Plan Review Details - Permit 05031435
Plan Review Stops For Permit 05031435
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-28 Cont ID  
Sent By alange Date 2006-08-28 Time 08:50 Rev Time 0.00
Received By alange Date 2006-08-28 Time 08:50 Sent To  
Notes
2006-08-28 00:00:00ROOF TILE REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-17 Cont ID  
Sent By jwitmer Date 2005-06-17 Time 12:00 Rev Time 2.22
Received By jwitmer Date 2005-06-17 Time 12:00 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-02 Cont ID  
Sent By jgomez Date 2005-05-02 Time 16:55 Rev Time 2.50
Received By jgomez Date 2005-05-02 Time 16:55 Sent To PC
Notes
2005-05-02 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 4- WEST ELEVATION DON'T MATCH FLOOR
 PLAN. SEE CORRIDOR BETWEEN FOYER AND
 BEDROOM #3. REVISE AS REQUIRED.
  
 5- PROVIDE COMPLETE SPECS AND DETAILS
 FOR STRUCTURAL COLUMNS IN FOYER AREA.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 6- ENTRY DOORS (101 AND 112) TO PROVIDE
 32" MIN. CLEAR OPENING PER LEAF AS REQ'D
 BY TABLE 1004 FBC 2001. REVISE AS REQ'D.
  
 7- NEED AT LEAST ONE BEDROOM WITH
 BATHROOM DOOR THAT PROVIDES 29" MINIMUM
 CLEAR OPENING AS REQ'D BY SEC. 11-11 FBC
  
 8- PROVIDE COMPLETE DETAILS AND SPECS
 FOR WOOD TRELLIS AT KITCHEN DECK. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 9- PROVIDE A/C CHASE DETAIL ON BEAM B-1.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 10- CONNECTORS MTS18 AND MSTA21 DON'T
 HAVE LATERAL LOADS. HOW ARE TRUSS
 LATERAL LOADS RESISTED? SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 11- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR:
 A) ENTRY DOORS.
 B) SINGLE HUNG WINDOWS.
 C) SPECIFY WHERE ARE THE THERMA-TRU
 DOORS GOING TO BE INSTALLED.
 D) KITCHEN DOOR.
 E) FLAT ROOF SYSTEM.
 F) ROOF TILE: NEED SBCCI REPORT THAT WAS
 SUBMITTED FOR FLORIDA APPROVAL.
 G) FRENCH DOORS. DADE COUNTY NOA ALONE
 IS NOT FLORIDA PRODUCT APPROVAL.
  
 12- PROVIDE COMPLETEFLUELESS FIREPLACE
 LISTING AND SPECIFICATIONS AS REQUIRED
 BY SEC. 2806 FBC 2001.
  
 13- ENERGY CALCULATIONS: PROVIDE
 COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING ADDRESS ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-06-16 Cont ID  
Sent By dpalmer Date 2006-06-16 Time 21:17 Rev Time 0.00
Received By dpalmer Date 2006-06-16 Time 21:01 Sent To PC
Notes
2006-06-16 00:00:00**** UNSAT ***
  
  
 1) NOTE: PLEASE SEE PLANS CAN BE
 REDLINED FOR MISSING LT FIXTURE REQUIRED
 FOR EGRESS. 210.70 LS 101 7.8.1.3
  
 2) NOTE: CALLED SUSI FROM STERLING COMM
 TO BRING IN 2ND SET OF SIGNED, AND
 SEALED PLANS.
  
 3) NOTE: PANEL SCHEDULE SHALL BE REVISED
 BEFORE FINAL AND SUBMITTED FOR REVIEW TO
 INDICATE ALL CIRCUITS AND ROOMS/AREAS IN
 WHICH THEY FEED. 408.4
  
  
 THESE NEED TO BE VERIFIED FOR THE SAME
 AS REV SUBMITTED AND REDLINED FOR NOTE
 #1 AND #3
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-09 Cont ID  
Sent By dpalmer Date 2006-06-09 Time 08:17 Rev Time 0.00
Received By dpalmer Date 2006-06-09 Time 07:30 Sent To M
Notes
2006-06-09 00:00:00****** UNSAT ******
  
  
 ** PLEASE SEE THE FOLLOWING COMMENTS AS
 THE RISER AND SERVICE DIAGRAM HAS
 COMPLETELY CHANGED FROM THE ORIGINAL
 PLANS SUBMITTED AND REVIEW.
  
  
 1) NOTE: PLEASE CORRELATE IDENTIFICATION
 OF PANELS AND CORRELATE WITH RISER.
 PLEASE SEE RISER SHOWS PANELS, A1, A2,
 B, C, AND POOL PANEL, YET THE TWO 200A
 PANEL SCHEDULES SUBMITTED ARE SHOWN AS
 "A" AND "B"?
 215.5
  
 2) NOTE: PLEASE SEE PANEL "A" INDICATES
 "FEED THRU LUGS" TO PANEL "B", YET RISER
 SHOWS PANEL "B" COMING FROM THE
 METER/MAIN PANEL.?
 215.5
  
 3) NOTE: PLEASE SEE NO PANEL SCHEDULE
 FOR THE METER/MAIN 8 CIRCUIT SECTION WAS
 SUBMITTED, YET THERE ARE ITEMS BEING FED
 FROM THIS PANEL?
 215.5,408
  
 4) NOTE: PLEASE SEE SERVICE IS NOW
 400A'S AND THE SEC'S ARE STILL BEING
 SHOWN FOR THE ORIGINAL 200A SERVICE??
 PLEASE INDICATE OF THE SEC'S ARE
 INSTALLED BY FPL, OR IF THESE ARE SEC'S
 INSTALLED TO A HAND HOLE WHICH WOULD
 FALL UNDER 310.16,240.4,310.15B6
 IN THIS CASE, PLEASE SEE THE FOLLOWING
 NOTE.
 215.5
  
 5) NOTE: PLEASE SEE THE GROUNDING
 ELECTRODE CONDUCTOR WAS NOT INCREASED
 FOR THE 400A SERVICE.
 PLEASE SEE 310.15B6, 250.66
 MIN SIZE SHALL BE 1/0.
  
 6) NOTE: PLEASE CORRELATE PANELS WITH
 RISER AS RISER SHOWS THESE AS 32CIR AND
 PANELS ARE SHOWN AS 42 CIRCUIT??
 215.5
  
 7) NOTE: PLEASE SEE SD IN BEDRMS WITH
 SLOPED CEILINGS SHALL MEET NFPA-72 BEING
 INSTALLED WITHIN 3' OF THE PEAK ON A
 SLOPED CEILING.
 CHAPTER 8-1 INNFPA-72 99 OR CHAPTER 11
 IN NFPA-72 2002.
 PLEASE SEE LOCATIONS ON PLANS WHICH NEED
 TO BE ADJUSTED.
  
 8) NOTE: PLEASE SEE KITCHEN COUNTER
 SPACE MISSING GFI RECEPTS AS REQUIRED
 PER 210.52C1-5, 210.8A6
  
 9) NOTE: PLEASE SEE RISER SHOWS A POOL
 PANEL , YET PLANS DO NOT??
 PLEASE SHOW LOCATION.
 215.5
  
 10) NOTE: PLEASE SEE REAR EGRESS WHERE A
 MIN OF ONE LT FIXTURE OF SOME TYPE WILL
 BE REQUIRED FOR EGRESS.
 210.70, NFPA-101 7.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-01 Cont ID  
Sent By btrobaug Date 2005-06-01 Time 09:56 Rev Time 0.75
Received By btrobaug Date 2005-05-31 Time 17:41 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-01 Cont ID  
Sent By dpalmer Date 2005-04-01 Time 07:10 Rev Time 1.00
Received By dpalmer Date 2005-03-31 Time 16:47 Sent To M
Notes
2005-04-01 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE CORRELATE AHU'S ON
 ELECTRICAL PLANS WITH MECH PLANS.
 PLEASE SEE TWO #3 A/C SYSTEMS. PLEASE
 SEE THESE ARE NOT ON MECH PLANS.
  
 2)NOTE: PLEASE SEE WHIRLPOOL TUB IS
 SHOWN ON PANEL SCHEDULE BUT NOT SHOWN ON
 PLANS.
 PLEASE ALSO SHOW GFI PROTECTION PER
 680.71.
 PLEASE ALSO SEE THIS IS SHOWN AS 2-POLE
 20A. ONLY A NOTE:
  
 3)NOTE: PLEASE SEE MEANS OF EGRESS
 LIGHTING CONTROL AT BOTTOM OF STAIRS AT
 FOYER LOCATION. SWITCH IS SHOWN AS
 SINGLE POLE, IS THIS THE 3-WAY FOR
 STAIRWAY? PLEASE ALSO SEE MEANS OF
 EGRESS CONTROL REQUIRED FOR OUTER
 STAIR/PORCH AREA BY BEDRM #4. 210.70, LS
 101 5-8.
  
 4)NOTE: PLEASE SEE MISSING RECEPTS
 REQUIRED PER 210.52 ALONG WALL/RAIL
 AREAS IN STUDY AND MEZZ. PLEASE SEE RAIL
 AREAS ARE CONSIDERED WALL SPACE.
  
 5)NOTE: PLEASE SEE SD FOR INSIDE MASTER
 BEDRM MUST BE WITHIN 3' OF PEAK OF
 CEILING. IF CEILING HAS A LESSTHAN 3'
 PEAK. SD IS STILL REQUIRED TO BE WITHIN
 BEDRM.
 NFPA-72 8-1.4, ETC.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-08-23 Cont ID  
Sent By adarroug Date 2006-08-23 Time 16:43 Rev Time 0.00
Received By adarroug Date 2006-08-23 Time 16:43 Sent To B
Notes
2006-08-23 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 13:35 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 13:35 Sent To M
Notes
2006-06-29 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-16 Cont ID  
Sent By adarroug Date 2006-06-16 Time 11:12 Rev Time 0.00
Received By adarroug Date 2006-06-16 Time 11:12 Sent To E
Notes
2006-06-16 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-06 Cont ID  
Sent By adarroug Date 2006-06-06 Time 10:31 Rev Time 0.00
Received By adarroug Date 2006-06-06 Time 10:31 Sent To E
Notes
2006-06-06 00:00:00TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-13 Cont ID  
Sent By adarroug Date 2005-07-13 Time 16:44 Rev Time 0.00
Received By adarroug Date 2005-07-13 Time 16:44 Sent To Z
Notes
2005-07-13 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 17:59 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 17:59 Sent To E
Notes
2005-05-24 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 13:38 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 13:38 Sent To E
Notes
2005-03-31 00:00:00TO "SFR""E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-25 Cont ID  
Sent By adarroug Date 2005-05-02 Time 08:17 Rev Time 0.00
Received By adarroug Date 2005-03-25 Time 08:17 Sent To Z
Notes
2005-03-25 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-06-29 Cont ID  
Sent By tgordon Date 2006-06-29 Time 15:55 Rev Time 0.25
Received By tgordon Date 2006-06-29 Time 15:55 Sent To  
Notes
2006-06-29 00:00:00REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-06-12 Cont ID  
Sent By hmoser Date 2006-06-12 Time 14:05 Rev Time 0.00
Received By hmoser Date 2006-06-12 Time 14:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-15 Cont ID  
Sent By pkrauss Date 2005-06-15 Time 07:10 Rev Time 0.40
Received By pkrauss Date 2005-06-15 Time 07:00 Sent To B
Notes
2005-06-15 00:00:00PROVISO:
 PLAN INDICATES GAS DRYER.PLEASE SUBMIT
 CALCULATIONS FOR COMBUSTION AIR PRIOR TO
 ROUGH INSPECTION.
  
 FLUELESS FIRE PLACE LOCATED IN THE
 LOGGIA AREA - CLEARANCE FROM CEILING AND
 SIDES SHALL COMPLY WITH THE
 MANUFACTURER'S SUBMITTAL/INSTALLATION
 INSTRUCTIONS ILLUSTRATED ON PAGE 7 & 8.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-05 Cont ID  
Sent By prafter Date 2005-04-05 Time 07:27 Rev Time 1.00
Received By prafter Date 2005-04-05 Time 07:27 Sent To P
Notes
2005-04-05 00:00:00MECH. PLAN REVIEW.
  
 1. PLEASE CORRECT FL. ENERGY
 CALCULACTIONS TO REFLECT WHAT ON PLANS.
 NOTE: (A) (B) (C) NATURAL GAS OR ELECT.
 HEATING?
 2. PLEASE SUPPLY PRODUCT APPROVEL
 INFORMATION ON FLUE-LESS FIRE
 PLACE.IF GAS, CONBUSTION AIR IS
 REQUIRED.
 3. GAS HOT WATER HEATER NOT REFLECTORED
 ON ENERGY CALCULATIONS.
 PAT RAFTER 8056728 OR 8056719 PATTY
 KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-04-07 Cont ID  
Sent By btrobaug Date 2005-06-01 Time 09:56 Rev Time 0.33
Received By jleech Date 2005-04-07 Time 17:17 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status   Date 2005-07-21 Cont ID  
Sent By mmclean Date 2005-07-21 Time 15:45 Rev Time 0.00
Received By mmclean Date 2005-07-21 Time 15:45 Sent To PC
Notes
2005-07-21 00:00:00APPROVING PAVERS FOR 20FT ACCESS
 EASEMENT (REVISON). GIVEN TO WANDA.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-30 Cont ID  
Sent By mmclean Date 2005-03-30 Time 15:10 Rev Time 0.00
Received By mmclean Date 2005-03-30 Time 15:10 Sent To I
Notes
2005-03-30 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE
 NOTE: MUST PULL SEPERATE PERMIT FOR
 WALL/FENCE/GATE WITH CITY OF WEST PALM
 BEACH UTILITY DEPT EASMENT APPROVAL.