
 #118 & 119 ARE WITHIN 10 FT OF THE
 EXHAUST TERMINATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-09 Cont ID  
Sent By pkrauss Date 2005-06-09 Time 06:56 Rev Time 9.00
Received By pkrauss Date 2005-06-09 Time 06:56 Sent To  
Notes
2005-06-09 00:00:00DENIED:
 1.PLAN SHEET AC0.01 HEAT PUMP SCHEDULE
 HP-5, PER 2001 FBC(M)606.2.1 DUCT SMOKE
 DETECTORS ARE REQUIRED IN UNITS THAT
 HAVE THE DESIGN CAPACITY GREATER THAN
 2,000 CFM.
  
 2.PLAN SHEET AC0.02 FAN SCHEDULE, EF-2
 DRYER BOOSTER FAN SHALL BE SUBMITTED
 UNDER ALTERNATE MATRERIALS & MEDTHODS TO
 THE BUILDING OFFICIAL, NEIL MELICK.
 PLEASE PROVIDE ALL SUBMITTAL DATA AND A
 LETTER FROM THE DRYER MANUFACTURER
 (ENGINEER) INDICATING THIS APPLICATION
 IS PERMITTED AND WILL NOT VOID THE
 WARRANTY.
  
 3.PLAN SHEET AC0.04 GARAGE EXHAUST IS
 DESIGNED TO FUNCTION WITH THE CO
 SENSORS.PLEASE CLARIFY THE FOLLOWING:
 A) WILL THIS BE A PRIVATE OR PUBLIC
 GARAGE?
 B) PROVIDE CALCULATIONS IN ACCORDANE
 WITH 2001 FBC 411.5.
  
 4.PLAN SHEET AC0.07 AHU DETAIL DOES
 NOT INDICATE AUXILIARY DRAIN PAN WITH
 OVERFLOW PROTECTION AS REQUIRED PER 2001
 FBC(M)307.2.3.
  
 5.PLAN SHEET AC2.01.1, EF-3 AND THE
 AIR MAKE-UP ARE INTO & FROM THE GARAGE.
 PER 2001 FBC(M)501.3, EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED
 OUTDOORS. REFERENCE ALSO TABLE 403.3,
 EXHAUST AIR SHALL NOT BE RECIRCULATED.
 THIS APPLICATION IS DONE THROUHOUT THE
 GARAGE AREA.
  
 6.PLAN SHEET AC2.01.2, SEF-8 & OUTSIDE
 AIR ARE WITHIN 10 FT OF EACH OTHER.
 EXHAUST SHALL NOT BE RECIRCULATED INTO
 FRESH AIR, NOXIOUS & TOXIC EXHAUST SHALL
 BE A MINIMUM OF 10 FT FROM FRESH AIR
 INTAKES PER 2001 FBC(M)401.5.1
  
 7.PLEASE NOTE, EXHAUST & INTAKE
 OPENINGS SHALL BE A MINIMUM OF 10 FT
 FROM LOT LINES OR BUILDINGS ON THE SAME
 LOT - 2001 FBC(M)401.5.PLANS DO NOT
 INDICATE REQUIRED DISTANCES.
  
 8.PLAN SHEET AC2.01.2, PLEASE NOTE THE
 LOCATION OF CU-EV2 ON A STAND THAT
 APPREARS TO BE IN THE PATH OF TRAVEL TO
 A TOWN HOUSE.ALSO PROVIDE SUBMTITAL
 DATA FOR THE CU-EV2, DOES MANUFACTURER
 ALLOW THE OUTDOOR CU TO BE LOCATED IN AN
 ENCLOSED GARAGE?
  
 9.PLAN SHEET AC2.08.2, PLEASE PROVIDE
 OUTSIDE AIR AND VENTILATION REQUIREMENTS
 FOR THE MECHANICAL ROOM.
  
 10. PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS FOR ALL AREAS RESIDENTIAL
 AND COMMON, FITNESS ROOMS LOBBY AREAS,
 ETC. IN ACCORDANCE WITH 2001 FBC(M)TABLE
 403.3.
  
 11. PLEASE PROVIDE RISER FOR THE SMOKE
 EVAC AND OUTSIDE AIR DUCTS.
  
 12. PROVIDE INFORMATION ON THE
 GENERATOR.INDICATE FUEL SOURCE.
  
 PLEASE NOTE, RESONSE TO COMMENTS MAY
 GENERATE NEW COMMENTS.PLEASE PROVIDE
 WRITTEN RESPONSE TO COMMENTS TO HELP
 EXPIDITE RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-12 Cont ID  
Sent By kstevens Date 2005-12-12 Time 16:26 Rev Time 0.00
Received By kstevens Date 2005-12-08 Time 13:36 Sent To  
Notes
2005-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB CODE
  
 1) PLUMBING PLANS ARE INCOMPLETE THIS
 SUBMITTAL AND MORE COMMENTS MAY BE
 FORTHCOMING ON THE NEXT REVIEW. SUBMIT
 THE FOLLOWING: - SEE NEW COMMENTS.
 A. EMERGENCY WATER HEATER PAN BUILDING
 ISOMETRIC AND RISER DIAGRAMS. SHOW
 MATERIAL TO BE USED. SHOW PIPE SIZE.
 SHOW TERMINATION POINT. - RESPONSE NOTED
 BUT HUB DRAIN INDICATED ON PAN DRAIN
 RISER DIAGRAM NOT FOUND ON ANY SYSTEM.
 PLEASE CLARIFY. SECTION 104.2.1.
 C. CONDENSATE BUILDING DRAIN ISOMETRIC
 AND RISER DIAGRAMS. SHOW MATERIAL TO BE
 USED. SHOW PIPE SIZE. SHOW TERMINATION
 POINT AND VENT TERMINATION. - RESPONSE
 NOTED, BUT CONDENSATE VENT SHALL NOT
 CONNECT TO THE SANITARY SYSTEM. ALSO
 CONDENSATE SYSTEM REQUIRES A RELIEF VENT
 (GOOSENECK) AS IT EXITS THE BUILDING.
 (SECTIONS 104.2.1, 504.7.1, 504.7.2,
 504.8.1, 504.8.2, CITY CODE 90-125(5).
 3) SHTS P3.03, P3.04, & P3.05.
 B. EVERY VENT STACK SHALL CONNECT TO THE
 BASE OF THE DRAINAGE STACK. THE VENT
 SHALL CONNECT AT OR BELOW THE LOWEST
 HORIZONTAL BRANCH. SECTION 903.4. -
 RESPONSE NOTED, BUT SOME VENTS ARE
 CONNECTED TO BRANCH LINES AND NOT THE
 BASE OF THE STACK AS REQUIRED.
 I. RISER S/9-S/34 DOES NOT REFLECT THE
 FLOOR PLAN AT THE 8TH FLOOR- RISER AND
 FLOOR PLANS STILL DO NOT REFLECT EACH
 OTHER..
 4) MORE INFORMATION REQUIRED. ARE THERE
 TOWNHOUSE UNITS ON SHT P2.001? PIPING
 SEEMS TO INDICATE THAT THERE ARE, BUT NO
 FLOOR PLAN SHOWN FOR THESE UNITS. IF NOT
 IS THE PIPING IN THE CEILING FOR THE
 NEXT FLOOR? SHEETS P2.01.1 & P2.01.2
 STATE "PARTIAL 1ST LEVEL PARKING, 1ST
 LEVEL TOWNHOUSE FLOOR PLAN. IS THE LOWER
 PARKING FLOOR PLAN AT GRADE LEVEL? IF SO
 IS THE 1ST LEVEL TOWNHOUSE ON THE 2ND
 FLOOR? PLEASE CLARIFY. - PIPING STILL
 INDICATES KITCHEN SINKS ARE ON THE
 GROUND FLOOR. PLEASE CLARIFY. (SEE NEW
 COMMENT CONCERNING PIPING LAYOUTS)
 5) SHTS P2.00.1 & P2.00.2 SHOW ALL PIPE
 SIZES, INDICATE RISER NUMBER ON ALL
 RISERS, SHOW FIXTURE UNITS AS THEY
 ACCUMULATE IN THE SYSTEM, SHOW SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM.
 - THESE ITEMS STILL NOT ADDRESSED FULLY.
 SECTION 104.2.1, AND TABLES 710.1(1),
 1106.2 & 1106.3.
 6) SHTS P2.01.1 & P2.01.2 SHOW ALL PIPE
 SIZES, RISER DESIGNATION NUMBERS. SANT.
 PIPING SHOWN ON FLOOR PLAN OF TOWNHOUSES
 DOES NOT SEEM TO CONNECT TO ANY
 FIXTURES. PLEASE CLARIFY. - RESPONSE
 NOTED, BUT ALL PIPING LAYOUTS SHALL BE
 SHOWN ON THE FLOOR PLAN FOR EACH FLOOR.
 SHOWING THE PIPING ON PREVIOUS SHEETS
 (BELOW THE SLAB) IS NOT OF SUFFICIENT
 CLARITY. SECTION 104.2.1. - SOME SHEETS
 SHOW SOME OF THE PIPING ON THE FLOOR
 PLAN AND SOME OF THE PIPING BELOW THE
 FLOOR PLAN.
 7) SHTS P2.02.1 & P2.02.2 SHOW THE
 LOCATION OF ALL RISERS FOR ALL SYSTEMS.
 SECTION 104.2.1. - RESPONSE NOTED, BUT
 ALL RISERS SHALL BE SHOWN INCLUDING W/M
 AND RWL RISERS.
 8) SHTS P2.03.1 & P2.03.2 SHOW THE COL.
 LINES SO RISERS CAN BE TRACED FROM ONE
 FLOOR TO THE NEXT. SHOW ALL RISERS AND
 INDICATE LOCATION AND RISER NUMBER. SHOW
 ALL PIPE SIZES. MOST OF THESE FIXTURES
 ARE NOT SHOWN ON THE RISER DIAGRAMS.
 PLEASE CLARIFY. SECTION 104.2.1. -
 RESPONSE NOTED, BUT RWL RISERS ARE NOT
 SHOWN AND THE PIPING FOR THE FIXTURES
 SHALL BE SHOWN. (SEE COMMENT #6).
 9) SHTS P2.04.1 & P2.04.2THESE
 FIXTURES ARE NOT SHOWN ON THE RISER
 DIAGRAMS OR THE SANT. BUILDING DRAIN
 ISOMETRICS. SHTS P3.060 & P3.061. SUBMIT
 RISER DIAGRAMS SHOWING THESE FIXTURES.
 SHOW ALL PIPE SIZES. SECTIONS 104.2.1,
 AND 104.3.1.1. RESPONSE NOTED, BUT PIPE
 SIZES ARE NOT SHOWN AND THE PIPING
 LAYOUTS SHALL BE SHOWN FOR THE FLOOR
 PLAN SUPERIMPOSED OVER THE FIXTURES THEY
 CONNECT TO. SHOW RWL RISERS.
 10) SHTS P2.05.1 & P2.05.2 RISERS 2/4,
 S/5, S/13, S/26, S/28, & S/37 DO NOT
 REFLECT THE FLOOR PLAN. RISERS S/13,
 S/25, & S/40 SHOW ALL PIPING. SECTION
 104.2.1. - SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS FOR
 THE 4TH FLOOR ELEVATION. SHOW SF OF EACH
 AREA AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO
 CALCULATIONS AS WELL AS AREA OF ANY ROOF
 THAT DRAINS ONTO THE AREAS FROM ABOVE.
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW THE LOCATION OF ALL
 PRIMARY AND SECONDARY DRAINS. - RESPONSE
 NOTED, BUT THE CALCULATIONS REQUESTED
 WERE NOT SUBMITTED. ALSO SHOW THE
 LOCATIONS FOR ALL SECONDARY DRAINS.
 11) SUBMIT THE FOLLOWING: RISER DIAGRAMS
 FOR THE TOWNHOUSE UNITS. UNITS ON THE
 1ST, 2ND, AND THIRD FLOORS. THE
 FOLLOWING RISER DIAGRAMS WERE NOT
 LOCATED: S/3, S/27, ALL W/M RISERS.
 SECTIONS 104.2.1, & 104.3.1.1.
 12) SHTS P2.06.1 & P2,06.2 SHOW RISER
 S/25 NUMBER DESIGNATION. - SHOW PIPING
 FOR RISER S/25, S/13, S/37, & S/40 -
 RISERS S/4, S/5, S/13. S/26, S/28, &
 S/37 DO NOT REFLECT THE RISER DIAGRAM.
 SECTION 104.2.1. RESPONSE NOTED, BUT NO
 FIXTURES WERE SHOWN ON THE FLOOR PLAN
 FOR RISER S/40 AND S/13-S/37 SHOW NO
 PIPING TO THE W/C'S.
 13) SHTS P2.07.1 & PS.07.2 RISERS DO NOT
 REFLECT THE RISER DIAGRAMS: S/4, S/13,
 S/28, & S/37. FOLLOWING RISERS SHALL
 SHOW DWV PIPING ON THE FLOOR PLAN: S/4,
 S/13, S/15, S/16, S/17, S/19, S/20,
 S/21, S/22, S/23, S/24, S/25, S/28,
 S/37, & S/40. RISER S/29 MISLABLED AS
 S/19. SECTION 104.2.1. - RESPONSE NOTED,
 BUT S/28 STILL DOES NOT REFLECT THE
 PIPING LAYOUT ON THE FLOOR PLAN.
 14) SHTS P2.08.1 & P2.08.2 RISERS S/1,
 S/13, S/28, & S/37 DO NOT REFLECT THE
 RISER DIAGRAMS. SHOW THE DWV PIPING FOR
 THE FOLLOWING RISERS: S/4, S/9, S/12,
 S/13, S/29, S/34, S/37, & S/38. - SHOW
 THE LOCATIONS FOR THE FOLLOWING VTR'S AS
 SHOWN ON RISER DIAGRAMS: S/16, S/19,
 S/20, S/21, S/22, S/23, S/25, & S/40.
 SECTION 104.2.1. - RESPONSE NOTED, BUT
 THE VENTING ROUTE SHALL BE SHOWN ON THE
 FLOOR PLAN, AND RISER VENT ROUTED TO
 SHALL BE INDICATED SO AS TO SIZE THE
 VENTS PER TABLE 916.1.
 16) SHTS P2.10.1 & P2.10.2 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SQUARE FEET OF EACH
 AREA AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS AS WELL AS ALL ROOF AREA THAT
 DRAINS DOWN TO ROOF FROM ABOVE IN
 CALCULATIONS PER SECTIONS 1106 & 1107
 AND ALL SUBSECTIONS. SHOW THE LOCATION
 OF ALL SECONDARY DRAIN AND/OR SCUPPERS.
 SUBMIT A DETAIL FOR SCUPPERS SHOW HEIGHT
 AND WIDTH TO SHOW SQ.IN. AREA OF
 SCUPPER. - INDICATE LOCATION OF ALL VTR.
 - RESPONSE NOTED, BUT CALCULATIONS WERE
 NOT SUBMITTED OR LOCATED. RISER S/20 VTR
 NOT LOCATED.
 18) SHTS P3.07.0 &P3.07.1 ROOF DRAIN,
 OVERFLOW DRAINS, DECK DRAINS, OVERFLOW
 DECK DRAINS, PARKING DRAINS ECT WILL BE
 REVIEWED AFTER THE CALCULATIONS FOR THE
 DRAINS HAS BEEN CHECKED. ONE SET OF ROOF
 DRAINS/OVERFLOW DRAINS (5900 SF) HAS
 BEEN CROSSED BETWEEN THE OVERFLOW AND
 DRAIN. ONE SET OF RWL/OVERFLOW RWL ARE
 SO CLOSE THE SYSTEMS CAN NOT BE CHECKED
 FOR COMPLIANCE. PLANS SHALL HAVE
 SUFFICIENT CLARITY TO REVIEW. - SUMP
 PUMP FOR PARKING AREA DRAINS SHALL BE
 LISTED. SUBMIT MANUF. SPECIFICATIONS
 SHEETS. SECTIONS 303.4.1, & 104.2.1. -
 RESPONSE NOTED, BUT CALCULATIONS WERE
 NOT SUBMITTED OR LOCATED.
 19) SHTS A2.03, A2.09, & A4.91 THRU
 A4.95 SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS. SHOW SQUARE
 FEET OF EACH AREA, AND SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS,
 AS WELL AS AREAS OF ROOFS THAT DRAIN
 ONTO THE ROOF AREAS FROM ABOVE ADDED IN
 CALCULATIONS. SECTIONS 1106, AND 1107
 AND ALL SUBSECTIONS. - NO RESPONSE NO
 CALCULATIONS SUBMITTED.
 20) SHT A1.06 SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH FHA REQUIREMENTS 3 THRU
 7, PAGE 7.33 FOR TOWNHOUSE UNITS. POWDER
 ROOM SHALL BE COMPLIANT.
 24) SHOW BACKING FOR UNITS PER
 SPECIFICATION 6 OF THE FHA DESIGN MANUAL
 - RESPONSE NOTED, BUT THE BACKING DETAIL
 SHALL REFLECT THE DESIGN MANUAL AND SHOW
 DIMENSIONS OFF THE FLOOR, LENGTH AND
 WIDTH OF THE BACKING.
 25) SHTS A4.32 & A4.35 SECONDARY ROOF
 DRAINS, (OVERFLOW DRAINS) SHALL BE
 LOCATED 2" ABOVE THE PRIMARY ROOF DRAINS
 PER SECTION 1503.4.2. PLEASE INDICATE
 HOW THIS WILL BE ACCOMPLISHED. IN SOME
 AREAS THE OVERFLOW DRAIN IS IN CLOSE
 PROXIMITY TO THE PRIMARY ROOF DRAIN.
 SECTION 1503.4.2. - RESPONSE NOTED, BUT
 AFTER SPEAKING TO THE BUILDING OFFICIAL,
 HE QUESTIONS THE DESIGN AND INDICATES
 THE POOLING EFFECT IN A HEAVY RAIN WILL
 HAVE WATER IN THE UNIT. SUBMIT
 CALCULATIONS SHOWING THE DRAINS FOR THE
 TERRACHS WILL MEET THE POOLING EFFECT
 FOR THE 4.5" RAINFALL SHOWN ON FIGURE
 1106.1 SHTS A4.32 & A4.35 INDICATE THE
 FLOOR ELEVATION TO BE 128'9" AND THE
 PATIO SLAB TO BE 128'3". PLEASE CLARIFY
 HOW THAT WILL BE ONLY 3/4" FROM DRAIN TO
 THRESHOLD.
 **************NEW COMMENTS**************
 1B. ALL PIPING FOR EACH FLOOR SHALL BE
 SHOWN ON THE FLOOR PLAN WITH THE
 FIXTURES SHOWN. SHOW ALL PIPE SIZES ON
 EACH FLOOR PLAN. SHOWING THE PIPING
 LAYOUT ON PREVIOUS SHEET IS CONFUSING
 AND ADDS MANY HOURS TO THE PLAN REVIEW.
 SOME SHEETS SHOW SOME OF THE PIPING ON
 THE SHEET WITH THE FIXTURES AND ALSO
 SHOW SOME PIPING ON PREVIOUS SHEETS.
 2B. CPVC IN THE PLENUMS IS NOT APPROVED
 UNLESS IT IS FILLED WITH WATER. PER
 MANUF. SPECIFICATIONS THE CPVC FOR THE
 P/T, PAN DRAIN AND CONDENSATE IS NOT
 APPROVED. PLEASE INDICATE AN ALTERNATIVE
 MATERIAL.
 3B. SHT P2.08.2 SHOW THE LOCATION OF THE
 FLOOR DRAIN SHOWN ON RISER 2/22 7TH
 FLOOR. FLOOR DRAIN SHALL NOT DRAIN STORM
 WATER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-21 Cont ID  
Sent By kstevens Date 2005-05-21 Time 16:44 Rev Time 17.50
Received By kstevens Date 2005-05-21 Time 16:44 Sent To  
Notes
2005-05-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB CODE
  
 1) PLUMBING PLANS ARE INCOMPLETE THIS
 SUBMITTAL AND MORE COMMENTS MAY BE
 FORTHCOMING ON THE NEXT REVIEW. SUBMIT
 THE FOLLOWING:
 A. EMERGENCY WATER HEATER PAN BUILDING
 ISOMETRIC AND RISER DIAGRAMS. SHOW
 MATERIAL TO BE USED. SHOW PIPE SIZE.
 SHOW TERMINATION POINT.
 B. P/T DISCHARGE VALVE RISERS AND BLDG
 DRAIN ISOMETRIC. SHOW MATERIAL TO BE
 USED. SHOW PIPE SIZE. SHOW TERMINATION
 POINT.
 C. CONDENSATE BUILDING DRAIN ISOMETRIC
 AND RISER DIAGRAMS. SHOW MATERIAL TO BE
 USED. SHOW PIPE SIZE. SHOW TERMINATION
 POINT AND VENT TERMINATION.
 (SECTIONS 104.2.1, 504.7.1, 504.7.2,
 504.8.1, 504.8.2, CITY CODE 90-125(5).
 2) SHT P3.02 WATER RISER DIAGRAMS. SHOWN
 ARE 6 FLOOR PLANS FOR THE WATER PIPING.
 IS THIS ALL THE FLOOR PLAN TYPES FOR THE
 WATER PIPING?
 A. WATER HAMMER ARRESTORS ARE REQUIRED
 AT THE DISH WASHER AND THE REFRIGERATOR.
 SECTION 604.9. THIS IS NOT SHOWN ON
 RISERS THAT DO NOT SHOW A SEPARATE LINE
 TO THE REF. NOR TO THE DISH WASHERS.
 B. HOSE BIBBS REQUIRE A SHUT OFF VALVE
 PER SECTION 606.2.(2).
 3) SHTS P3.03, P3.04, & P3.05.
 A. ALL RISERS ON ALL SHEETS. EVERY
 SANITARY DRAINAGE SYSTEM RECEIVING THE
 DISCHARGE OF A WATER CLOSET SHALL HAVE A
 MAIN VENT THAT IS EITHER A VENT STACK OR
 STACK VENT. SUCH VENT SHALL RUN
 UNDIMINISHED IN SIZE AND DIRECTLY AS
 POSSIBLE FROM THE BUILDING DRAIN THROUGH
 TO THE OPEN AIR ABOVE. SECTION 903.1.
 B. EVERY VENT STACK SHALL CONNECT TO THE
 BASE OF THE DRAINAGE STACK. THE VENT
 SHALL CONNECT AT OR BELOW THE LOWEST
 HORIZONTAL BRANCH. SECTION 903.4. -
 C. ALL RISERS SHALL SHOW ALL PIPE SIZES.
 TABLE 710.1(1).
 D. ALL RISERS WITH AIR ADMITTENCE VALVES
 SHALL HAVE A RELIEF VENT WHEN INSTALLED
 OVER 4 BRANCH INTERVALS BELOW THE TOP OF
 THE STACK. SECTION 917.3.2.
 E. RISER S/4-S/28 DOES NOT REFLECT THE
 FLOOR PLAN AT THE 4TH, 5TH, & 6TH
 FLOORS. SECTION 104.2.1.
 F. RISER S/15-S/18 DOES NOT REFLECT THE
 FLOOR PLAN AT THE 7TH FLOOR. SECTION
 104.2.1.
 G. RISERS S/13-S/37, & S/12-S/38 DO NOT
 REFLECT THE FLOOR PLAN. NO 9TH FLOOR
 SHOWN. PLEASE CLARIFY. SECTION 104.2.1.
 H. RISER S/10-S/35 DOES NOT REFLECT THE
 FLOOR PLAN ALL FLOORS, AND THE SHOWER IS
 NOT VENTED. SECTIONS 104.2.1. & 901.2.1.
 I. RISER S/9-S/34 DOES NOT REFLECT THE
 FLOOR PLAN AT THE 8TH FLOOR.
 - TUB ON ISOMETRIC NOT DRAWN CORRECTLY.
 (AS DRAWN IT INDICATES A DOWNWARD DROP
 OFF BRANCH LINE) SECTION 104.2.1.
 J. RISER S/25-2/40 SHOWER ON ISOMETRIC
 NOT DRAWN CORRECTLY. (SEE PREVIOUS
 COMMENT).
 K. RISER S/20-S/23 DOES NOT REFLECT THE
 FLOOR PLAN AT 7TH FLOOR. NO FIXTURES
 SHOWN ON THE FLOOR PLAN. - S/22 KITCHEN
 SINK PIPED OPPOSITE FROM OTHER RISERS.
 INDICATE ON RISER. SECTION 104.2.1.
 4) MORE INFORMATION REQUIRED. ARE THERE
 TOWNHOUSE UNITS ON SHT P2.001? PIPING
 SEEMS TO INDICATE THAT THERE ARE, BUT NO
 FLOOR PLAN SHOWN FOR THESE UNITS. IF NOT
 IS THE PIPING IN THE CEILING FOR THE
 NEXT FLOOR? SHEETS P2.01.1 & P2.01.2
 STATE "PARTIAL 1ST LEVEL PARKING, 1ST
 LEVEL TOWNHOUSE FLOOR PLAN. IS THE LOWER
 PARKING FLOOR PLAN AT GRADE LEVEL? IF SO
 IS THE 1ST LEVEL TOWNHOUSE ON THE 2ND
 FLOOR? PLEASE CLARIFY. - PIPING STILL
 INDICATES KITCHEN SINKS ARE ON THE
 GROUND FLOOR. PLEASE CLARIFY.
 5) SHTS P2.00.1 & P2.00.2 SHOW ALL PIPE
 SIZES, INDICATE RISER NUMBER ON ALL
 RISERS, SHOW FIXTURE UNITS AS THEY
 ACCUMULATE IN THE SYSTEM, SHOW SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM.
 CONDENSATE DRAINING FROM THE EAST OF
 COL. LINE E1 IS NOT CONNECTED TO DRAIN.
 SECTION 104.2.1 AND TABLES 710.1(1),
 1106.2 & 1106.3.
 6) SHTS P2.01.1 & P2.01.2 SHOW ALL PIPE
 SIZES, RISER DESIGNATION NUMBERS. SANT.
 PIPING SHOWN ON FLOOR PLAN OF TOWNHOUSES
 DOES NOT SEEM TO CONNECT TO ANY
 FIXTURES. PLEASE CLARIFY. P&T VALVE
 DISCHARGE LINES MAY DRAIN INTO AN
 INDIRECT WASTE RECEPTOR. FLOOR DRAINS
 ARE NOT AN APPROVED I.W. RECEPTOR.
 EITHER A FLOOR SINK OR A HUB DRAIN IS
 REQUIRED. SECTIONS 104.2.1, 802.3 &
 802.3.2.
 7) SHTS P2.02.1 & P2.02.2 SHOW THE
 LOCATION OF ALL RISERS FOR ALL SYSTEMS.
 SECTION 104.2.1.
 8) SHTS P2.03.1 & P2.03.2 SHOW THE COL.
 LINES SO RISERS CAN BE TRACED FROM ONE
 FLOOR TO THE NEXT. SHOW ALL RISERS AND
 INDICATE LOCATION AND RISER NUMBER. SHOW
 ALL PIPE SIZES. MOST OF THESE FIXTURES
 ARE NOT SHOWN ON THE RISER DIAGRAMS.
 PLEASE CLARIFY. SECTION 104.2.1.
 9) SHTS P2.04.1 & P2.04.2THESE
 FIXTURES ARE NOT SHOWN ON THE RISER
 DIAGRAMS OR THE SANT. BUILDING DRAIN
 ISOMETRICS. SHTS P3.060 & P3.061. SUBMIT
 RISER DIAGRAMS SHOWING THESE FIXTURES.
 SHOW ALL PIPE SIZES. SECTIONS 104.2.1,
 AND 104.3.1.1.
 10) SHTS P2.05.1 & P2.05.2 RISERS 2/4,
 S/5, S/13, S/26, S/28, & S/37 DO NOT
 REFLECT THE FLOOR PLAN. RISERS S/13,
 S/25, & S/40 SHOW ALL PIPING. SECTION
 104.2.1. - SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS FOR
 THE 4TH FLOOR ELEVATION. SHOW SF OF EACH
 AREA AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO
 CALCULATIONS AS WELL AS AREA OF ANY ROOF
 THAT DRAINS ONTO THE AREAS FROM ABOVE.
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW THE LOCATION OF ALL
 PRIMARY AND SECONDARY DRAINS.
 11) SUBMIT THE FOLLOWING: RISER DIAGRAMS
 FOR THE TOWNHOUSE UNITS. UNITS ON THE
 1ST, 2ND, AND THIRD FLOORS. THE
 FOLLOWING RISER DIAGRAMS WERE NOT
 LOCATED: S/3, S/27, ALL W/M RISERS.
 SECTIONS 104.2.1, & 104.3.1.1.
 12) SHTS P2.06.1 & P2,06.2 SHOW RISER
 S/25 NUMBER DESIGNATION. - SHOW PIPING
 FOR RISER S/25, S/13, S/37, & S/40 -
 RISERS S/4, S/5, S/13. S/26, S/28, &
 S/37 DO NOT REFLECT THE RISER DIAGRAM.
 SECTION 104.2.1.
 13) SHTS P2.07.1 & PS.07.2 RISERS DO NOT
 REFLECT THE RISER DIAGRAMS: S/4, S/13,
 S/28, & S/37. FOLLOWING RISERS SHALL
 SHOW DWV PIPING ON THE FLOOR PLAN: S/4,
 S/13, S/15, S/16, S/17, S/19, S/20,
 S/21, S/22, S/23, S/24, S/25, S/28,
 S/37, & S/40. RISER S/29 MISLABLED AS
 S/19. SECTION 104.2.1.
 14) SHTS P2.08.1 & P2.08.2 RISERS S/1,
 S/13, S/28, & S/37 DO NOT REFLECT THE
 RISER DIAGRAMS. SHOW THE DWV PIPING FOR
 THE FOLLOWING RISERS: S/4, S/9, S/12,
 S/13, S/29, S/34, S/37, & S/38. - SHOW
 THE LOCATIONS FOR THE FOLLOWING VTR'S AS
 SHOWN ON RISER DIAGRAMS: S/16, S/19,
 S/20, S/21, S/22, S/23, S/25, & S/40.
 SECTION 104.2.1.
 15) SHTS P2.09.1 & P2.09.2 RISERS S/11,
 S/38, & S/39 DO NOT REFLECT THE RISER
 DIAGRAMS. -RECHECK ALL RISERS FOR DWV
 PIPING ON THE FLOOR PLAN. - TWO #2
 RISERS SHOWN. SECTION 104.2.1.
 16) SHTS P2.10.1 & P2.10.2 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SQUARE FEET OF EACH
 AREA AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS AS WELL AS ALL ROOF AREA THAT
 DRAINS DOWN TO ROOF FROM ABOVE IN
 CALCULATIONS PER SECTIONS 1106 & 1107
 AND ALL SUBSECTIONS. SHOW THE LOCATION
 OF ALL SECONDARY DRAIN AND/OR SCUPPERS.
 SUBMIT A DETAIL FOR SCUPPERS SHOW HEIGHT
 AND WIDTH TO SHOW SQ.IN. AREA OF
 SCUPPER. - INDICATE LOCATION OF ALL VTR.
 17) SUBMIT MANUF. SPECIFICATION SHEET
 FOR DOMESTIC WATER BOOSTER PUMP. PUMP
 SHALL BE LISTED. SECTION 303.4.1.
 18) SHTS P3.07.0 &P3.07.1 ROOF DRAIN,
 OVERFLOW DRAINS, DECK DRAINS, OVERFLOW
 DECK DRAINS, PARKING DRAINS ECT WILL BE
 REVIEWED AFTER THE CALCULATIONS FOR THE
 DRAINS HAS BEEN CHECKED. ONE SET OF ROOF
 DRAINS/OVERFLOW DRAINS (5900 SF) HAS
 BEEN CROSSED BETWEEN THE OVERFLOW AND
 DRAIN. ONE SET OF RWL/OVERFLOW RWL ARE
 SO CLOSE THE SYSTEMS CAN NOT BE CHECKED
 FOR COMPLIANCE. PLANS SHALL HAVE
 SUFFICIENT CLARITY TO REVIEW. - SUMP
 PUMP FOR PARKING AREA DRAINS SHALL BE
 LISTED. SUBMIT MANUF. SPECIFICATIONS
 SHEETS. SECTIONS 303.4.1, & 104.2.1.
 19) SHTS A2.03, A2.09, & A4.91 THRU
 A4.95 SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS. SHOW SQUARE
 FEET OF EACH AREA, AND SHOW 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS,
 AS WELL AS AREAS OF ROOFS THAT DRAIN
 ONTO THE ROOF AREAS FROM ABOVE ADDED IN
 CALCULATIONS. SECTIONS 1106, AND 1107
 AND ALL SUBSECTIONS.
 20) SHT A1.06 SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH FHA REQUIREMENTS 3 THRU
 7, PAGE 7.33 FOR TOWNHOUSE UNITS. POWDER
 ROOM SHALL BE COMPLIANT.
 21) SHT A1.06 PROVIDE A TYPICAL 2/3 BD
 UNIT. SECTION 104.2.1.
 22) SHT A1.06 DETAIL 06/A-1.06 INDICATE
 IF THIS IS SPECIFICATION "A" OR "B"
 23) SHT A1.06 ALL UNITS, MINIMUM
 OPENINGS FOR THE W/C IS 33". THE W/C
 SHALL BE 18" OFF THE WALL FROM
 CENTERLINE OF FIXTURE IF WALL IS
 AVAILABLE. PROVIDE INFORMATION ON
 TYPICAL UNITS SHEET.
 24) SHOW BACKING FOR UNITS PER
 SPECIFICATION 6 OF THE FHA DESIGN MANUAL
 25) SHTS A4.32 & A4.35 SECONDARY ROOF
 DRAINS, (OVERFLOW DRAINS) SHALL BE
 LOCATED 2" ABOVE THE PRIMARY ROOF DRAINS
 PER SECTION 1503.4.2. PLEASE INDICATE
 HOW THIS WILL BE ACCOMPLISHED. IN SOME
 AREAS THE OVERFLOW DRAIN IS IN CLOSE
 PROXIMITY TO THE PRIMARY ROOF DRAIN.
 SECTION 1503.4.2.
 26) SHTS A4.91 THRU A4.95 SHOW THE
 LOCATION OF ALL PRIMARY AND SECONDARY
 ROOF DRAINS. SECTION 104.2.1.
 27) SHT A7.05 INDICATE HEIGHT AND WIDTH
 OF SCUPPERS AT DETAIL 1/A7.05. SECTION
 104.2.1.
 28) SHT A9.08 PUBLIC TOILET ROOMS, NON
 ABSORBENT WALLS UP TO A HEIGHT OF 4 FT.
 REQUIRED PER SECTION 1204.2
 29) INFORMATIONAL: SEPARATE PERMIT
 REQUIRED FOR POOL AND IRRIGATION.
 SECTION 104.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2006-03-15 Cont ID  
Sent By eschneid Date 2006-03-15 Time 16:27 Rev Time 0.00
Received By eschneid Date 2006-03-15 Time 16:27 Sent To  
Notes
2006-03-15 00:00:00VARIANCE EXPIRED.

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-04-15 Time   Rev Time  
Received By   Date   Time   Sent To I
Notes
***NONE***