| 2005-04-26 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- SHEET A-2: A) FOUNDATION NOTE #1. |
| | NEED 6 MIL, NOT 4 MIL VAPOR BARRIER. |
| | SEC. 1909.2 FBC 2001. |
| | |
| | B) REVISE FOUNDATION NOTE #2. SEE |
| | CHAPTER 19 FBC 2001 FOR PROPER ACI |
| | REFERENCE. |
| | |
| | C) THERE IS SOME OVERLAPPING INFORMATION |
| | THAT DOESN'T ALLOW NOTES TO BE LEGIBLE. |
| | REVISE AS REQUIRED. |
| | |
| | 2- SHEET A-3: A) DESIGN PARAMETERS: |
| | WHERE IS THE BASIC VELOCITY PRESSURE |
| | TAKEN FROM? IT IS NOT SHOWN IN CHAPTER |
| | 16 FBC 2001. |
| | |
| | B) REVISE HANDRAIL HEIGHT. SEE SECTION |
| | 1007.5.1 FBC 2001 (EXEMPTION #3). |
| | |
| | C) PROVIDE ATTIC ACCESS AT MASTER SUITE |
| | WING AND AT BEDROOM #2 WING. AS REQUIRED |
| | BY SEC. 2309.6 FBC 2001. |
| | |
| | 3- SHEET A-4: A) REVISE HANDRAIL HEIGHT. |
| | SEE SEC. 1007.5.1 (EXEMPTION #3) FBC. |
| | |
| | B) THERE IS SOME INFORMATION THAT IS |
| | OVERLAPPING. REVISE AS REQUIRED TO MAKE |
| | IT LEGIBLE. |
| | |
| | 4- SHEET A-10: PROVIDE SMOKE DETECTOR ON |
| | FIRST FLOOR IN CLOSE PROXIMITY TO THE |
| | STAIRWAY LEADING TO THE 2ND FLOOR. SMOKE |
| | DETECTOR IS SHOWN ABOVE THE STAIRS. THIS |
| | IS A DOUBLE HEIGHT CEILING AND THERE IS |
| | ALREADY A SMOKE DETECTOR SHOWN ON SHEET |
| | A-11. REVISE AS REQUIRED TO COMPLY WITH |
| | SEC. 905.2.2 FBC 2001 |
| | |
| | 5- SHEET A-5: FRONT ELEVATION CALLS FOR |
| | FLAT CEMENT TILE. PRODUCT APPROVAL |
| | SUBMITTED IS FOR "S" TILE. REVISE. |
| | |
| | 6- SHEET A-7: A) REVISE ROOF SHEATHING |
| | NAIL TYPE REQUIRED FOR ROOF WITH 25' |
| | MEAN ROOF HEIGHT ON ZONE 3 OF ROOF. SEE |
| | TABLE 2306.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | B) REVISE/UPDATE TRUSS ANCHOR SCHEDULE. |
| | SEE LATEST CATALOGUE. PROVIDE COMPLETE |
| | ENGINEERING CALCULATIONS FOR NAIL TYPE |
| | AND NUMBER THAT DIFFERS FROM THOSE |
| | TESTED AND PUBLISHED BY MANUFACTURER. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 7- SHEET A-8: A) REVISE ROOF SHEATHING |
| | NAIL TYPE. SEE TABLE 2306.1 CITY |
| | AMENDMENTS TO FBC 2001 FOR ZONE 3 ON |
| | ROOF OVER 25'-0" MEAN ROOF HEIGHT. |
| | |
| | B) REVISE CONNECTOR G SPECIFIED FOR |
| | MASONRY WALL ON LEFT HAND SIDE. NEED |
| | WOOD TO MASONRY CONNECTOR. |
| | |
| | C) DETAIL 2/A-13 SHOWN ON RIGHT HAND |
| | SIDE DOESN'T APPLY. REVISE AS REQUIRED. |
| | |
| | 8- STAIR SECTION ON SHEET A-13 DOESN'T |
| | MATCH STAIRS SHOWN ON PLANS. REVISE AS |
| | REQUIRED. AND PROVIDE COMPLETE |
| | INFORMATION INCLUDING FIREBLOCKING AS |
| | REQUIRED BY SEC. 2305.2 FBC 2001. |
| | |
| | 9- GARAGE DOOR: PROVIDE PRODUCT APPROVAL |
| | FOR 8'-0" WIDE GARAGE DOOR THAT MEETS |
| | THE DESIGN PRESSURES SHOWN ON PLANS. |
| | |
| | 10-SPECIFY ROOF TILE FASTENING. IT'S THE |
| | DESIGNER OF RECORD RESPONSIBILITY NOT HE |
| | CONTRACTOR.. SEE SEC. 104.2.1.1 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 11- PROVIDE COMPLETE DETAIL/SPECS FOR |
| | CEILING INSTALLATION AT ENTRY AND REAR |
| | PORCHES. SEE ASTM C926 AND ASTM C1063. |
| | SPECIFY ALL FASTENERS AND SPACING. |
| | |
| | 12- OWES $934.91 FOR UPDATED VALUATION |
| | AND RADON FEES. |
| | |
| | 13- SPECIFY MULLION SIZE AND ANCHORS TO |
| | BE USED BETWEEN 12'-0" WIDE SLIDING |
| | GLASS DOORS AND TRANSOM ABOVE TO VERIFY |
| | STRUCTURAL ADEQUACY OF MULLION SELECTED. |
| | |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 14- PROVIDE PRODUCT APPROVAL FOR SINGLE |
| | FRENCH DOORS AS SHOWN ON PLANS. |
| | |
| | 15- PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | DOORS WITH IMPACT GLAZING AS SHOWN ON |
| | PLAN AND ELEVATIONS. |
| | |
| | PLEASE DON'T STAPLE PRODUCT APPROVALS TO |
| | PLANS AND IF YOU HAVE ANY QUESTIONS, |
| | PLEASE CALL JULIO GOMEZ AT (561)805-6712 |