| Plan Review Stops For Permit 05031461 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-09-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-09-26 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2005-09-26 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2005-09-26 00:00:00 | BUILDING REVISION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-08-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-08-17 |
Time |
16:37 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2005-08-17 |
Time |
16:37 |
Sent To |
PC |
|
| Notes |
| 2005-08-17 00:00:00 | BUILDING REVIEW PROVISO: | | | 1- REVISE SCREW SIZE SPECIFIED FOR | | | THD210 CONNECTOR. NEED 1 3/4" MIN. | | | EMBEDMENT. SEE TECHNICAL BULLETIN. | | | 2- STAIR SHOP DRAWINGS: A) NUMBER OF | | | RISERS DON'T MATCH PLANS. REVISE. | | | B) HANDRAIL DIMENSIONS DON'T MATCH PLANS | | | C) SHOW STAIRS SUPPORTED ON CONCRETE | | | WALL. THERE IS A FRAMED WALL. SEE PLANS. | | | D) SAYS DESIGNED PER R311.5.3.2. REVISE, | | | PLANS ARE DESIGNED PER FBC 2001 NOT THE | | | 2004 RESIDENTIAL CODE. | | | 3- ARCHITECT TO SPECIFY ON PLANS ROOF | | | TILE FASTENING AS REQUIRED BY SECTION | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-06-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-06-30 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-06-30 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2005-06-30 00:00:00 | DENIED | | | | | | 1) SUBMIT (2) COPIES OF THE USP | | | TECHNICAL BULLETINS FOR THE THD210 AND | | | THD210-2 MASONRY APPLICATIONS. | | | | | | 2) REVISE THE TRUSS ANCHOR SCHEDULE FOR | | | THE THD210 AND THD210-2 CONNECTORS. THE | | | NUMBER AND SIZE OF THE FASTENERS MUST BE | | | CONSISTENT WITH THE TECHNICAL BULLETINS. | | | THE NUMBER AND SPECIFIC LOCATIONS OF THE | | | MASONRY SCREWS ARE ESSENTIAL FOR THE | | | PROPER PERFORMANCE OF THE HANGERS. | | | | | | 3) SHEET A-8: KEYED DETAILS DON'T MATCH | | | THOSE SHOWN ON DETAIL SHEET. REVISE. SEE | | | ITEM #4 OF FIRST REVIEW. THE KEY ON A8 | | | FOR 3/12 IS AT THE WOOD FRAME WALL TO | | | MASONRY WALL ATTACHMENTS. DETAIL 3 ON | | | SHEET 12 IS FOR LOAD BEARING WALL. | | | | | | 4) ITEM #8 FROM FIRST REVIEW. SUBMIT | | | STATE PRODUCT APPROVALS FOR STRUCTURAL | | | MULLIONS. SPECIFY ON THE PRODUCT | | | APPROVAL THE MULLION APPLICATION THAT | | | WILL BE USED TO MEET THE PRESSURES FOR | | | THE OPENING AT THE 12' WIDE SLIDING | | | GLASS DOORS. | | | | | | 5) SUBMIT AN ADDITIONAL COPY OF THE | | | STAIR SHOP DRAWINGS. | | | | | | 6) THE GUARDRAIL HEIGHT ON DETAIL 3 ON | | | A13 HAS BEEN CHANGED BY WHITE OUT AND A | | | HANDWRITTEN MEASUREMENT. THIS IS NOT | | | ACCEPTABLE. CHANGES TO THE PLANS CAN | | | ONLY BE MADE BY THE DESIGNER OF RECORD. | | | THE GUARDRAILS ARE REQUIRED TO BE A | | | MINIMUM OF 36" HIGH PER FBC 1026.5. | | | HANDRAILS ARE REQUIRED TO BE NOT LESS | | | THAN 34" NOR MORE THAN 38" IN HEIGHT PER | | | FBC 1007.5. PLEASE CORRECT. | | | | | | 7) ITEM #5 FROM PREVIOUS REVIEW. SPECIFY | | | THE ROOF TILE FASTENING AS REQ'D BY SEC. | | | 104.2.1.1 CITY AMENDMENTS TO 2001 FBC. | | | THE REQUIRED AERODYNAMIC UPLIFT MOMENT | | | FOR THIS STRUCTURE IS 26.1 FT.LBS. | | | SPECIFY THE METHOD OF ATTACHMENT THAT | | | WILL BE USED TO RESIST THIS (I.E. THE | | | TYPE AND NUMBER OF MECHANICAL FASTENERS | | | OR TYPE OF ADHESIVE). | | | | | | IF YOU HAVE ANY QUESTIONS CALL: | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-04-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-04-26 |
Time |
15:17 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2005-04-26 |
Time |
15:17 |
Sent To |
PC |
|
| Notes |
| 2005-04-26 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- SHEET A-2: A)KEYED DETAILS DON'T | | | MATCH. THERE IS NOT SHEET A-13. REVISE | | | ALL KEYED DETAILS TO MATCH SPECIFIC | | | DETAIL SHEET AND NUMBER/LETTER. | | | | | | B) DELETE BBQ TO MATCH FLOOR PLAN. | | | | | | C) FOUNDATION NOTE #2. SEE CHAPTER 19 | | | FBC 2001 FOR PROPER CONCRETE REFERENCE. | | | REVISE NOTE AS REQUIRED. | | | | | | 2- SHEET A-3: A) STAIR WINDERS TO HAVE | | | 6" MIN. AT THE NARROWEST EDGE AS REQ'D | | | BY SECTION 1007.8.1 FBC 2001. REVISE. | | | | | | B) KEYED DETAIL/SECTIONS DON'T MATCH. | | | THERE IS NOT SHEET A-13. REVISE ALL | | | DETAILS TO MATCH CORRECT SHEET & NUMBER. | | | | | | C) DESIGN PARAMETERS: WHERE IS THE BASIC | | | VELOCITY PRESSURE TAKEN FROM?. THERE IS | | | NOT MENTION OF THAT IN THE FBC 2001. | | | | | | 3- SHEET A-7: A) REVISE THE TRUSS ANCHOR | | | SCHEDULE. SEE LATEST CATALOGUE OR | | | PROVIDE COMPLETE ENGINEERING CALCS FOR | | | TYPE AND NUMBER OF FASTENERS THAT DIFFER | | | FROM THOSE TESTED AND PUBLISHED BY THE | | | MANUFACTURER. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | B) KEYED DETAILS/SECTIONS DON'T MATCH | | | THOSE SHOWN ON DETAIL SHEET. REVISE AS | | | REQUIRED. | | | | | | 4- SHEET A-8: KEYED DETAILS DON'T MATCH | | | THOSE SHOWN ON DETAIL SHEET. REVISE. | | | | | | 5- SPECIFY ROOF TILE FASTENING AS REQ'D | | | BY SEC. 104.2.1.1 CITY AMENDMENTS TO FBC | | | 2001. | | | | | | 6- PLANS CALL FOR FLAT ROOF TILE. | | | PRODUCT APPROVAL SUBMITTED IS FOR "S". | | | TILE. REVISE PLANS AS REQUIRED. | | | | | | 7- PROVIDE STRUCTURAL BUCK DETAIL FOR: | | | A) WINDOWS. SEE SEC. 1707.4.4.2 FBC 2001 | | | B) DOORS. SEE SEC. 1707.4.4.2 FBC 2001 | | | FOR PROPER BUCK INSTALLATION. | | | C) GARAGE DOOR. | | | | | | 8- CLEARLY SPECIFY SIZE OF MULLION AND | | | ANCHORS TO BE USED FOR DOOR MULLION | | | ABOVE 12'-0" WIDE SLIDING GLASS DOORS. | | | SEE PRODUCT APPROVAL AND VERIFY THAT | | | MULLION WILL MEET THE REQUIRED DESIGN | | | PRESSURES. | | | | | | | | | 9- CLARIFY IF USING THE STEEL DOORS FOR | | | ENTRY DOORS. OTHERWISE, PROVIDE | | | CORRESPONDING PRODUCT APPROVAL. | | | | | | 10 ENERGY CALCULATIONS ARE INCOMPLETE: | | | THIS IS A 2 STORY HOUSE AND CALCULATIONS | | | WERE DONE WITHOUT INCLUDING THE 2ND | | | FLOOR. REVISE AS REQUIRED. | | | | | | 11- OWES $988.89 FOR UPDATED VALUATION | | | AND RADON FEES. | | | | | | 12- PROVIDE STAIRS COMPLETE STAIR | | | FRAMING DETAILS AND SPECS. | | | **PROVIDE HANDRAIL SPECS. SEE SECTION | | | 1007.5 FBC 2001. | | | ***SPECIFY FIREBLOCKING. SEE SEC. | | | 2305.1.4 FBC 2001 | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-04-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-17 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-17 |
Time |
08:04 |
Sent To |
PC |
|
| Notes |
| 2006-04-17 00:00:00 | RISER SHOWS 200A PANEL FOR PANEL "A", | | | WITH 150A FEED. THIS IS OK, HOWEVER DOES | | | NOT CORRELATE WITH PANELS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-03-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-10 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-10 |
Time |
07:06 |
Sent To |
PC |
|
| Notes |
| 2006-03-10 00:00:00 | RISER SHOWS 2/0'S FOR 150A PANELS, THIS | | | IS OK. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-28 |
Time |
20:28 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-07-28 |
Time |
20:17 |
Sent To |
M |
|
| Notes |
| 2005-07-28 00:00:00 | REDLINED GROUNDING ELECTRODE CONDUCTOR | | | TO BE A MIN OF 1/0. 250.66,310.15B6 | | | | | | ELECTRICAL PLANS STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-06-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-22 |
Time |
16:42 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-06-22 |
Time |
16:31 |
Sent To |
M |
|
| Notes |
| 2005-06-22 00:00:00 | ************ UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE NEW RISER DIAGRAM NOW | | | SUBMITTED. PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR TO POOL SUB PANEL, | | | 250.110,250.24,680.6 | | | | | | 2)NOTE: PLEASE SEE ELECTRICAL SHEET HAS | | | NOW COME BACK WITH A DIFFERENT SIGNATURE | | | FOR ARCH OF RECORD THAN SIGNATURE ON | | | FILE FOR ARCH AND DIFERENT FROM | | | SIGNATURE ON OTHER SHEETS. THIS | | | SIGNATURE AS SHOWN IS NOT ACCEPTABLE TO | | | THIS OFFICE. THIS HAS BEEN NOTED ON | | | NUMEROUS PREVIOUS REVIEWS OF OTHER | | | PROJECTS. PLEASE SEE FS 481.221 WHICH | | | REQUIRES THE ARCH TO SIGN,SEAL AND DATE | | | PLANS. THIS MAY ONLY BE DONE BY THE | | | ARCHITECT HOLDING LICENSE AND SAID SEAL. | | | ONE COPY OFELECTRICAL PLANS ARE BEING | | | RETAINED AND SHALL BE PLACED WITH PLANS | | | ALREADY IN RETENTION. THIS WAS SUBMITTED | | | TO THE BLDG OFFICAL AND ALL PLANS SHALL | | | BE TURNED OVER TO THE STATE LEGAL | | | COUNSEL FOR STATE BOARD OF ARCHITECT'S | | | FOR REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-03-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-31 |
Time |
15:41 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-03-31 |
Time |
15:41 |
Sent To |
M |
|
| Notes |
| 2005-03-31 00:00:00 | **** UNSAT **** | | | | | | 1)NOTE: PLEASE SEE PLANS INDICATE A | | | DRYER, HOWEVER PANEL SCHEDULE AND LOAD | | | CALCULATIONS DO NOT SHOW. | | | | | | 2)NOTE: PLEASE SEE PANEL SCHEDULE | | | INDICATES DISHWASHER ON A 2P20A BRKR FOR | | | OCP.? | | | IS THIS PART OF DISPOSAL/DISHWASHER? | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING TO CONDENSING UNITS. | | | PLEASE ALSO SEE 3-#6'S TO COND UNIT. IS | | | THIS 2-#6'S AND ONE #10? | | | PLEASE SEE CONDUIT FILL FOR SCHEDULE 80 | | | PVC. PLEASE SEE EUIPMENT GROUNDING PER | | | 250.122 | | | | | | 4)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | 5)NOTE: PLEASE SEE NUMEROUS BRANCH | | | CIRCUITS WITH 15A OCP ON #12 AWG. THIS | | | IS OK AND DOES MEET CODE, HOWEVER PLEASE | | | VERIFY. IF SHOWN, THEN THIS MUST BE | | | DONE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-04-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-15 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-15 |
Time |
15:09 |
Sent To |
E |
|
| Notes |
| 2006-04-15 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-03-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-09 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-09 |
Time |
15:53 |
Sent To |
E |
|
| Notes |
| 2006-03-09 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-09-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-22 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-22 |
Time |
16:09 |
Sent To |
B |
|
| Notes |
| 2005-09-22 00:00:00 | TO "JGOMEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-28 |
Time |
18:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-28 |
Time |
18:24 |
Sent To |
E |
|
| Notes |
| 2005-07-28 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-20 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-20 |
Time |
14:25 |
Sent To |
E |
|
| Notes |
| 2005-06-20 00:00:00 | TO DVP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-03-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-31 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-31 |
Time |
13:37 |
Sent To |
E |
|
| Notes |
| 2005-03-31 00:00:00 | TO "SFR""E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-04-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-04-26 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2005-03-25 |
Time |
09:00 |
Sent To |
PC |
|
| Notes |
| 2005-03-25 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-19 |
Time |
15:30 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2005-09-19 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2005-08-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-08-02 |
Time |
19:25 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-08-02 |
Time |
19:25 |
Sent To |
B |
|
| Notes |
| 2005-08-02 00:00:00 | DENIED. | | | | | | NO PLANS OR MANUAL J PROVIDED. | | | | | | RONALD J REGUEIRO | | | 561-805-6734 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-28 |
Time |
06:45 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2005-06-28 |
Time |
06:45 |
Sent To |
B |
|
| Notes |
| 2005-06-28 00:00:00 | DENIED: | | | PLEASE PROVIDE MANUAL J CALCULATIONS AS | | | REQUIRED PER 2001 FBC(M) CHAPTER 6. | | | | | | PROVIDE EQUIPMENT SCHEDULE. | | | | | | NO MECHANICAL PLAN PROVIDED FOR REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-04-04 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-04-04 |
Time |
10:40 |
Rev Time |
0.45 |
| Received By |
prafter |
Date |
2005-04-04 |
Time |
10:40 |
Sent To |
P |
|
| Notes |
| 2005-04-04 00:00:00 | MECH. PLAN REVIEW. | | | | | | NO A/C PLANS OR EQUIPMENT INFORMATION. | | | | | | PAT RAFTER 805/6728 OR 805/6719 PATTY | | | KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-28 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-06-28 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2005-06-28 00:00:00 | SEE REVIEW BY PAT RAFTER DATED 4-4-05 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2005-04-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-04-07 |
Time |
17:28 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-04-07 |
Time |
17:28 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-03-30 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-03-30 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-03-30 |
Time |
15:17 |
Sent To |
I |
|
| Notes |
|
|