Plan Review Details - Permit 05031171
Plan Review Stops For Permit 05031171
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 17:29 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 17:29 Sent To P
Notes
2005-10-11 00:00:00TO "P" BOX/REV

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-14 Cont ID  
Sent By jleech Date 2005-10-14 Time 11:18 Rev Time 2.50
Received By jleech Date 2005-10-14 Time 11:18 Sent To  
Notes
2005-10-14 00:00:00DENIED;
 1. ENGINEER TO COMPLY WITH FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002
 (2). COPY ATTACHED.
 2.THIS PLAN COVERS NEW WORK. PERMIT
 05031171 IS FOR REPAIRAND REPLACEMENT
 OF FIXTURES. NEW PERMIT APPLICATION IS
 REQUIRED, TO COVER BUILDING, ELECTRIC,
 MECHANICAL AND PLUMBING PERMIT. PLANS TO
 SHOW ALL NEW WORK AS REQUIRED TO INSTALL
 THE JOB TO THE FBC-2004 CODES.
 3.PLUMBING PLAN REVIEW; LIST EQUIPMENT
 TO BE INSTALLED IN COFFEE BAR AND SHOW
 LOCATION.
 ALL INDIRECT WASTE TO DUMP INTO A
  
 FLOOR SINK.
 4.WASTE AND DRAIN DIAGRAM IS NOT TO
 CODE. SEE FBC-2004 PLUMBING TABLE 906.1.
 MAXIMUM DISTANCE OF FIXTURE TO TRAP.
 5.TOILET ROOMS TO COMPLY WITH FBC-2004
 BUILDING CHAPTER 11. SHOW CLEAR FLOOR
 SPACE AND TURNING RADIUS ON PLANS. SHOW
 ROOM DIMENSIONS. SHOW FIG. 29 AND FIG 31
 ON PLANS SHOWING ALL MESSUREMENTS
 REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695