Plan Review Details - Permit 05031481
Plan Review Stops For Permit 05031481
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-15 Cont ID  
Sent By jleahy Date 2005-06-15 Time 07:13 Rev Time 0.30
Received By jleahy Date 2005-06-15 Time 07:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-30 Cont ID  
Sent By jleahy Date 2005-03-30 Time 15:54 Rev Time 0.05
Received By jleahy Date 2005-03-30 Time 15:54 Sent To  
Notes
2005-03-30 00:00:00NEED LOAD CALCULATION AND DRAWINGS
 SHOWING THE LOCATION, PLUS SIZE OF WIRE
 BREAKERS AND OR FUSES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-07 Cont ID  
Sent By shill Date 2005-06-07 Time 15:35 Rev Time 0.00
Received By shill Date 2005-06-07 Time 15:35 Sent To  
Notes
2005-06-07 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-25 Cont ID  
Sent By adarroug Date 2005-03-25 Time 09:08 Rev Time 0.00
Received By adarroug Date 2005-03-25 Time 09:07 Sent To E
Notes
2005-03-25 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-08 Cont ID  
Sent By pkrauss Date 2005-04-08 Time 12:19 Rev Time 0.20
Received By pkrauss Date 2005-04-08 Time 12:19 Sent To E
Notes
2005-04-08 00:00:00PROVISO:
 DUCT SMOKE DETECTOR REQUIRED IN THE
 SUPPLY AIR DUCT.FAN SHUTDOWN SHALL
 HAVE NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.