Plan Review Details - Permit 05031272
Plan Review Stops For Permit 05031272
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-25 Cont ID  
Sent By jgomez Date 2005-05-25 Time 07:48 Rev Time 1.00
Received By jgomez Date 2005-05-25 Time 07:48 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-25 Cont ID  
Sent By jgomez Date 2005-04-25 Time 17:46 Rev Time 2.00
Received By jgomez Date 2005-04-25 Time 17:46 Sent To PC
Notes
2005-04-25 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- NEED ENERGY CALCULATIONS.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- IMPACT FEES. NEED DRAWINGS TO BE
 STAMPED BY PALM BEACH COUNTY.
  
 4- KEYED DETAILS ON ROOF FRAMING PLANS
 DON'T MATCH DETAILS ON SHEET A6.DETAIL
 G/6 AND C1-C2/6 DON'T MATCH. REVISE AS
 REQUIRED.
  
 5- OWES $1840.76 BALANCE OF PERMIT FEES
 AND UPDATED VALUATION AND RADON FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-05-02 Cont ID  
Sent By dpalmer Date 2006-05-02 Time 18:58 Rev Time 0.00
Received By dpalmer Date 2006-05-02 Time 18:51 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-12-22 Cont ID  
Sent By dpalmer Date 2005-12-22 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2005-12-22 Time 11:48 Sent To  
Notes
2005-12-22 00:00:00CONDUITS ONLY FOR FUTURE GEN.
 LOCATION FOR CONDUITS NOT REVIEWED FOR
 CODE COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-22 Cont ID  
Sent By dpalmer Date 2005-11-22 Time 09:38 Rev Time 0.30
Received By dpalmer Date 2005-11-22 Time 08:21 Sent To  
Notes
2005-11-22 00:00:00REDLINED,
  
  
 SD IN MASTER BEDRM PER NFPA-72 11.8.3
  
 20A OCP SHOWN ON #14 AWG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-05-03 Time 17:44 Rev Time 0.30
Received By dpalmer Date 2005-05-03 Time 17:44 Sent To P
Notes
2005-05-03 00:00:00********** PROVISO/REVISION **********
  
 PLEASE SEE NOTE'S #2 AND #5 FROM
 PREVIOUS REVIEW.
  
 1)NOTE: NOTE #2 , PLEASE SEE ORIGINAL
 PLANS RISER SHOWED 2-#6'S, 1-#8 AND
 1-#10 FOR POOL SUB PANEL AND PANEL
 SCHEDULE "B" SHOWED 3-#6'S?
 PLEASE SEE NOW AN ADDITIONAL PHASE/HOT
 CONDUCTOR HAS BEEN ADDED TO FEED
 PANEL"C". PLEASE SEE RISER NOW SHOWS
 3-HOTS, 1-NEUTRAL AND 1-EQUIP GRND.???
  
 PLEASE ADJUST TO ACTUAL INSTALLATION.
  
 2)NOTE: NOTE #5, ORIG PLANS SHOWWS 4.5KW
 FOR COND UNITS, WITH 40A OCP AND #10
 AWG. PLEASE SEE 4.5KW @240= 18.75A'S.
 IT WAS REQUESTED TO VERIFY OCP FOR LOAD
 AND AWG SHOWN, HOWEVER, 3-#6'S WERE
 ADDED TO PANEL SCHEDULES INSTEAD.???
  
 PLEASE ADJUST TO ACTUAL INSTALLATION.
  
  
  
 ***PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT WITH ANY OTHER POSSIBLE REVISIONS
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, ONCE AGAIN,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-28 Cont ID  
Sent By dpalmer Date 2005-03-28 Time 16:39 Rev Time 0.50
Received By dpalmer Date 2005-03-28 Time 16:39 Sent To M
Notes
2005-03-28 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE CORRELATE RISER WITH
 PLANS. PLANS INDICATE TWO POOL PANELS?
 ONE AT SERVICE LOCATION AND ONE AT POOL
 EQUIPMENT LOCATION. (MISPRINT).
  
 2)NOTE: PLEASE CORRELATE WIRING FOR
 SUB-PANEL "C", SHOWS 3-#6'S ON PANEL
 SCHEDULE"B" , YET RISER SHOWS 2-#6'S AND
 #8?
  
 3)NOTE: PLEASE SEE MISSING RECETP PER
 210.52 IN BEDRM #3.
  
 4)NOTE: PLEASE SEE COOKTOP SHOWS 6KW
 LOAD ON 1-POLE 20A BRKR.
 215.5,310.16,240.4 TEC.
  
 5)NOTE: PLEASE VERIFY LOAD/OCP AND AWG
 FOR BOTH A/C CU'S.
 4.5KW ON 40A OCP AND #10 AWG.
 240.4,310.16
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 08:45 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 08:45 Sent To E
Notes
2006-05-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-18 Cont ID  
Sent By adarroug Date 2005-11-18 Time 14:06 Rev Time 0.00
Received By adarroug Date 2005-11-18 Time 14:06 Sent To E
Notes
2005-11-18 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 18:40 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 18:40 Sent To P
Notes
2005-09-29 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 14:06 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 14:06 Sent To E
Notes
2005-05-03 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-28 Cont ID  
Sent By adarroug Date 2005-03-28 Time 14:11 Rev Time 0.00
Received By adarroug Date 2005-03-28 Time 14:11 Sent To E
Notes
2005-03-28 00:00:00TO "SFR""E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-25 Cont ID  
Sent By jgomez Date 2005-04-25 Time 18:02 Rev Time 0.00
Received By jgomez Date 2005-03-23 Time 15:19 Sent To PC
Notes
2005-03-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-19 Cont ID  
Sent By prafter Date 2005-05-19 Time 11:49 Rev Time 0.50
Received By prafter Date 2005-05-19 Time 11:49 Sent To B
Notes
2005-05-19 00:00:00MECH. RESUB:
  
 A/C PLANS AND EQUIP. INFO. OK.
 ENERGY CALK,SOK.
  
 PR 5/19/05.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-04 Cont ID  
Sent By prafter Date 2005-04-04 Time 07:46 Rev Time 0.45
Received By prafter Date 2005-04-04 Time 07:46 Sent To P
Notes
2005-04-04 00:00:00MMECH. PLAN REVIEW.
  
 1. NO A/C PLANS OR EQUIPMENT
 INFORMATION.
 2. NO ENERGY CALCULATION FOR BUILDING.
  
 PAT RAFTER 805/6728 OR 805/6719 PATTY
 KRAUSS.
 PLEASE CALL IF THEAR ANY QUISTION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-05-14 Cont ID  
Sent By jleech Date 2005-05-14 Time 12:45 Rev Time 0.25
Received By jleech Date 2005-05-14 Time 12:45 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-04-06 Cont ID  
Sent By jleech Date 2005-04-06 Time 17:58 Rev Time 0.33
Received By jleech Date 2005-04-06 Time 17:58 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-25 Cont ID  
Sent By mmclean Date 2005-03-25 Time 15:25 Rev Time 0.00
Received By mmclean Date 2005-03-25 Time 15:25 Sent To I
Notes
2005-03-25 00:00:00NOTE: 2ND REF MUST BE A U/C REF.
 MUST PULL SEPERATE PERMIT FOR
 POOL/DECK/SPA/SCREEN ENCLOSURE.