| 2005-04-22 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PAY IMPACT FEES. BRING BACK STAMPED |
| | DRAWINGS AND PAID RECEIPT. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 3- SHEET A1: A) ATTIC ABOVE GARAGE USED |
| | FOR STORAGE NEEDS TO BE DESIGNED FOR |
| | 30PSF LIVE LOAD AT BOTTOM CHORD OF |
| | TRUSS. REMAINDER OF ATTIC IF IS NOT USED |
| | FOR STORAGE NEEDS TO BE DESIGNED FOR |
| | 10PSF AS REQUIRED BY TABLE 1604.1 FBC |
| | 2001. REVISE NOTE ON GARAGE AREA AND |
| | CLEARLY INDICATE STORAGE OR NON STORAGE |
| | AREAS. SEE PLANS FOR COMMENTS. |
| | |
| | B) SPECIFY SAFETY GLASS AT FAMILY ROOM |
| | AND MASTER BEDROOM WINDOWS AS REQUIRED |
| | BY SEC. 2405.2.1(3) FBC 2001. SEE PLANS. |
| | |
| | C) SPECIFY SIZE OF ATTIC ACCESS IN |
| | MASTER BEDROOM CLOSET. SEC. 2309.6 FBC. |
| | |
| | D) REVISE ELEVATIONS FOR BEAMS AT ENTRY |
| | DOORS. SIZE OF DOOR IS TALLER THAN |
| | HEIGHT SPECIFIED FOR BEAM HEIGHT. |
| | |
| | E) SHOW ON PLAN PRIVACY WALL IN FRONT OF |
| | BATHROOM AS SHOWN ON FOUNDATION PLAN. |
| | |
| | 4- SHEET A2: A)THERE ARE NOT FOOTINGS |
| | FOR PORTICO COLUMNS AND COLUMNS IN FRONT |
| | OF GARAGE. PROVIDE DETAILS SPECS AS |
| | REQ'D. SEC. 104.2.1.2 CITY AMENDMENTS TO |
| | FBC 2001. |
| | |
| | B) CLARIFY WHY FOOTINGS FOR CONCRETE |
| | BLOCK PIERS AT FRONT PRIVACY WALLARE |
| | BIGGER THAN THE FOOTINGS SPECIFIED FOR |
| | REAR PORCH AND INTERIOR STEEL COLUMN. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 5- SHEET A3: A) CLEARLY INDICATE ON ROOF |
| | FRAMING PLAN ANCHORS TO BE USED. SPECIFY |
| | ANCHORS AT ALL CONNECTIONS IN ROOF |
| | FRAMING PLAN. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | B) CONNECTOR SPECIFIED AT FRONT OF |
| | PORTICO IS FOR MASONRY APPLICATION. |
| | NEEDS WOOD TO WOOD CONNECTOR. REVISE AS |
| | REQ'D. |
| | |
| | C) REVISE ROOF LOADS CHART. NEED TO |
| | SPECIFY 30PSF AND 10PSF ATTIC LIVE LOAD |
| | IN THE ATTIC (BCLL) AS REQUIRED BY TABLE |
| | 1604.1 FBC 2001. |
| | |
| | 6- ELEVATIONS ON SHEET A6 DON'T MATCH |
| | FLOOR PLAN. RIGHT SIDE ELEVATION NEED TO |
| | SHOW POCKET FOR SLIDING GLASS DOORS AND |
| | MASTER BATHROOM GLASS BLOCK. REAR |
| | ELEVATION DON'T SHOW SAME TYPE AND |
| | NUMBER OF WINDOWS AS SPECIFIED ON PLANS. |
| | |
| | |
| | 7- SHEET A7: REVISE CONNECTORS SPECIFIED |
| | ON WOOD BEARING WALL DETAIL. SEMCO IS |
| | OUT OF BUSINESS. |
| | |
| | 8- PROVIDE FRAMING DETAILS AND SPECS FOR |
| | POCKET WALL AT SLIDING GLASS DOORS IN |
| | FAMILY ROOM. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 9- BBQ SPECS TYPICALLY SAY THAT THEY ARE |
| | DESIGNED FOR OUTDOORS ONLY. PROVIDE BBQ |
| | LISTING AND MANUFACTURER SPECS STATING |
| | THAT BBQ WILL BE OK TO INSTALL IN THE |
| | PORCH.SECTION 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 10- CLEARLY SPECIFY IF USING WINDOWS AND |
| | DOORS WITH IMPACT GLAZING OR SHUTTERS. |
| | BOTH PRODUCT APPROVALS WERE SUBMITTED |
| | AND IS NOT CLEAR WICH GLASS PROTECTION |
| | METHOD IS GOING TO BE INSTALLED. |
| | |
| | 11- IF USING STORM SHUTTERS, THEN |
| | PROVIDE KEY PLAN AND COMPLETE |
| | INSTALLATION SCHEDULE. SEE SAMPLE. SEE |
| | SHUTTERS INSTALLATION SCHEDULE IN |
| | DRAWINGS AND MARK SPECIFIC ANCHOR AND |
| | SPACING TO BE USED. |
| | |
| | 12- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: A) 10'-0" H. ENTRY DOORS. |
| | |
| | B) 18'-0" WIDE GARAGE DOOR. |
| | |
| | C) POCKET SLIDING GLASS DOORS. SEE PLANS |
| | |
| | D) WINDOW MULLIONS. |
| | |
| | E) CASEMENT WINDOWS.\ |
| | |
| | F) ALL TRUSS CONNECTORS SPECIFIED ON |
| | PLANS. |
| | |
| | G) HORIZONTAL SLIDER WINDOWS. |
| | |
| | H) BUTT GLAZING SYSTEM OR WINDOW |
| | ASSEMBLIES AS SHOWN ON MASTER BEDROOM, |
| | LIVING ROOM AND BREAKFAST AREA. |
| | |
| | I) FRENCH DOORS AS SHOWN ON PLANS. |
| | |
| | 13- PROVIDE FRAMING DETAILS AND SPECS |
| | FOR CONSTRUCTION OF WALL ABOVE WINDOW IN |
| | BREAKFAST AREA. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 14- OWES $4247.67 FOR PERMIT FEES AND |
| | RADON FEES. |
| | |
| | 15- ENERGY CALCULATIONS: A) THIS IS A |
| | MODEL HOUSE. NEED ENERGY CALCULATIONS |
| | FOR WORST CASE SCENARIO OR CALCULATIONS |
| | SHALL BE DONE WITH SPECIFIC HOUSE |
| | ORIENTATION IN LOT TO BE BUILT. |
| | |
| | B) OVERHANG LENGHT AND OVERHANG HEIGHT |
| | ARE INCORRECT. SEE PLANS AND ELEVATIONS |
| | AND REVISE ACCORDINGLY. SEE ATTACHED |
| | SKETCH SHOWING HOW OVERHANG LENGTH AND |
| | HEIGHT ARE CALCULATED. |
| | |
| | C) OWNER/AGENT TO SIGN AND DATE FORM. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |