Plan Review Details - Permit 05031461
Plan Review Stops For Permit 05031461
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-26 Cont ID  
Sent By jgomez Date 2005-09-26 Time 09:55 Rev Time 0.00
Received By jgomez Date 2005-09-26 Time 09:55 Sent To  
Notes
2005-09-26 00:00:00BUILDING REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-17 Cont ID  
Sent By jgomez Date 2005-08-17 Time 16:37 Rev Time 2.00
Received By jgomez Date 2005-08-17 Time 16:37 Sent To PC
Notes
2005-08-17 00:00:00BUILDING REVIEW PROVISO:
 1- REVISE SCREW SIZE SPECIFIED FOR
 THD210 CONNECTOR. NEED 1 3/4" MIN.
 EMBEDMENT. SEE TECHNICAL BULLETIN.
 2- STAIR SHOP DRAWINGS: A) NUMBER OF
 RISERS DON'T MATCH PLANS. REVISE.
 B) HANDRAIL DIMENSIONS DON'T MATCH PLANS
 C) SHOW STAIRS SUPPORTED ON CONCRETE
 WALL. THERE IS A FRAMED WALL. SEE PLANS.
 D) SAYS DESIGNED PER R311.5.3.2. REVISE,
 PLANS ARE DESIGNED PER FBC 2001 NOT THE
 2004 RESIDENTIAL CODE.
 3- ARCHITECT TO SPECIFY ON PLANS ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-30 Cont ID  
Sent By rmcdouga Date 2005-06-30 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2005-06-30 Time 07:36 Sent To  
Notes
2005-06-30 00:00:00DENIED
  
 1) SUBMIT (2) COPIES OF THE USP
 TECHNICAL BULLETINS FOR THE THD210 AND
 THD210-2 MASONRY APPLICATIONS.
  
 2) REVISE THE TRUSS ANCHOR SCHEDULE FOR
 THE THD210 AND THD210-2 CONNECTORS. THE
 NUMBER AND SIZE OF THE FASTENERS MUST BE
 CONSISTENT WITH THE TECHNICAL BULLETINS.
 THE NUMBER AND SPECIFIC LOCATIONS OF THE
 MASONRY SCREWS ARE ESSENTIAL FOR THE
 PROPER PERFORMANCE OF THE HANGERS.
  
 3) SHEET A-8: KEYED DETAILS DON'T MATCH
 THOSE SHOWN ON DETAIL SHEET. REVISE. SEE
 ITEM #4 OF FIRST REVIEW. THE KEY ON A8
 FOR 3/12 IS AT THE WOOD FRAME WALL TO
 MASONRY WALL ATTACHMENTS. DETAIL 3 ON
 SHEET 12 IS FOR LOAD BEARING WALL.
  
 4) ITEM #8 FROM FIRST REVIEW. SUBMIT
 STATE PRODUCT APPROVALS FOR STRUCTURAL
 MULLIONS. SPECIFY ON THE PRODUCT
 APPROVAL THE MULLION APPLICATION THAT
 WILL BE USED TO MEET THE PRESSURES FOR
 THE OPENING AT THE 12' WIDE SLIDING
 GLASS DOORS.
  
 5) SUBMIT AN ADDITIONAL COPY OF THE
 STAIR SHOP DRAWINGS.
  
 6) THE GUARDRAIL HEIGHT ON DETAIL 3 ON
 A13 HAS BEEN CHANGED BY WHITE OUT AND A
 HANDWRITTEN MEASUREMENT. THIS IS NOT
 ACCEPTABLE. CHANGES TO THE PLANS CAN
 ONLY BE MADE BY THE DESIGNER OF RECORD.
 THE GUARDRAILS ARE REQUIRED TO BE A
 MINIMUM OF 36" HIGH PER FBC 1026.5.
 HANDRAILS ARE REQUIRED TO BE NOT LESS
 THAN 34" NOR MORE THAN 38" IN HEIGHT PER
 FBC 1007.5. PLEASE CORRECT.
  
 7) ITEM #5 FROM PREVIOUS REVIEW. SPECIFY
 THE ROOF TILE FASTENING AS REQ'D BY SEC.
 104.2.1.1 CITY AMENDMENTS TO 2001 FBC.
 THE REQUIRED AERODYNAMIC UPLIFT MOMENT
 FOR THIS STRUCTURE IS 26.1 FT.LBS.
 SPECIFY THE METHOD OF ATTACHMENT THAT
 WILL BE USED TO RESIST THIS (I.E. THE
 TYPE AND NUMBER OF MECHANICAL FASTENERS
 OR TYPE OF ADHESIVE).
  
 IF YOU HAVE ANY QUESTIONS CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By jgomez Date 2005-04-26 Time 15:17 Rev Time 2.00
Received By jgomez Date 2005-04-26 Time 15:17 Sent To PC
Notes
2005-04-26 00:00:00BUILDING REVIEW CHECKLIST:
 1- SHEET A-2: A)KEYED DETAILS DON'T
 MATCH. THERE IS NOT SHEET A-13. REVISE
 ALL KEYED DETAILS TO MATCH SPECIFIC
 DETAIL SHEET AND NUMBER/LETTER.
  
 B) DELETE BBQ TO MATCH FLOOR PLAN.
  
 C) FOUNDATION NOTE #2. SEE CHAPTER 19
 FBC 2001 FOR PROPER CONCRETE REFERENCE.
 REVISE NOTE AS REQUIRED.
  
 2- SHEET A-3: A) STAIR WINDERS TO HAVE
 6" MIN. AT THE NARROWEST EDGE AS REQ'D
 BY SECTION 1007.8.1 FBC 2001. REVISE.
  
 B) KEYED DETAIL/SECTIONS DON'T MATCH.
 THERE IS NOT SHEET A-13. REVISE ALL
 DETAILS TO MATCH CORRECT SHEET & NUMBER.
  
 C) DESIGN PARAMETERS: WHERE IS THE BASIC
 VELOCITY PRESSURE TAKEN FROM?. THERE IS
 NOT MENTION OF THAT IN THE FBC 2001.
  
 3- SHEET A-7: A) REVISE THE TRUSS ANCHOR
 SCHEDULE. SEE LATEST CATALOGUE OR
 PROVIDE COMPLETE ENGINEERING CALCS FOR
 TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 B) KEYED DETAILS/SECTIONS DON'T MATCH
 THOSE SHOWN ON DETAIL SHEET. REVISE AS
 REQUIRED.
  
 4- SHEET A-8: KEYED DETAILS DON'T MATCH
 THOSE SHOWN ON DETAIL SHEET. REVISE.
  
 5- SPECIFY ROOF TILE FASTENING AS REQ'D
 BY SEC. 104.2.1.1 CITY AMENDMENTS TO FBC
 2001.
  
 6- PLANS CALL FOR FLAT ROOF TILE.
 PRODUCT APPROVAL SUBMITTED IS FOR "S".
 TILE. REVISE PLANS AS REQUIRED.
  
 7- PROVIDE STRUCTURAL BUCK DETAIL FOR:
 A) WINDOWS. SEE SEC. 1707.4.4.2 FBC 2001
 B) DOORS. SEE SEC. 1707.4.4.2 FBC 2001
 FOR PROPER BUCK INSTALLATION.
 C) GARAGE DOOR.
  
 8- CLEARLY SPECIFY SIZE OF MULLION AND
 ANCHORS TO BE USED FOR DOOR MULLION
 ABOVE 12'-0" WIDE SLIDING GLASS DOORS.
 SEE PRODUCT APPROVAL AND VERIFY THAT
 MULLION WILL MEET THE REQUIRED DESIGN
 PRESSURES.
  
  
 9- CLARIFY IF USING THE STEEL DOORS FOR
 ENTRY DOORS. OTHERWISE, PROVIDE
 CORRESPONDING PRODUCT APPROVAL.
  
 10 ENERGY CALCULATIONS ARE INCOMPLETE:
 THIS IS A 2 STORY HOUSE AND CALCULATIONS
 WERE DONE WITHOUT INCLUDING THE 2ND
 FLOOR. REVISE AS REQUIRED.
  
 11- OWES $988.89 FOR UPDATED VALUATION
 AND RADON FEES.
  
 12- PROVIDE STAIRS COMPLETE STAIR
 FRAMING DETAILS AND SPECS.
 **PROVIDE HANDRAIL SPECS. SEE SECTION
 1007.5 FBC 2001.
 ***SPECIFY FIREBLOCKING. SEE SEC.
 2305.1.4 FBC 2001
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-04-17 Cont ID  
Sent By dpalmer Date 2006-04-17 Time 08:38 Rev Time 0.00
Received By dpalmer Date 2006-04-17 Time 08:04 Sent To PC
Notes
2006-04-17 00:00:00RISER SHOWS 200A PANEL FOR PANEL "A",
 WITH 150A FEED. THIS IS OK, HOWEVER DOES
 NOT CORRELATE WITH PANELS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-10 Cont ID  
Sent By dpalmer Date 2006-03-10 Time 07:22 Rev Time 0.00
Received By dpalmer Date 2006-03-10 Time 07:06 Sent To PC
Notes
2006-03-10 00:00:00RISER SHOWS 2/0'S FOR 150A PANELS, THIS
 IS OK.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-28 Cont ID  
Sent By dpalmer Date 2005-07-28 Time 20:28 Rev Time 0.30
Received By dpalmer Date 2005-07-28 Time 20:17 Sent To M
Notes
2005-07-28 00:00:00REDLINED GROUNDING ELECTRODE CONDUCTOR
 TO BE A MIN OF 1/0. 250.66,310.15B6
  
 ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-22 Cont ID  
Sent By dpalmer Date 2005-06-22 Time 16:42 Rev Time 0.30
Received By dpalmer Date 2005-06-22 Time 16:31 Sent To M
Notes
2005-06-22 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE NEW RISER DIAGRAM NOW
 SUBMITTED. PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR TO POOL SUB PANEL,
 250.110,250.24,680.6
  
 2)NOTE: PLEASE SEE ELECTRICAL SHEET HAS
 NOW COME BACK WITH A DIFFERENT SIGNATURE
 FOR ARCH OF RECORD THAN SIGNATURE ON
 FILE FOR ARCH AND DIFERENT FROM
 SIGNATURE ON OTHER SHEETS. THIS
 SIGNATURE AS SHOWN IS NOT ACCEPTABLE TO
 THIS OFFICE. THIS HAS BEEN NOTED ON
 NUMEROUS PREVIOUS REVIEWS OF OTHER
 PROJECTS. PLEASE SEE FS 481.221 WHICH
 REQUIRES THE ARCH TO SIGN,SEAL AND DATE
 PLANS. THIS MAY ONLY BE DONE BY THE
 ARCHITECT HOLDING LICENSE AND SAID SEAL.
 ONE COPY OFELECTRICAL PLANS ARE BEING
 RETAINED AND SHALL BE PLACED WITH PLANS
 ALREADY IN RETENTION. THIS WAS SUBMITTED
 TO THE BLDG OFFICAL AND ALL PLANS SHALL
 BE TURNED OVER TO THE STATE LEGAL
 COUNSEL FOR STATE BOARD OF ARCHITECT'S
 FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-31 Cont ID  
Sent By dpalmer Date 2005-03-31 Time 15:41 Rev Time 0.50
Received By dpalmer Date 2005-03-31 Time 15:41 Sent To M
Notes
2005-03-31 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE PLANS INDICATE A
 DRYER, HOWEVER PANEL SCHEDULE AND LOAD
 CALCULATIONS DO NOT SHOW.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES DISHWASHER ON A 2P20A BRKR FOR
 OCP.?
 IS THIS PART OF DISPOSAL/DISHWASHER?
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING TO CONDENSING UNITS.
 PLEASE ALSO SEE 3-#6'S TO COND UNIT. IS
 THIS 2-#6'S AND ONE #10?
 PLEASE SEE CONDUIT FILL FOR SCHEDULE 80
 PVC. PLEASE SEE EUIPMENT GROUNDING PER
 250.122
  
 4)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 5)NOTE: PLEASE SEE NUMEROUS BRANCH
 CIRCUITS WITH 15A OCP ON #12 AWG. THIS
 IS OK AND DOES MEET CODE, HOWEVER PLEASE
 VERIFY. IF SHOWN, THEN THIS MUST BE
 DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-15 Cont ID  
Sent By adarroug Date 2006-04-15 Time 15:09 Rev Time 0.00
Received By adarroug Date 2006-04-15 Time 15:09 Sent To E
Notes
2006-04-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 15:53 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 15:53 Sent To E
Notes
2006-03-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-22 Cont ID  
Sent By adarroug Date 2005-09-22 Time 16:09 Rev Time 0.00
Received By adarroug Date 2005-09-22 Time 16:09 Sent To B
Notes
2005-09-22 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 18:24 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 18:24 Sent To E
Notes
2005-07-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 14:25 Rev Time 0.00
Received By shill Date 2005-06-20 Time 14:25 Sent To E
Notes
2005-06-20 00:00:00TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 13:37 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 13:37 Sent To E
Notes
2005-03-31 00:00:00TO "SFR""E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-26 Cont ID  
Sent By jgomez Date 2005-04-26 Time 15:59 Rev Time 0.00
Received By jgomez Date 2005-03-25 Time 09:00 Sent To PC
Notes
2005-03-25 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-09-19 Cont ID  
Sent By pkrauss Date 2005-09-19 Time 15:30 Rev Time 0.30
Received By pkrauss Date 2005-09-19 Time 15:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2005-08-02 Cont ID  
Sent By rregueir Date 2005-08-02 Time 19:25 Rev Time 0.00
Received By rregueir Date 2005-08-02 Time 19:25 Sent To B
Notes
2005-08-02 00:00:00DENIED.
  
 NO PLANS OR MANUAL J PROVIDED.
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-06-28 Cont ID  
Sent By pkrauss Date 2005-06-28 Time 06:45 Rev Time 0.25
Received By pkrauss Date 2005-06-28 Time 06:45 Sent To B
Notes
2005-06-28 00:00:00DENIED:
 PLEASE PROVIDE MANUAL J CALCULATIONS AS
 REQUIRED PER 2001 FBC(M) CHAPTER 6.
  
 PROVIDE EQUIPMENT SCHEDULE.
  
 NO MECHANICAL PLAN PROVIDED FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-04-04 Cont ID  
Sent By prafter Date 2005-04-04 Time 10:40 Rev Time 0.45
Received By prafter Date 2005-04-04 Time 10:40 Sent To P
Notes
2005-04-04 00:00:00MECH. PLAN REVIEW.
  
 NO A/C PLANS OR EQUIPMENT INFORMATION.
  
 PAT RAFTER 805/6728 OR 805/6719 PATTY
 KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-28 Cont ID  
Sent By dpalmer Date 2005-06-28 Time 06:49 Rev Time 0.00
Received By pkrauss Date 2005-06-28 Time 06:49 Sent To  
Notes
2005-06-28 00:00:00SEE REVIEW BY PAT RAFTER DATED 4-4-05

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-04-07 Cont ID  
Sent By jleech Date 2005-04-07 Time 17:28 Rev Time 0.50
Received By jleech Date 2005-04-07 Time 17:28 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-30 Cont ID  
Sent By mmclean Date 2005-03-30 Time 15:17 Rev Time 0.00
Received By mmclean Date 2005-03-30 Time 15:17 Sent To I
Notes
***NONE***