| 2005-04-18 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05031504 |
| | ADD: 2323 N FLAGLER DR |
| | CONT:FIRST BLDG CORP OF FLORIDA |
| | TEL:(954)561-4900 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE IF A COMMENT IS MADE ON A |
| | PARTICULAR SHEET THIS COMMENT MAY NOT |
| | APPEAR ON OTHER SHEET. |
| | |
| | LOOK FOR COMMENTS BY OTHER PLAN REVIEW |
| | DISCIPLINES THAT MAY BE WRITTEN ON THE |
| | APPLICATION, PLANS, OR ATTACHED |
| | SEPARETLY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NESSARY. |
| | A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND, |
| | WILL HELP EXPEDITE YOUR PERMIT . THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 3) THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES |
| | BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'.A 'UNITY OF TITLE' SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. |
| | SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | |
| | 4) FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | |
| | 5) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS |
| | FOR THE BUILDING WHICH ARE REQUIRED TO |
| | BE SIGNED AND SEALED BY THE ARCHITECT OR |
| | ENGINEER OF RECORD CON- TAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR |
| | ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 6) SHEET A2.01, A2.02 REFERNCES THE TERM |
| | "TOWNHOUSE", THE LEGAL TERM (DEFINITION) |
| | IS A SINGLE FAMILY DWELLING CONSTRUCTED |
| | IN A SERIES OF ATTACHED UNITS WITH |
| | PROPERTY LINES SEPERATING EACH UNIT. SEE |
| | DEFINITIONS. |
| | |
| | 7) SHEET A2.00 DOESN'T INDICATE THE |
| | STRUCTURAL WALL LINE ON THE WEST END OF |
| | THE LOWER PARKING PLAN, 104.2.1.2* |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 8) A2.01 DOESN'T INDICATE BARRIERS IN |
| | THE STAIRWELLS THAT LEAD TO BELOW GRADE. |
| | SEE 1005.6.6 A STAIRWAY IN A SMOKEPROOF |
| | ENCLOSURE SHALL NOT CONTINUE BELOW THE |
| | GRADE LEVEL UNLESSS AN APPROVED BARRIER |
| | IS PROVIDED AT THE GROUND LEVEL TO |
| | PREVENT PERSONS FROM ACCIDENTALLY |
| | CONTINUING INTO THE BASEMENT. |
| | |
| | 9) THE PRIMARY ENTRY DOOR OF COVERED |
| | DWELLING UNITS IS PART OF PUBLIC AND |
| | COMMON USE SPACES, THEREFORE, IT MUST BE |
| | ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE, |
| | I.E., MEET THE ANSI REQUIREMENTS OF |
| | 4.13 DOORS. ANSI 4.13.9 LEVER OR OTHER |
| | EASY USE DOOR HARDWARE. |
| | THE UNITS 110-116 HAVE STAIRS ON THE |
| | ENTERNAL HALLWAYS MAKING THEM |
| | INACCESSIBLE TO THE HANDICAPPED. |
| | |
| | 10) 1012.1.2 EGRESS DOORS SHALL BE SIDE |
| | SWINGING TYPE. DOORS SHALL SWING IN THE |
| | DIRECTION OF EGRESS FOR THE FOLLOWING: |
| | SHEETA2.01 CORRIDOR 133, THE DOOR |
| | LEADING INTO CORRIDOR 132 SHOULD HAVE A |
| | REVERSED SWING, DIRECTION OF TRAVEL IN A |
| | EXIT. |
| | |
| | 11A) CORRIDOR 132 (SHEET A4.04) |
| | INDICATES THAT THERE IS A ENTRANCE INTO |
| | UNIT# 116, THIS CORRIDOR IS AN EXTENSION |
| | OF THE 2 HR RATED STAIRWAY, A EXIT |
| | PASSAGE SHALL HAVE THE SAME RATING AS |
| | THE STAIRWAY, 1005.6.5A SMOKEPROOF |
| | ENCLOSURE SHALL EXIT INTO A PUBLIC WAY |
| | OR INTO AN EXIT PASSAGE, YARD OPEN COURT |
| | OR OPEN SPACE HAVING DIRECT ACCESS TO A |
| | PUBLIC WAY. THE EXIT PASSAGE SHALL BE |
| | WITHOUT OTHER OPENINGS AND SHALL HAVE |
| | WALLS,FLOORS, AND CEILING OF 2-HR FIRE |
| | RATING. |
| | |
| | 11B) THIS SAME CORRIDOR ALSO HAS A |
| | STORAGE ROOM DOOR THAT OPENS INTO THIS |
| | 2HR EXIT PASSAGE, 1005.6.5. |
| | |
| | 11C) A4.04, CORRIDOR# 132, THE DOOR |
| | SCHEDULE FOR THE FIRST FLOOR (A9.02) |
| | INDICATES DOORS 10,11) TO HAVE THE WRONG |
| | NUMBER IDENTIFYING THEM, AND RATING. |
| | |
| | 11D) A9.02 DOOR SCHEDULE FOR THE |
| | TOWNHOUSE AND FIRST FLOOR LEVEL ARE |
| | NUMBERED THROUGH TO 30, THERE OTHER |
| | MISSING NUMBERED WITH AN IDENTIFYING |
| | NUMBER HIGHER THAN THIS. |
| | |
| | 11E) THE TOWNHOUSE ENTRY DOORS ARE NOT |
| | IDENTIFIED & NOT INCLUDED IN THE DOOR |
| | SCHEDULE NOR RATING. |
| | |
| | 12) SHEET A2.01 CORRIDOR# 138: |
| | 1003.2.7.2 WHERE CHANGES IN ELEVATION OF |
| | 12 IN.(305 MM) OR LESSOCCUR IN |
| | EXIT ACCESS CORRIDORS, EXITS AND EXIT |
| | DISCHARGE, RAMPS COMPLYING WITH ?1013 |
| | SHALL BE PROVIDED. |
| | |
| | 13) SHEET A4.01: |
| | A) ALL TOWNHOUSE ENTRY DOORS LEADING |
| | FROM THE GARAGE TO THE UNITS ARE NOT |
| | INCLUDED ON DOOR SCHEDULE NOR RATING. |
| | |
| | B) DOOR #21 IN DOOR SCHEDULE IS |
| | INDICATING BEING INSTALLED IN THE MECH |
| | ROOM, NO FIRE RATING TABLE 705.1.2 |
| | |
| | C) TRASH ROOM DOORS #22 TO BE 3/4 HR |
| | RATING, T ABLE 705.1.2 SAME WITH #23 |
| | |
| | D)STAIR TOWER DOOR #31 NOT LISTED IN |
| | DOOR SCHEDULE, NO RATING |
| | |
| | E) POWDER ROOM & CLOSET DOORS ARE NOT |
| | IDENTIFIED. |
| | |
| | F) BOTTOM LEFT CORNER "BARRIER CABLES" |
| | SEE DETAIL 7/A8.02 WRONG REFRENCE? |
| | SAME REFRENCE ON A4.02 |
| | |
| | G) SEE 11-4.1.3(8)(D) ENTRANCES THAT ARE |
| | NOT ACCESSIBLE SHALL HAVE DIRECTIONAL |
| | SIGNAGE COMPLYING WITH 11-4.30.1, |
| | 11-4.30.2, 11-4.30.3 & 11-4.30.5. |
| | |
| | H) A4.01 UNIT# 111, COMMON TO QUITE A |
| | FEW UNITS, ANSI 4.13.6. THERE IS TO BE |
| | 18" CLEAR ON THE LATCH SIDE OF THE DOOR |
| | (PULL SIDE) FOR ACCESSIBLE DOORS.THIS IS |
| | FOR DOORS LOCATED IN COMMON AREAS ALSO. |
| | NOTE USABLE DOORS SHALL REQUIRE A CLEAR |
| | 32 INCHES.USABLE DOORS ARE SECONARY |
| | ENTRANCE DOORS OR DOORS THAT ALLOW FOR |
| | PASSAGE WITHIN THE DWELLING UNIT. |
| | |
| | |
| | 14) SHEET A4.03 |
| | A) STAIRWELL NOT LABELED, MAYBE #5: THIS |
| | SHALL APPLY TO ALL STAIRS, AT THE BOTTOM |
| | OF LANDINGS UNDER THE STAIR CARRIAGE, |
| | 11-4.4.2 HEAD ROOM, IF VERTICAL |
| | CLEARENCE OF AN AREA ADJOINING AN |
| | ACCESSIBLE ROUTE IS REDUCED TO LESS THAN |
| | 80"INCHESA BARRIER TO WARN BLIND OR |
| | VISUALLY-IMPAIRED PERSONS SHALL BE |
| | PROVIDED. |
| | |
| | B) PROVIDE ADDITIONAL INFORMATION ON |
| | TECTUM FINALE PANELS, PROVIDE FIRE |
| | RATINGS, |
| | |
| | C) CORRIDOR 132 DOESN'T PROVIDE VERTICAL |
| | ACCESSIBILITY, NO RAMP. 11-4.1.2 |
| | VERTICAL ACCESSIBILITY, NOTHING IN THIS |
| | CODE SHALL BE CONSTRUED TO RELIEVE THE |
| | OWNER OF ANY BUILDING, SSTRUCTURE OR |
| | FACILITY FROM THE DUTY TO PROVIDE |
| | VERTICAL ACCESSIBILITY TO ALL LEVELS |
| | ABOVE OR BELOW THE OCCUPIAABLE GRADE |
| | LEVEL. |
| | |
| | D) CORRIDOR #132 DOOR #02 MISSING THE |
| | 1 1/2 HR RATING, TABLE 705.2.1. |
| | |
| | 15) SHEET A4.05: |
| | A) INDICATES 2 UNITS THAT |
| | DO NOT MEET THE ACCESSIBILTY |
| | REQUIREMENTS FOR FAIR HOUSING.SEE 1.21 |
| | BUILDINGS WITH ELEVATORS. |
| | |
| | B) SHEET A4.04/ A4.05 INDICATE STAIRS |
| | WITHIN THE 1ST FLOOR, NOT THE STAIRS TO |
| | THE SECOND FLOOR OF THE UNIT. THE FIRST |
| | FLOOR IS TO BE ACCESSIBLE.FAIR HOUSING |
| | INDICATES ON PAGE 1.22 THAT UNITS THAT |
| | ARE SERVICED BY AN ELEVATOR ARE TO BE |
| | ACCESSIBLE FOR THAT FLOOR.ELEVATORS MUST |
| | PROVIDE ACCESS TO PRIMARY ENTRY DOORS OF |
| | TWO-STORY DWELLING IN ELEVATOR BUILDINGS |
| | SEE FAIR HOUSING GUIDELINES ON PAGE 4.4 |
| | CHANGES IN LEVEL. WITHIN SINGLE STORY |
| | DWELLING UNITS( AND ON THE PRIMARY ENTRY |
| | LEVEL OF A MULTISTORY DWELLING UNITS IN |
| | BUILDINGS WITH ELEVATORS) THE MAXIMUM |
| | VERTICAL FLOOR LEVEL CHANGE IS 1/4 INCH, |
| | EXCEPT WHEN A TAPERED THRESHOLD IS USED |
| | ,THE MAXIMUM HEIGHT IS 1/2 INCH. |
| | |
| | 16)SHEET A4.06 |
| | A) PLANS INDICATE A 1/2 INCH DIFFERENCE |
| | IN GRADE AT THE ENTRANCE TO EACH |
| | DWELLING UNIT, THE DETAILS ON A9.10 |
| | STOREFRONT DETAIL "B" INDICATE A 3/4" |
| | CHANGE IN GRADE PLUS THE THRESHOLD.SEE |
| | FAIR HOUSING THRESHOLDS AT EXTERIOR |
| | DOORS FOR CORRECTION OF THRESHOLDS. |
| | |
| | B) PLANS FOR STAIRWELL RAILINGS/ |
| | GAURDRAILS INDICATE DETAILS ON A8.01 |
| | DETAIL# 1, THE BOTTOM RAIL ON THE STAIRS |
| | SHALL COMPLY WITH: |
| | 1015.3(1) A 6 INCH SPHERE SHALL NOT PASS |
| | THROUGH THE TRIANGLE OPENING FORMED BY A |
| | TREAD , RISER AND THE BOTTOM OF A |
| | GUARDRAIL. |
| | |
| | 17) SHEET A4.07 |
| | A) DISCREPANCY BETWEEN A2.01.1 & A4.07 |
| | SHEET A2.01.1 EAST OF STAIRWELL# 4 |
| | INDICATES A STORAGE AREA, A4.07 DOESN'T |
| | INDICATE STORAGE AREA, THE SECOND ISSUE |
| | IS ON A4.07 THE AREA EAST OF THIS HAS A |
| | DOORWAY WITH NO ROOM IDENTIFICATION, |
| | PLANS INDICATE THE USE OF TECTUM FINALE |
| | PANELS PROVIDE FIRE AND SMOKE |
| | DEVELOPMENT INFORMATION. |
| | |
| | B) THIS SAME AREA INDICATES SOME TYPE OF |
| | |
| | OPENINGS IN THE INTERIOR AS WELL AS |
| | EXTERIOR WALLS BUT NO INFO? CHECKING |
| | ELEVATIONS IS THIS AREA FOR VENTILATION |
| | IN BOTH WALLS? |
| | |
| | 18) A4.11 VS A9.02 STAIRWELL AND |
| | ELEVATOR LOBBY DOOR FIRE RATINGS AND |
| | STYLE ARE REVERSED IN THE DOOR SCHEDULE. |
| | |
| | 19) A4.13 VS A9.02 STAIRWELL #1 DOOR IS |
| | LABELED 3/4 HR IN DOOR SCHEDULE. |
| | |
| | 20) A4.14 INDICATES A 1/2 INCH CHANGE IN |
| | GRADE, FAIR HOUSING MAX 1/4". |
| | |
| | 21) A4.16 INDICATES A DOOR # 20 TO A |
| | MECHANICAL ROOM MISSING ON A9.02 DOOR |
| | SCHEDULE. |
| | |
| | 22) A4.21/ A4.23 HAVE ELEVATOR LOBBIES, |
| | THE WINDOW IN THE LOBBY DOESN'T INDICATE |
| | |
| | ANY FIRE RATING, SEE 412.6(1)1HR WALLS |
| | REQUIRE 20-MINUTE OPENING PROTECTIVES. |
| | |
| | 23) A4.31 THERE ARE RATED WALLS 1 & 2 HR |
| | THAT DO NOT INDICATE WHICH SYSTEM SHOULD |
| | BE USED? |
| | |
| | 24) A4.34: |
| | A) THE COMMUNITY ROOM, FAIR HOUSING |
| | INDICATES THAT THE ACCESSIBLE |
| | ROUTE TO THE SUN DECK IS DISCREMINTORY |
| | BECAUSE OF THE TRAVEL DISTANCE REQUIRED |
| | IF YOU ARE HANDICAPPED. |
| | |
| | 25) A4.35: |
| | A) PLANS INDICATE THAT THE SECONARY |
| | ENTRY DOOR ( TERRACE) FROM UNITS ONTO |
| | THE PATIO BUT NOT ACCESSIBILE BECAUSE OF |
| | THE STEPSONTO THE SUN DECK.THIS IS |
| | DISCRIMINATING AGAINST THE HANDICAPPED |
| | BECAUSE THE HANDICAPPED HAVE TO USE |
| | ANOTHER ROUTE. |
| | CONTACTED BARBRA CHANDLIER/ FAIR HOUSING |
| | |
| | B) THE SECOND ISSUE WITH THIS ROUTE IS |
| | THE GATE HAS TO BE A MINIMUM OF 32" |
| | CLEAR FOR A SECONARY EXTERIOR DOORWAY. |
| | PAGE 3.10 |
| | |
| | C) HANDRAILS WILL BE REQUIRED FOR A |
| | CHANGE IN GRADE OVER 6". |
| | |
| | 26) A4.36 THE PLANS APPEAR TO HAVE (2) |
| | COLUMNS IN THE ROOM ,1 IN THE MIDDLE OF |
| | A DOORWAY UNIT 303? |
| | |
| | 27) A4.43 UNIT 405 IT APPEARSTHAT 2 |
| | COLUMNS APPEAR AS COMMENT ABOVE. |
| | |
| | 28) A4.46 THE KEY PLAN DOES NOT MATCH |
| | THE CONFIGURATION OF THE BUILDING, THIS |
| | IS THE SOUTHWEST CORNER OF THE BUILDING |
| | |
| | 29) A4.53 SAME COMMENT AS 26 ROOM 505. |
| | |
| | 30) A4.63 SAME COMMENT AS 26 ROOM 605. |
| | |
| | 31) A4.65 SAME COMMENT AS 26 ROOM 603. |
| | |
| | 32 A4.72 SAME COMMENT AS 26 ROOM 705. |
| | |
| | 33) A4.74 SAME COMMENT AS 26 ROOM 703. |
| | |
| | 34) A4.71/ A4.72/ A2.07: |
| | A) 1004.1.4 WHERE 2 OR MORE EXITS OR |
| | EXIT ACCESS DOORS ARE REQUIED, AT LEAST |
| | 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL |
| | BE PLACED A DISTANCE APART EQUAL TO NOT |
| | LESS THAN 1/2 OF THE LENGTH OF THE MAX- |
| | IMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED, REDUCED |
| | TO 1/3 THE DIAGONAL FOR FIRE SPRINKLERED |
| | SPRINKLERS. |
| | |
| | 35)A8.01/DETAILS 7&8,A8.03 /12 |
| | ARCHITECTURAL TRIM |
| | TYPE I, II CONSTRUCTION OR MORE THAN |
| | 40', SHALL BE SECURED TO THE WALL WITH |
| | METAL OR APPROVED FASTENERS.WHEN TRIM IS |
| | LOCATED ALONG THE TOP OF EXTERIOR WALLS, |
| | IT SHALL BE COMPLETELY BACKED BY THE |
| | EXTERIOR WALL AND SHALL NOT EXTEND OVER |
| | THE TOP OF EXTERIOR WALLS. 1404.1. |
| | |
| | A36) THIS BUILDING HAS BEEN TRATED AS A |
| | BIG SQUARE AS FAR AS WIND ZONES! |
| | 1606.2.2.1/1606.2.2.2 MEMBERES THAT ARE |
| | BOTH PART OF THE MAIN FORCE RESISTING |
| | SYSTEM AND AS COMPONENTS AND CLADDING |
| | SHALL BE DESIGNED FOR EACH SEPERATE LOAD |
| | CASE. LOOKING AT A3.03 THE SOUTH |
| | ELEVATION THE INTERNAL ZONE HAS BEEN |
| | TAKEN FOR THE COMPLETE SOUTH SIDE WITH |
| | THE EXCEPTION OF THE EXTREME END ZONES |
| | TAKEN AS 16'-0". THERE IS NO |
| | CONSIDERATION FOR THE SOCALLED INTERIOR |
| | END ZONES SEE UNITS 601 & 624 FOR |
| | EXAMPLE. THE WIND ALSO WILL PRESSURIZE |
| | ONTO THE NORTH WALL AT THE POOL DECK. |
| | REVISIT PRESSURE ZONES. NO MENTION OF A |
| | PRESSURE DIFFERENCE AT THE ROOF TOP |
| | CABANAS CONSIDERED WHICH ZONE? |
| | |
| | 37)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 38)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) EXTERIOR DOORS GLAZED OR NOT |
| | B) WINDOWS FIXED OR MOVABLE, STOREFRONT |
| | C) LOUVERS |
| | D)STORM SHUTTERS |
| | E) EXTERIOR RAILINGS |
| | F) EFIS SYSTEMS |
| | G) SKYLIGHTS IF USED |
| | H) ROOFING ASSEMBLIES |
| | |
| | 39) 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 40) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 41) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY |
| | NOT COVERED BY 1707.4.2 |
| | (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| | ED FOR A PERIOD EQUAL TO THE QUANITY |
| | 3600/ V WHERE THE TIME PERIOD IS IN |
| | SECTIONS AND V IS IN MILES PER HR TAKEN |
| | FROM FIGURE 1606. THE TIME PERIOD SHALL |
| | ALSO INCLUDE A 10 SECOND PERIOD AT A |
| | LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| | PRESSURE. DADE COUNTY & SBCCI REPORTS |
| | ARE ACCEPTED. |
| | |
| | 42) PLANS DO NOT INDICATE WHERE FAIR |
| | HOUSING INFORMATION CAN BE FOUND, CLEAR |
| | FLOOR SPACE FOR KITCHEN APPLIANCES |
| | BATHROOMS, NOR WHCICH UNITS ARE "A" OR |
| | "B" UNITS. ALSO MISSING IS INFORMATION |
| | FOR BACKING FOR BATHROOMS AND LOCATIONS. |
| | |
| | 43) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |