| Plan Review Stops For Permit 05031469 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2006-04-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-06 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-06 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2006-04-06 00:00:00 | TRUSS ENGINEERING PREPARED BY S.WALSH |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
F |
Date |
2006-03-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-03-18 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-03-18 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2006-03-18 00:00:00 | ****CORRECTIONS**** | | | ****TRUSS ENGINEERING**** | | | ****THIRD REVIEW**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | FROM PREVIOUS LISTS: | | | | | | 1.)ADDRESSED. | | | | | | 2.)ADDRESSED. | | | | | | 3.)THE SEAL IS TO STATE "LICENSE", NOT | | | "CERTIFICATE".THIS IS REQUIRED | | | EFFECTIVE JANUARY 1, 2006, | | | FAC61G15-23.001(1).SEE THE INFORMATION | | | ON THE FBPE WEBSITE, WWW.FBPE.ORG. | | | | | | NOT ADDRESSED.PLEASE CONTACT FBPE IF | | | YOU HAVE QUESTIONS OR OBJECTIONS. | | | | | | 4.)ALL SUBMITTALS ARE TO BE REVIEWED | | | BY DESIGNER OF RECORD.TRUSS | | | ENGINEERING IS REQUIRED TO BE REVIEWED | | | BY STRUCTURAL ENGINEER OF RECORD | | | FAC61G15-31.003(2). | | | | | | NOT ADDRESSED.PLEASE HAVE STRUCTURAL | | | ENGINEER REVIEW AS REQUIRED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2006-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-02-16 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-02-16 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2006-02-16 00:00:00 | ****CORRECTIONS**** | | | ****TRUSS ENGINEERING**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | FROM PREVIOUS LIST: | | | | | | 1.)PROVIDE A SIGNED AND SEALED TRUSS | | | PLACEMENT PLAN. | | | | | | THIS WAS PROVIDED BUT THE INFORMATION | | | REQUIRED BY FAC61G15-23.002 (TITLE | | | BLOCK) IS NOT ON THE PLAN. | | | | | | 2.)SOME OF THE TRUSS ENGINEERING | | | SHEETS ARE NOT SEALED.THE SHEETS | | | APPEAR TO BE PHOTOCOPIES.ORIGINAL | | | SIGNED, SEALED AND DATED ENGINEERING | | | REQUIRED. | | | | | | NOT ADDRESSED PROPERLY.SIGNATURE STILL | | | APPEARS TO BE A PHOTOCOPY.SOME SHEETS | | | NOT SEALED.THE COVER PAGE WAS SIGNED | | | AND SEALED.IF THIS IS TO SERVE AS AN | | | INDEX SHEET, IT IS TO COMPLY WITH | | | FAC61G15-31.003. | | | | | | NEW COMMENT: | | | | | | 3.)THE SEAL IS TO STATE "LICENSE", NOT | | | "CERTIFICATE".THIS IS REQUIRED | | | EFFECTIVE JANUARY 1, 2006, | | | FAC61G15-23.001(1).SEE THE INFORMATION | | | ON THE FBPE WEBSITE, WWW.FBPE.ORG. | | | | | | 4.)ALL SUBMITTALS ARE TO BE REVIEWED | | | BY DESIGNER OF RECORD.TRUSS | | | ENGINEERING IS REQUIRED TO BE REVIEWED | | | BY STRUCTURAL ENGINEER OF RECORD | | | FAC61G15-31.003(2). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2006-01-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-01-11 |
Time |
16:52 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2006-01-11 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2006-01-11 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)PROVIDE A SIGNED AND SEALED TRUSS | | | PLACEMENT PLAN. | | | | | | 2.)SOME OF THE TRUSS ENGINEERING | | | SHEETS ARE NOT SEALED.THE SHEETS | | | APPEAR TO BE PHOTOCOPIES.ORIGINAL | | | SIGNED, SEALED AND DATED ENGINEERING | | | REQUIRED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2005-12-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-12-25 |
Time |
18:54 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-12-25 |
Time |
18:54 |
Sent To |
|
|
| Notes |
| 2005-12-25 00:00:00 | REVISED LS1, A1, A3, A12 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2005-09-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-09-22 |
Time |
23:28 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-09-22 |
Time |
23:28 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-08-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-14 |
Time |
11:41 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-08-14 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2005-08-14 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)SUBMIT ORIGINALS FOR THE ROOF | | | ENGINEERING. | | | | | | 2.)SUBMIT STATE OR LOCAL PRODUCT | | | APPROVALS FOR THE CONNECTORS FAC9B72. | | | | | | 3.)THE NOC IS EXPIRED (OVER 90 DAYS | | | WITHOUT COMMENCING WORK), FS713.13(2). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-07-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-25 |
Time |
17:03 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-07-25 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2005-07-25 00:00:00 | ***PROVISO*** | | | SUBMIT ORIGINAL ROOF ENGINEERING | | | | | | SUBMIT SHEET S3 AS A REVISION WITH | | | CONNECTORS COMPLIANT WITH FAC9B72 | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-07-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-23 |
Time |
22:49 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-07-23 |
Time |
21:55 |
Sent To |
|
|
| Notes |
| 2005-07-23 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)THE NOC IS EXPIRED, OVER 90 DAYS | | | WITHOUT COMMENCING WORK, FS713.13(2). | | | PLEASE RERECORD TO GET A NEW RECORDING | | | DATE. | | | | | | THE FOLLOWING COMMENTS ARE FROM THE | | | PREVIOUS REVIEW (KEEPING THE SAME | | | COMMENT NUMBERS): | | | | | | 7.)REGARDING THE ROOF PRODUCT APPROVAL | | | SUBMITTED: | | | | | | A. PAGE 11 OF 107 OF THE BUTLER ROOF | | | SYSTEM SUBMITTED STATES THAT THE SYSTEM | | | HAS A 36 PSF MAXIMUM ALLOWABLE UPLIFT. | | | THE WEBSITE WWW.FLORIDABUILDING.ORG HAS | | | A DIFFERENT DOCUMENT (104 PAGES), | | | DIFFERENT PRODUCT NAME.THE PAPERWORK | | | SUBMITTED DOES NOT APPEAR CODE | | | COMPLIANT.THE ENGINEER?S RESPONSE IN | | | REGARDS TO ENHANCED FASTENING IN ZONES 2 | | | AND 3 IS ACKNOWLEDGED BUT I AM UNABLE TO | | | LOCATE THE DESIGN PRESSURES OF 41 AND | | | 76.8.PLEASE HIGHLIGHT UPLIFTS IN THE | | | PRODUCT APPROVAL, AND SUBMIT PAPERWORK | | | CONSISTENT WITH THE STATE WEBSITE, SO | | | THAT CODE COMPLIANCE CAN BE DETERMINED. | | | | | | B. THE PAPERWORK SUBMITTED DOES NOT | | | MATCH THE FLORIDA STATE PRODUCT | | | APPROVAL. | | | | | | C. IF A CODE COMPLIANT PRODUCT APPROVAL | | | IS NOT SUBMITTED PRIOR TO PERMIT | | | ISSUANCE, THE ROOF SUB PERMIT WILL BE | | | VOIDED AND A SEPARATE PERMIT WILL BE | | | REQUIRED. | | | | | | ENGINEER PROVIDED SHEET 9 OF 107 WHICH | | | SHOWS -41 FOR A 4' SPAN.HOWEVER, THE | | | PAPERWORK SUBMITTED IS STILL NOT THE | | | SAME AS ON THE STATE WEBSITE FOR THIS | | | APPROVAL. | | | | | | ENGINEERING FOR THE ENHANCED FASTENING | | | FOR ZONES 2 AND 3 ARE REQUIRED TO BE | | | SIGNED & SEALED ORIGINALS.THE TITLE | | | BLOCK IS TO INCLUDE ALL INFORMATION | | | REQUIRED BY FAC61G15-23.002. | | | | | | 9.)SEE PREVIOUS LIST, ITEM #8. | | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED FOR STRUCTURAL COMPONENTS, | | | FAC9B72.IF YOU ARE GOING TO INSTALL A | | | TESTED/ENGINEERED PRODUCT REQUIRING | | | PRODUCT APPROVAL NOT IN ACCORDANCE WITH | | | MANUFACTURER'S SPECIFICATIONS ON THE | | | WEBSITE, A LOCAL PRODUCT APPROVAL IS | | | REQUIRED.ALSO, ALPINE CANNOT CHANGE | | | THE SPECIFICATION FOR SIMPSON.I HAVE | | | SPOKEN WITH JIM MAMOLA OF ONM&J AND HAVE | | | EMAILED THE STATE TO CONFIRM MY | | | UNDERSTANDING AND TO GET THIS RESOLVED | | | WITH ONM&J.AS DISCUSSED WITH JIM | | | MAMOLA, IF THIS ISSUE DOES NOT GET | | | RESOLVED PRIOR TO PERMIT ISSUANCE THE | | | PERMIT WILL BE ISSUED WITH A PROVISO | | | THAT THE TRUSS TIE DOWN SCHEDULE BE | | | REVISED. | | | | | | THE SIMPSON CONNECTORS DO NOT HAVE | | | FLORIDA STATE APPROVAL FOR THIS | | | APPLICATION.THEY ARE ALSO NOT INCLUDED | | | IN THE SIMPSON CATALOG FOR LIGHT GAGE | | | METAL TRUSSES, SEE ATTACHED (OR SEE | | | CATALOG ONLINE AT STRONG-TIE.COM).IT | | | WAS MY UNDERSTANDING WITH JIM MAMOLA | | | THAT THIS WOULD BE A PROVISO ITEM, BUT | | | SHEET S3 HAS BEEN REVISED AND THE | | | TRANSMITTAL LETTER STATES THAT THIS HAS | | | BEEN ADDRESSED.ALL CONNECTORS REQUIRE | | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL. | | | | | | | | | 10.)A 4X FEE IS REQUIRED TO BE CHARGED | | | FS553.80(2)(B). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-29 |
Time |
10:52 |
Rev Time |
5.00 |
| Received By |
shill |
Date |
2005-06-27 |
Time |
17:13 |
Sent To |
|
|
| Notes |
| 2005-06-29 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)PLEASE PROVIDE THE IMPACT FEE | | | RECEIPT (ONLY THE BILL WAS IN THE | | | PACKAGE). | | | | | | 3.)SEE PREVIOUS LIST, ITEM #4, | | | FBC3206.2, SIDEWALK OBSTRUCTION NOT | | | ALLOWED.THE GATE WAS CHANGED ON A1 TO | | | BE SLIDING BUT SP1 STILL SHOWS THE GATE | | | OVER THE SIDEWALK. | | | | | | 4.) THE HANDRAIL EXTENSIONS ARE SHOWN AT | | | 42IN AT THE STAIR LANDINGS ON A1. | | | PLEASE SEE FBC11-4.9.4, CHAPTER 11 | | | FIGURE 19, FBC1007.5.5.EXTENSIONS NOT | | | SHOWN ON 4-A8 OR A1. | | | | | | 5.)THE STAIR RAIL SERVES AS A | | | GUARDRAIL (FBC1015.1) AND IS TO BE NOT | | | LESS THAN 42IN HIGH, FBC1015.2, A1. | | | | | | 6.)SECTION 2-A8 SHOULD BE REVISED TO | | | ELIMINATE THE LAUNDRY CHUTE (STILL SHOWS | | | THE CHUTE OPENING INTO AN EXIT ACCESS | | | CORRIDOR FBC705.2.4.3).IF THE LAUNDRY | | | CHUTE IS TO REMAIN, PLEASE ADD IT TO THE | | | FLOOR PLAN AND COMPLY WITH FBC705.2.4.3. | | | | | | 7.)REGARDING THE ROOF PRODUCT APPROVAL | | | SUBMITTED: | | | | | | A. PAGE 11 OF 107 OF THE BUTLER ROOF | | | SYSTEM SUBMITTED STATES THAT THE SYSTEM | | | HAS A 36 PSF MAXIMUM ALLOWABLE UPLIFT. | | | THE WEBSITE WWW.FLORIDABUILDING.ORG HAS | | | A DIFFERENT DOCUMENT (104 PAGES), | | | DIFFERENT PRODUCT NAME.THE PAPERWORK | | | SUBMITTED DOES NOT APPEAR CODE | | | COMPLIANT.THE ENGINEER?S RESPONSE IN | | | REGARDS TO ENHANCED FASTENING IN ZONES 2 | | | AND 3 IS ACKNOWLEDGED BUT I AM UNABLE TO | | | LOCATE THE DESIGN PRESSURES OF 41 AND | | | 76.8.PLEASE HIGHLIGHT UPLIFTS IN THE | | | PRODUCT APPROVAL, AND SUBMIT PAPERWORK | | | CONSISTENT WITH THE STATE WEBSITE, SO | | | THAT CODE COMPLIANCE CAN BE DETERMINED. | | | | | | B. THE PAPERWORK SUBMITTED DOES NOT | | | MATCH THE FLORIDA STATE PRODUCT | | | APPROVAL. | | | | | | C. IF A CODE COMPLIANT PRODUCT APPROVAL | | | IS NOT SUBMITTED PRIOR TO PERMIT | | | ISSUANCE, THE ROOF SUB PERMIT WILL BE | | | VOIDED AND A SEPARATE PERMIT WILL BE | | | REQUIRED. | | | | | | 8.)THE DETAILS DATED 9/02/02 PROVIDED | | | BY ALPINE FOR THE SIMPSON CONNECTORS | | | SHOW A STRESS INCREASE FOR STEEL.THIS | | | IS NOT ALLOWED FBC1609.4.3(2).SIMPSON | | | AND USP HAVE REVISED THEIR CATALOG. | | | | | | 9.)SEE PREVIOUS LIST, ITEM #8. | | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED FOR STRUCTURAL COMPONENTS, | | | FAC9B72.IF YOU ARE GOING TO INSTALL A | | | TESTED/ENGINEERED PRODUCT REQUIRING | | | PRODUCT APPROVAL NOT IN ACCORDANCE WITH | | | MANUFACTURER?S SPECIFICATIONS ON THE | | | WEBSITE, A LOCAL PRODUCT APPROVAL IS | | | REQUIRED.ALSO, ALPINE CANNOT CHANGE | | | THE SPECIFICATION FOR SIMPSON.I HAVE | | | SPOKEN WITH JIM MAMOLA OF ONM&J AND HAVE | | | EMAILED THE STATE TO CONFIRM MY | | | UNDERSTANDING AND TO GET THIS RESOLVED | | | WITH ONM&J.AS DISCUSSED WITH JIM | | | MAMOLA, IF THIS ISSUE DOES NOT GET | | | RESOLVED PRIOR TO PERMIT ISSUANCE THE | | | PERMIT WILL BE ISSUED WITH A PROVISO | | | THAT THE TRUSS TIE DOWN SCHEDULE BE | | | REVISED. | | | | | | 10.)SEE ATTACHED FS553.80(2)(B). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-12 |
Time |
17:04 |
Rev Time |
6.00 |
| Received By |
shill |
Date |
2005-05-12 |
Time |
09:24 |
Sent To |
PC |
|
| Notes |
| 2005-05-12 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION. | | | | | | 3.)THE SQUARE FOOTAGE ON THE ENERGY | | | CALC IS DIFFERENT FROM THE AREA | | | CALCULATIONS. | | | | | | 4.)FBC3206.2, SIDEWALK OBSTRUCTION NOT | | | ALLOWED.THE GATE SWINGS OVER THE | | | PUBLIC SIDEWALK, SP1. | | | | | | 5.)FBC 304, GYMNASIUM IS ASSEMBLY | | | OCCUPANCY.PLANS SHOW A GYM ON THE | | | SECOND FLOOR.SHOW OCCUPANCY SEPARATION | | | REQUIRED BY FBC TABLE 704.1 (2 HOUR); | | | REVISE LS1. | | | | | | 6.)ADDITIONAL FEES DUE, SEE ATTACHED | | | (RADON). | | | | | | 7.) A8 SHOWS A 1 HR TENANT SEPARATION | | | BETWEEN THE GYM AND 1ST FLOOR.A 2 HR | | | (OCCUPANCY) SEPARATION REQUIRED. | | | | | | 8.)THE SIMPSON AND ALPINE CONNECTORS | | | SPECIFIED ARE FOR WOOD TRUSSES. | | | FAC9B72, IF YOU ARE GOING TO SPECIFY AND | | | INSTALL A TESTED/ENGINEERED PRODUCT | | | REQUIRING A PRODUCT APPROVAL NOT IN | | | ACCORDANCE WITH THE MANUFACTURER?S | | | SPECIFICATIONS, APPLY FOR A LOCAL | | | PRODUCT APPROVAL AND ENGINEERING/TEST | | | REPORTS.WWW.FLORIDABUILDING.ORG FOR | | | MORE INFORMATION. | | | | | | 9.)THE NOA FOR THE METAL ROOF REQUIRES | | | ENGINEERED ENHANCED FASTENING IN THE | | | PERIMETER AND CORNER ZONES. | | | | | | 10.)THE NOA FOR THE METAL ROOF IS FOR | | | WOOD DECKS.SUBMIT A LOCAL PRODUCT | | | APPROVAL AND ENGINEERING IF YOU WISH TO | | | USE THIS PRODUCT IN THIS APPLICATION, OR | | | SUBMIT PAPERWORK IN ACCORDANCE WITH YOUR | | | JOB CONDITIONS. | | | | | | 11.)PROVIDE PRODUCT APPROVALS FOR THE | | | FIXED GLASS WINDOWS. | | | | | | 12.)OPENINGS WITHIN 10 FEET OF THE | | | EXTERIOR STAIR ARE TO HAVE ? HOUR | | | ASSEMBLIES.OPENINGS ON BOTH THE NORTH | | | AND WEST ELEVATIONS APPEAR TO BE | | | AFFECTED.NOTE ON PLAN (DOOR #27, | | | AFFECTED WINDOWS) AND SUBMIT APPROPRIATE | | | PRODUCT APPROVALS/FIRE RATING | | | INFORMATION. | | | | | | 13.)FBC 705.2.4.3, ACCESS OPENINGS TO | | | LAUNDRY CHUTES SHALL NOT BE LOCATED IN | | | EXIT ACCESS CORRIDORS (2ND FLOOR). | | | | | | 14.)I WAS UNABLE TO LOCATE DOOR #24 ON | | | THE PLAN.PLEASE PROVIDE DIRECTION AND | | | PRODUCT APPROVAL IF THIS IS ON THE PLAN. | | | | | | 15.)PROVIDE A DETAIL FOR THE STAFF | | | LOUNGE SINK, FBC11-4.24. | | | | | | 16.)HANDRAIL REQUIRED BOTH SIDES, | | | EXTERIOR STAIR, FBC1007.5.2. | | | | | | 17.)PROVIDE DESIGN CRITERIA FOR | | | HANDRAILS AND GUARDRAILS, FBC1608.2. | | | | | | 18.)THE STAIR HANDRAILS, A10, REQUIRE | | | EXTENSIONS AT TOP AND BOTTOM | | | FBC1007.5.5. | | | | | | 19.)THE DOORS IN A SERIES, VESTIBULE | | | (124), SHEET A1, ARE TO COMPLY WITH | | | FBC11 FIGURE 26. | | | | | | 20.)PROVIDE A DETAIL FOR THE GUARDRAIL | | | AND HANDRAIL FOR THE EXTERIOR STAIRS. | | | | | | 21.)IDENTIFY THE FIRE RATED WALL IN | | | ACCORDANCE WITH FBC704.2.1.4. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-21 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-21 |
Time |
07:05 |
Sent To |
PC |
|
| Notes |
| 2006-08-21 00:00:00 | GEN AS-BUILTS/ REVSIONS. | | | | | | GEN /ATS IS NOT UNDER THIS PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-06-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-12 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-12 |
Time |
13:44 |
Sent To |
PC |
|
| Notes |
| 2006-06-12 00:00:00 | REV TO FLR LAYOUT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-12-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-21 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-21 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2005-12-21 00:00:00 | REDLINED. | | | | | | GEN/ ATS NOT IN SCOPE OF THIS PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-12 |
Time |
20:27 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-07-12 |
Time |
20:27 |
Sent To |
|
|
| Notes |
| 2005-07-12 00:00:00 | PLANS NOTED FOR GENERATOR/ATS/FUEL TANK | | | TO BE INSTALLED UNDER SEPARATE PERMITS. | | | NOTED AS "FUTURE" BY ENGINEER. | | | | | | PLANS ALSO NOTED BY ENGINEER, LIGHTNING | | | PROTECTION SYSTEM TO BE UNDER SEPARATE | | | PERMIT AND INSTALLED PER NFPA-780. | | | | | | ELECTRICAL PLANS STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-29 |
Time |
15:22 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2005-06-29 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2005-06-29 00:00:00 | ********UNSAT ******* | | | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEW. | | | | | | 1)NOTE: NOTE #1, NO, PLEASE SEE | | | GENERATOR IS NOTED AS BEING FUTURE, | | | HOWEVER PLEASESEE ATS IS STILL BEING | | | SHOWN AS BEING INSTALLED AND NO SPECS | | | ETC WERE SUBMITTED FOR THIS.?215.5, | | | 225.36 | | | | | | 2)NOTE: NOTE #2, NO, PLEASE SEE RESPONSE | | | LTR MENTIONS LIGHTNING PROTECTION SHALL | | | BE SUBMITTED UDNER SEPARATE PERMIT, | | | HOWEVER, LIGHTING DEVICES ETC ARE STILL | | | BEING SHOWN ON PLANS?? | | | SEE PREVIOUS NOTE. | | | | | | 3)NOTE:PLEASE SEE DOOR SWINGS ON E-1 ,AT | | | GEN/ ELECTRICAL RM AREA. | | | PLEASE CORRELATE WITH E-2 , AND A-1. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-04-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-18 |
Time |
12:22 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-04-18 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2005-04-18 00:00:00 | ********** UNSAT ************** | | | | | | 1)NOTE" PLEASE SEE IF GENERATOR IS GOING | | | TO BE INCLUDED UNDER BASE BLDG PERMIT, | | | PLEASE SUBMIT ALL MANUFACTURE SPEC | | | SHEETS FOR GENERATOR, ATS, SUB BASE FUEL | | | TANK. | | | IF NOT UNDER BASE BLDG, THIS WILL BE | | | REQUIRED TO BE UNDER A SEPARATE PERMIT. | | | | | | 2)NOTE: PLEASE KNOW, IF "LIGHTING | | | PROTECTION" IS ALSO GOING TO BE UNDER | | | THE BASE BLDG ELECTRICAL PERMIT, PLEASE | | | SHOW DETAILS FOR RODS, CONNECTIONS, ETC. | | | IF SYSTEM IS GOING TO BE INSTALLED BY A | | | LIGHTING PROTECTION SUB-CONTRACTOR, THEN | | | SYSTEM CAN BE SHOWN ON PLANS, HOWEVER IT | | | WILL REQUIRED A SEPARATE PERMIT. | | | PLEASE BE SURE TO SEE NFPA-780 FOR | | | SYSTEMS WHICH APPROVED AND RECOGNIZED | | | AND APPROVED BY NFPA. | | | | | | 3)NOTE: PLEASE SEE 600.5 FOR REQUIRED | | | SIGN CIRCUIT. | | | | | | 4)NOTE: PLEASE SEE AWG FOR AHU SHOWN AS | | | #12, ON 50A OCP. | | | 424.3,240.4,310.16 | | | | | | 5)NOTE: PLEASE CLARIFY LOCATION OF GFI | | | PER 210.63 | | | | | | 6)NOTE: PLEASE CLARIFY SIZE OF AWG FOR | | | INSTA-HOT ON PANEL "G". 8.3KW, W/ 30A | | | OCP AND #12? | | | 240.4,310.16 | | | | | | 7)NOTE: PLEASE CLARIFY, TOP LEFT CORNER | | | OF EACH PANEL, "PANEL TYPE" ALL SHOWN AS | | | ITE ETC, HOWEVER, PANEL "L: MENTIONS | | | VERIFY W/ TEKTRON??? | | | | | | PLEASE SEE OTHER POSSIBLE COMMENTS FROM | | | OTHER REVIEWERS WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-05-05 |
Time |
09:50 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2005-05-05 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2005-05-05 00:00:00 | PASSED WITH PROVISOS: | | | | | | 1. PLEASE NOTE THAT CIVIL PLANS MUST | | | REVIEWED AND APPROVED BY THE PUBLIC | | | UTILITIES AND ENGINEERING FOR ALL THE | | | CONNECTIONS TO THE CITY SERVICES, | | | CONTACT MANNY GONZALEZ, 494-1085. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-12-22 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-12-22 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-12-22 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2005-12-22 00:00:00 | REVISION DATED 11/15/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-08-03 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-03 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-03 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2005-08-03 00:00:00 | PLANS APPROVED PREVIOUSLY | | | | | | STAMPED ON 8/3/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-06-20 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-06-20 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-04-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-04-28 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-04-28 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2005-04-28 00:00:00 | 1) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 2) PLEASE NOTE THAT THE BUILDING IS | | | DESCRIBED AS A TWO STORY STRUCTURE THAT | | | IS 55' IN HEIGHT. SHEET #LS1. | | | | | | 3) THE DOOR SWING APPEARS TO OBSTRUCT | | | MORE THAN 1/2 THE WIDTH OF THE CORRIDOR. | | | SHEET #LS1.- 1ST FLOOR | | | | | | 4) EMERGENCY LIGHTING APPEARS TO BE | | | MISSING IN EGRESS AREAS ON BOTH FLOORS. | | | | | | 5) DRAWINGS DON'T SHOW LOCATIONS OF FIRE | | | HYDRANTS. | | | | | | 7) THE DOUBLE CHECK DETECTOR ASSEMBLY | | | SHALL BE SECURED WITH A CHAIN AND LOCK | | | IN ADDITION TO ELECTRONIC SUPERVISION. | | | | | | 8) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER/FIRE | | | ALARM SYSTEMS. | | | | | | 9) NEW BUILDINGS ARE REQUIRED TO BE | | | MONITORED BY A UL LISTED CENTRAL STATION | | | SERVICE. | | | | | | 10) PLEASE PROVIDE THE LOCATION OF THE | | | FIRE DEPARTMENT CONNECTION. IT SHALL BE | | | LOCATED NOT MORE THAN 150' FROM THE | | | CLOSEST HYDRANT | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-07 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-07 |
Time |
14:15 |
Sent To |
M |
|
| Notes |
| 2006-09-07 00:00:00 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2006-08-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-18 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-18 |
Time |
15:13 |
Sent To |
E |
|
| Notes |
| 2006-08-18 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2006-08-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-18 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-18 |
Time |
13:39 |
Sent To |
M |
|
| Notes |
| 2006-08-18 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2006-06-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-08 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-08 |
Time |
16:21 |
Sent To |
E |
|
| Notes |
| 2006-06-08 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2006-03-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-27 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-27 |
Time |
16:10 |
Sent To |
B |
|
| Notes |
| 2006-03-27 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-03-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-17 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-17 |
Time |
12:00 |
Sent To |
B |
|
| Notes |
| 2006-03-17 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-03-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-06 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-06 |
Time |
08:12 |
Sent To |
Z |
|
| Notes |
| 2006-03-06 00:00:00 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-03-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-04 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-04 |
Time |
16:45 |
Sent To |
B |
|
| Notes |
| 2006-03-04 00:00:00 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-02-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-01 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-01 |
Time |
19:01 |
Sent To |
B |
|
| Notes |
| 2006-02-01 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-01-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-10 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-10 |
Time |
09:22 |
Sent To |
B |
|
| Notes |
| 2006-01-10 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-12-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-30 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-30 |
Time |
12:20 |
Sent To |
Z |
|
| Notes |
| 2005-12-30 00:00:00 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-12-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-05 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-05 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2005-12-20 00:00:00 | TO "COMM" BD#10 | | 2005-12-05 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-13 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-13 |
Time |
13:08 |
Sent To |
B |
|
| Notes |
| 2005-09-13 00:00:00 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-07-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-07 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-07 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2005-07-07 00:00:00 | TO "COMM" BD#40 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-06-01 |
|
|
Cont ID |
|
| Sent By |
jlong |
Date |
2005-06-29 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-01 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2005-06-07 00:00:00 | COMM BOARD #43 | | 2005-06-01 00:00:00 | IN INCOMING AWAITING SPACE ON "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-05-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-12 |
Time |
20:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-03-28 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2005-03-28 00:00:00 | TO "COMM" BD#60 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-09-27 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-09-27 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2006-09-27 00:00:00 | SUBMITTAL OF THE VAV'S |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-08-23 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-23 |
Time |
15:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-02-03 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-02-03 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-26 |
Time |
15:57 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-07-26 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2005-07-26 00:00:00 | COMMENTS PER HAROLD MOSER WERE | | | ADDRESSED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-06-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-06-30 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-06-30 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2005-06-30 00:00:00 | PLAN DENIED | | | 1) PLEASE REFER TO SECTION 307.2.3 | | | AUXILLIARY DRAIN PANS.MINIMUN DEPTH IS | | | 1 1/2IN.AND SHALL NOT BE LESS THAN 3IN. | | | LARGER THAN THE UNIOT. | | | 2) PLEASE REFER TO SECTION 601.3 DRYER | | | AND EXHAUST DUCT CAN NOT BE INSTALLED IN | | | RETURN AIR PLENUMS. | | | 3) PLEASE REFER TO SECTION 602.2.1 | | | MATERALS EXPOSED WITHIN PLENUMS.(ABOVE | | | CEILING RETURNAIR) | | | 4) PLESE REFER TO SECTION 606.4.1 | | | SUPERVISON.DUCT SMOKE DETECTORS. | | | 5)FIRE DAMPER FOR EF#5 ROOM 122 IS NOT | | | REQUIRED PER SECTION 607.1.3 EXECPTION | | | #3 | | | 6) PLESE HAVE THE INSPECTION ON | | | REFRIGERANT LINES BEFOR LINE CHASE IS | | | INSTALLED. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-05-11 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-05-06 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2005-05-11 00:00:00 | DENIED: | | | 1.PLAN SHEET A3 INDICATES THE | | | FOLLOWING ROOMS AS HAVING A 1 HR | | | FLOOR/CEILING ASSEMBLY; 111, 115, 123, | | | 121, 122, 126, 124, 120, 125, 119, 118, | | | 117 & 116.ALSO 2ND FLOOR 200.PLEASE | | | PROVIDE DETAIL FOR THE PENETRATION OF | | | THE DUCT/GRILLES.PLEASE NOTE, FIRE | | | DAMPERS REQUIRED AT CEILING GRILLES. | | | | | | 2.PLAN SHEET M-1 INDICATES FLEX DUCT | | | PENETRATING RATED PARTITIONS WHICH IS | | | NOT PERMITTED EPR 2001 FBC(M)603.5.5. | | | | | | 3.PLAN M-1 INDICATES DRYER EXHAUST | | | DUCT PENETRATING RATED PARTITION & FLOOR | | | CEILING ASSEMBLY IN VIOLATION OF 2001 | | | FBC(M)504.2. | | | | | | 4.PROVIDE ELEVATION FOR THE | | | TERMINATION OF ALL EXHAUST TO THE | | | EXTERIOR WALL UNDER/AT THE STAIRWELL. | | | PER 2001 FBC(M)401.5.2, EXHAUST SHALL | | | TERMIANTE AS TO NOT CREATE A NUISANCE | | | AND SHALL NOT BE DIRECTED ONTO WALKWAYS. | | | | | | 5.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS REQUIRED PER | | | 2001 FBC(M)606.2.1 & 606.4.1 #2. | | | | | | 6.PLAN SHEET M-4, THE AHU DETAIL | | | INDICATES THE AUXILIARY DRAIN LINE "SEE | | | PLUMBING FOR CONTINUATION".THE | | | AUXILIARY LINE IS NOT SHOWN ON THE | | | PLUMBING PLANS.PLEASE NOTE, PER 2001 | | | FBC(M)307.2.3 & 307.2.4, THE AUXILAIRY | | | DRAIN LINE SHALL TERMINATE AT A | | | "CONSPICUOUS" POINT TO SERVE AS AN ALARM | | | THAT THE PRIMARY DRAIN IS RESTRICTED. | | | IN LIEU OF A SECONDARY DRAIN LINE AN | | | APPROVED FLOAT DETECTOR MAY BY USED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2006-02-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-02-24 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-02-24 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2006-02-24 00:00:00 | REVISION OK - SHTS P-1, P-2, P-3, P-4 | | | FLOOR PLAN 1ST FLOOR, 2ND FLOOR, AND | | | RELETED WATER & SANT RISER DIAGRAMS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-08-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-08-05 |
Time |
15:09 |
Rev Time |
1.34 |
| Received By |
kstevens |
Date |
2005-08-05 |
Time |
15:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-06-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-25 |
Time |
07:51 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2005-06-25 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2005-06-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: | | | 1. SHT A1 TOILET ROOMS 109 & 110 SHOW | | | THE TURNING AREA REQUIRED BY SECTION | | | 11-4.22.3. | | | 3. SHT A2 TOILET ROOMS 201 & 209 SHOW | | | THE TURNING AREA REQUIRED BY SECTION | | | 11-4.22.3. | | | 5. SHTS A12 & A13 TOILET ROOM DETAILS, | | | SHOW THE FOLLOWING ACCESSIBLITY | | | REQUIREMENTS ON DETAILS: | | | D. FAUCETS 11-4.19.5 - NO RESPONSE FOR | | | THE LAVS. NOTE ADDED ONLY REFERS TO THE | | | W/C'S. | | | 6. SHT A12 DETAILS FOR STAFF LOUNGE | | | SHALL SHOW THE FOLLOWING: | | | C. SINK DEPTH 11-4.24.4 - NO RESPONSE | | | NOTED. | | | F. FAUCETS 11-4.24.7 - NO RESPONSE FOR | | | THE SINK FAUCET. - NOTE ADDED ONLY | | | REFERS TO THE W/C VALVE. | | | ****************NEW COMMENT************* | | | 1B. SHT A13 TYPICAL FIXTURE MOUNTING | | | HEIGHTS DETAIL: | | | A. 11-4.16.6 DISPENSERS SHALL BE 19" | | | MINIMUM TO CENTERLINE ABOVE THE FLOOR. | | | DETAIL SHOWS 17". FIG 29. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-04-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-23 |
Time |
11:16 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2005-04-23 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2005-04-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A1 TOILET ROOMS 109 & 110 SHOW | | | CLEAR FLOOR SPACE FOR THE FIXTURES AND | | | THE TURNING AREA REQUIRED BY SECTIONS | | | 11-4.16.2, 11-4.19.3 AND 11-4.22.3. | | | 2) SHT A1 DRINKING FOUNTAINS, SHOW THE | | | CLEAR FLOOR SPACE FOR ACCESSIBLE | | | DRINKING FOUNTAINS REQUIRED BY SECTION | | | 11-4.15.5. | | | 3) SHT A2 TOILET ROOMS 201 & 209 SHOW | | | THE CLEAR FLOOR SPACE AND TURNING AREA | | | REQUIRED BY SECTIONS 11-4.16.2, | | | 11-4.19.3 AND 11-4.22.3. | | | 4) SHT A2 SHOW THE CLEAR FLOOR SPACE FOR | | | THE ACCESSIBLE DRINKING FOUNTAIN | | | REQUIRED BY SECTION 11-4.15.5. | | | 5) SHTS A12 & A13 TOILET ROOM DETAILS, | | | SHOW THE FOLLOWING ACCESSIBLITY | | | REQUIREMENTS ON DETAILS: | | | A. TOILET HEIGHT 11-4.16.3 | | | B. FLUSH CONTROLS 11-4.16.5. | | | C. HEIGHT & CLEARANCES 11-4.19.2 | | | D. FAUCETS 11-4.19.5 | | | E. BOTTOM OF MIRROR TO BE 40" NOT 42" | | | AS SHOWN. 11-4.19.6 | | | 6) SHT A12 DETAILS FOR STAFF LOUNGE | | | SHALL SHOW THE FOLLOWING: | | | A. HEIGHT 11-4.24.2 | | | B. KNEE CLEARANCE 11-4.24.3 | | | C. SINK DEPTH 11-4.24.4 | | | D. CLEAR FLOOR SPACE SHALL BE PROVIDED | | | TO ALLOW FORWARD APPROACH AND SHALL | | | EXTEND A MAXIMUM OF 19" UNDERNEATH THE | | | SINK. 11-4.24.2 | | | E. EXPOSED PIPES & SURFACES 11-4.24.6 | | | F. FAUCETS 11-4.24.7 | | | 7) DOORS SHALL NOT SWING INTO THE CLEAR | | | FLOOR SPACE REQUIRED FOR ANY FIXTURE. | | | SECTION 11-4.22.2 | | | 8) SHTS P-1 & P-4 BACKFLOW PROTECTION | | | SHALL BE REQUIRED ON THE SUPPLY LINES TO | | | EACH WATER FEATURE. | | | 9) SEPARATE PERMITS REQUIRED FOR THE | | | WATER FEATURES AS INDICATED BY NOTE ON | | | SHT A1. INFORMATION ON DRAINING | | | FOUNTAINS WILL BE REQUIRED AT THAT TIME. | | | SECTION 104.2.1. | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-03-29 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-03-29 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-03-29 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2006-03-29 00:00:00 | 3/29/2006 ***PASSED*** | | | | | | PER JOHN ROACH, SENIOR PLANNER, | | | PREVIOUSLY-APPROVED CMU WALL MAY BE | | | SUBSTITUTED WITH PRESSURE-TREATED WOOD, | | | AS INDICATED IN SECTION 94-216(D)(2) OF | | | THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-01-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-01-18 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-01-18 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2006-01-18 00:00:00 | DENIED, | | | 1. CANNOT HAVE CHAINLINK AS A SEPERATION | | | FROM RESIDENTIAL IN REAR OF PROPERTY. | | | 2. MUST HAVE A CMU WALL IN REAR OF | | | PROPERTY TO SEPERATE FROM MF14 | | | RESIDENTAL IN BACK OF PROPERTY. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
jlong |
Date |
2005-04-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
jlong |
Date |
2005-06-29 |
Time |
08:42 |
Sent To |
I |
|
| Notes |
|
|