Plan Review Details - Permit 05031130
Plan Review Stops For Permit 05031130
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-01 Cont ID  
Sent By dpalmer Date 2006-06-01 Time 17:44 Rev Time 0.00
Received By dpalmer Date 2006-06-01 Time 16:03 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-02-22 Cont ID  
Sent By dpalmer Date 2006-02-22 Time 17:16 Rev Time 0.00
Received By dpalmer Date 2006-02-22 Time 16:29 Sent To M
Notes
2006-02-22 00:00:00*********** UNSAT 3RD REVIEW *********
  
 ** PLEASE SEE COMMENTS FROM TWO PREVIOUS
 REVIEWS WHICH WERE NOT CORRECTED.
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.023 FOR MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCKS.
 PLEASE SEE MISSING CA/ EB # AS REQUIED.
 PLEASE SEE THIS HAS BEN REQUESTED ON TWO
 PREVIOUS REVIEWS.
  
 2)NOTE: PLEASE CORRELATE SCOPE OF WORK.
 PLEASE SEE PLASN INDICATE A NW SW BOARD,
 YET RISER SHOWS THIS AS EXISTING?
 PLEASE SEE STILL NO LOAD CALCULATIONS,
 PANEL SCHEDULES ETC HAVE BEEN SUBMITTED
 FOR REVIEW.
 215.5,220, 110.9,ETC
 NOTED ON BOTH PREVIOUS REVIEWS.
  
 3)NOTE: PLEASE SEE NOTES ON PLANS WHICH
 ARE CIRCILED WHICH ARE NOT ALL LISTED IN
 THE "NOTES" LEGEND? #8?
 215.5
  
 4)NOTE: PLEASE SEE NO OCPETC IS SHOWN
 FOR NEW FEED TO DISCONNECT TO"CH4MP",
 PLEASE SEE 240.21 , TAPS??
 240.4,310.16ETC.
 PREVIOUS REVIEW, PART OF NOTES FOR RISER
 AND NEW OCP, LOADS ETC.
  
 5)NOTE: PLEASE SEE VALUATION HAS STILL
 NOT BEEN INCREASED FOR SCOPE OF WORK
 SHOWN ON PLANS.
 PLEASE SEE WHAT PLANS SHOW AND
 APPLICATION SHOWS IS TWO DIFFERENT
 THINGS.
 PLEASE KNOW, AN ELECTRICAL PERMIT WILL
 BE REQUIRED FOR ELECTRICAL SCOPE OF
 WORK.
 FBC 104.6.5,104.2.1
  
 6)NOTE: PLEASE SEE AIC RATINGS FOR NEW
 DISCONNECTS ETC NOT SHOWN, ONLY FOR
 PANEL "CH4MP".
 110.9,215.5
  
 7)NOTE: PLEASE SEE A NOTICE WAS GIVEN
 AND ATTACHED TO NOTES AND RE-SUBMITTIAL
 SHEET DATED 7/18/05 PERTAINING TO FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS THREE
 OR MORE TIMES.
 PLEASE SEE A 4X FEE HAS NOW BEEN
 ACCESSED AS REQUIRED PER FS FOR SAID
 REPEAT COMMENTS.
 THIS FEE IS BASED ON 4X THE PLAN REVIEW
 PORTION OF THE BASE PERMIT FEE.(30%)
 THE AMOUNT NOW OWED IS $980.00 AND SHALL
 BE PAID BEFORE RESUBMITTING PLANS FOR
 NEXT REVIEW. PLEASE, KNOW, IF ANY OF THE
 SAME COMMENTS ARE REPEAT COMMENTS ON
 NEXT REVIEW, THE FEE SHALL BE ACCESSED
 ONCE AGAIN AND PLANS SHALL BE FORWARDED
 TO THE STATE.
 PLEASE KNOW, ONE SET OF PLANS ARE BEING
 RETAINED FOR FILE AND POSSIBLE REVIEW BY
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS, AND THE FBPE'S LEGAL CONSEL
 FOR REVIEW AND SAID MISSING REQUIRED
 CERTIFICATE OF AUTHORIZATIONLICENSE
 NUMBER AS REQUIRE BY DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. ONCE AGAIN AS NOTED ON BOTH
 PREVIOUS REVIEWS, IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE TO GO OVER
 COMMENTS OR QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-10 Cont ID  
Sent By dpalmer Date 2006-02-10 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2006-02-10 Time 20:08 Sent To PC
Notes
2006-02-10 00:00:00*******UNSAT ******
  
 1)NOTE: PLEASE SEE THAT PLANS HAVE HAD
 MORE THAN 6 MONTHS OF INACTIVITY. FBC
 ADMINISTRATIVE CODE 104.1.6
 CALLED CONTRACTOR.
  
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-20 Cont ID  
Sent By dpalmer Date 2005-07-20 Time 13:39 Rev Time 0.75
Received By dpalmer Date 2005-07-20 Time 13:39 Sent To  
Notes
2005-07-20 00:00:00********* UNSAT 2ND REVIEW **********
  
 PLEASE SEE SOME OF THE SAME NOTES FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: PLEASE SEE MSSING INFORMATION
 REQUIRED ON TITLE BLOCK PER FAC
 61G15-23.002. PLEASE SEE MISSING LICENSE
 # WHICH IS REQUIRED UNDER FS 471.023.
 THE CERTIFICATE OF AUTHORIZATION #?
  
 2)NOTE: PLEASE CORRELATE PLANS. PLEASE
 SEE SHEET E-1 STILL SHOWS NEW
 SWICTHBOARD EQUIPMENT ETC, HOWEVER PANEL
 SCHEDULES ETC ARE NOT SUBMITTED AND DO
 NOT CORRELATE WITH THIS SCOPE OF WORK?
 PLEASE SEE A CIRCLED NOTE #8 ON ON PLAN,
 BUT IN "NOTE"?
 215.5
  
 2)NOTE: PLEASE SEE NOTE #2 ON PLANS
 MENTIONS TO "MODIFY" CHDP??
 PLEASE VERIFY THIS, AS CHANGING OR
 MODIFICATION OF ANY LISTED PRODUCT OS
 NOT PERMITTED.
 PLEASE SEE 90.7, 110.3.
  
 3)NOTE: PLEASE SEE NO PANEL SCHEDULE
 FOR CHDP.
 PLEASE SEE NO LOAD CALCULATIONS WERE
 SUBMITTED FOR ADDED LOADS TO CHDP OR
 MAIN SW BOARD.
 215.5,220.
  
 4)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND COMMENTS REPEATED FOR
 PLANS REVIEW.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-30 Cont ID  
Sent By pkrauss Date 2005-03-29 Time 16:36 Rev Time 0.33
Received By dpalmer Date 2005-03-30 Time 17:34 Sent To  
Notes
2005-03-30 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE THE FAC 61G15-23.002
 FOR ALL INFORMATION REQUIRED ON PRINTED
 TITLE BLOCK.
  
 2)NOTE: PLEASE CLARIFY SCOPE OF WORK.
 PLEASE SEE APPLICATION MENTIONS ONE NEW
 CHILLER, HOWEVER THERE ARE MANY THINGS
 ON ELECTRICAL PLANS WHICH INDICATE OTHER
 WORK BEING PERFORMED??
 PLEASE SEE PLANS MENTIONS NEW
 SWITCHBOARD, NEW PUMPS?
 PLEASE SEE NOTE ON PLANS MENTIONS NEW
 OCP FOR NEW CHILLERS 1,2,3 ALSO HOWEVER
 NOTHING SHOWN FOR NEW CHILLER #4?
 PLEASE INCLUDE REVISED LOAD CALCULATIONS
 FOR ADDITION OF ALL NEW ELECTRICAL
 LOADS.
 215.5,220, 240.4 ETC.
  
 3)NOTE: PLEASE SEE FBC 104.6.5, FOR
 SCOPE OF WORK AND VALUATION OF WORK.
 PLEASE SEE VALUE MUST INCLUDE ALL LABOR
 AND MATERIALS , EVENS IF OWNER SUPPLIED.
 PLEASE PROVIDE COPY OCONTRACTS ETC TO
 VERIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 08:34 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 08:34 Sent To E
Notes
2006-05-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-09 Cont ID  
Sent By adarroug Date 2006-02-09 Time 15:13 Rev Time 0.00
Received By adarroug Date 2006-02-09 Time 15:13 Sent To E
Notes
2006-02-09 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 16:26 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 16:26 Sent To E
Notes
2005-07-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-18 Cont ID  
Sent By adarroug Date 2005-03-18 Time 16:00 Rev Time 0.00
Received By adarroug Date 2005-03-18 Time 15:59 Sent To M
Notes
2005-03-18 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-06-02 Cont ID  
Sent By tgordon Date 2006-06-02 Time 08:25 Rev Time 0.35
Received By tgordon Date 2006-06-02 Time 08:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-02-23 Cont ID  
Sent By tgordon Date 2006-02-23 Time 08:53 Rev Time 0.20
Received By tgordon Date 2006-02-23 Time 08:52 Sent To  
Notes
2006-02-23 00:00:00PASSED MECHANICAL REVIEW, PLEASE COMPLY
 WITH ELECTRICAL REVIEW REQUIREMENTS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-23 Cont ID  
Sent By rregueir Date 2005-07-23 Time 10:35 Rev Time 0.00
Received By rregueir Date 2005-07-23 Time 10:35 Sent To PC
Notes
2005-07-23 00:00:00MECHANICAL REVIEW OK.PERMIT TO BE
 ISSUED PENDING SATISFACTION OF
 ELECTRICAL PLAN REVIEW REQUIREMENTS.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-29 Cont ID  
Sent By pkrauss Date 2005-03-29 Time 16:47 Rev Time 0.55
Received By pkrauss Date 2005-03-29 Time 16:27 Sent To E
Notes
2005-03-29 00:00:00DENIED:
 PER FS 471.025 & FAC 61G15-23.002 (2),
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND NUMBER ON EACH SHEET.
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 NOTICE OF COMMENCEMENT REQUIRED.
  
 ELECTRICAL PERMIT REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.