Plan Review Details - Permit 05031124
Plan Review Stops For Permit 05031124
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-19 Cont ID  
Sent By jwitmer Date 2005-07-19 Time 17:02 Rev Time 1.22
Received By jwitmer Date 2005-07-19 Time 17:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-20 Cont ID  
Sent By jwitmer Date 2005-05-20 Time 11:55 Rev Time 0.77
Received By jwitmer Date 2005-05-20 Time 11:55 Sent To  
Notes
2005-05-20 00:00:00PERMIT: 05031124
 ADD: 1515 N FLAGLER #320
 CONT: POINTE SITE DEV
 TEL: (954) 709-1926
 2001 FL BLD CODE= 2001 FLORIDA BUILDING
 CODE * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 *****COMMENTS NOT ADDRESSED FROM THE
 FIRST REVIEW******
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 4) 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 SEE RECEPTION DOOR AND STORAGE DOOR!!!!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-14 Cont ID  
Sent By jwitmer Date 2005-04-14 Time 07:46 Rev Time 0.55
Received By jwitmer Date 2005-04-14 Time 07:38 Sent To  
Notes
2005-04-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031124
 ADD: 1515 N FLAGLER #320
 CONT: POINTE SITE DEV
 TEL: (954) 709-1926
 2001 FL BLD CODE= 2001 FLORIDA BUILDING
 CODE * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 4) 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 17:45 Rev Time 0.50
Received By dpalmer Date 2005-07-26 Time 17:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-29 Cont ID  
Sent By dpalmer Date 2005-06-29 Time 19:49 Rev Time 0.30
Received By dpalmer Date 2005-06-29 Time 19:30 Sent To  
Notes
2005-06-29 00:00:00******** UNSAT **********
  
 PLEASE SEE PLANS HAVE NOW COME IN WITH
 CHANGES FROM PREVIOUS PLANS SUBMITTED
 FOR REVIEW.
  
 1)NOTE: PLEASE SEE 110.26, 450.9,
 450.13, 450.21 ETC.
 MINIMUM WORKING CLEARANCES ARE NOT
 REQUIRED IF THE EQUIPMENT IS SUCH THAT
 IT IS NOT LIKELY TO REQUIRE EXAMINATION,
 ADJUSTMENT, SERVICING, OR MAINTENANCE
 WHILE ENERGIZED. HOWEVER, ?SUFFICIENT?
 ACCESS AND WORKING SPACE ARE STILL
 REQUIRED BY THE OPENING PARAGRAPH OF
 110.26, PLEASE SEE 450 AS NOTED ABOVE
 FOR MIN AREA.
 IF USEING SCALE ON PLANS, LESS THAN 9"
 IS SHOWN TO REACH DISC, ETC.
  
 2)NOTE: PLEASE SHOW ATTACHMENT FOR
 TRANSFORMER GROUNDING. 250.30
 PLEASE SEE NOTE MENTIONS TO BLDG
 SECONDARY GRND? PER APPLICABLE CODE.
 PLEASE SEE FBC 104.2.1, CODE SHALL NOT
 BE REFERENCED IN WHOLE OR IN PART FOR
 TECHNICAL AREAS.
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-05-03 Time 15:21 Rev Time 0.25
Received By dpalmer Date 2005-05-03 Time 15:21 Sent To  
Notes
2005-05-03 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PREVIOUS REVIEW WAS
 SET UP AS "PROVISO" FOR CORRECTIONS TO
 BE MADE. PLEASE SEE NEW ELECTRICAL
 SHEETS WERE SUBMITTED AND NO CORRECTIONS
 WERE MADE.
  
 2)NOTE: PLEASE SEE PREVIOUS BLDG REVIEW
 COMMENTS WHICH REQUESTED ALL OLD/VOIDED
 SHEETS BE REMOVED FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE SEE MULTIPLE SHEETS WERE
 SUBMITTED LOOSELY AND NOT INSERTED AS
 REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-24 Cont ID  
Sent By dpalmer Date 2005-03-24 Time 13:17 Rev Time 0.30
Received By dpalmer Date 2005-03-24 Time 13:17 Sent To  
Notes
2005-03-24 00:00:00********** PROVISO/ REVISION **********
  
 1)NOTE: PLEASE SHOW LOAD ON EXISTING
 GUTTER/TAP ALONG WITH NEW LOAD ADDED.
 215.5,220
  
 PLEASE SUBMIT THE ABOVE BEFORE ROUGH
 ELECTRICAL INSPECTION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-07-15 Cont ID  
Sent By mwennerg Date 2005-07-15 Time 15:09 Rev Time 0.00
Received By mwennerg Date 2005-07-15 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-04-06 Cont ID  
Sent By mwennerg Date 2005-04-06 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2005-04-06 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-25 Cont ID  
Sent By adarroug Date 2005-07-25 Time 11:10 Rev Time 0.00
Received By adarroug Date 2005-07-25 Time 11:06 Sent To E
Notes
2005-07-25 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-15 Time 15:00 Rev Time 0.00
Received By shill Date 2005-06-15 Time 15:00 Sent To  
Notes
2005-06-20 00:00:00COMM BOARD #46
  
2005-06-15 00:00:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-02 Cont ID  
Sent By adarroug Date 2005-05-02 Time 17:10 Rev Time 0.00
Received By adarroug Date 2005-05-02 Time 17:10 Sent To  
Notes
2005-05-02 00:00:00TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-18 Cont ID  
Sent By pkrauss Date 2005-04-18 Time 09:58 Rev Time 0.00
Received By pkrauss Date 2005-03-23 Time 13:40 Sent To  
Notes
2005-03-23 00:00:00TO "COMM" BD#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-08 Cont ID  
Sent By pkrauss Date 2005-04-08 Time 14:14 Rev Time 0.45
Received By pkrauss Date 2005-04-08 Time 14:01 Sent To  
Notes
2005-04-08 00:00:00PROVISO:
 1.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC/M
 307.2.3.
  
 2.FIRE DAMPERS ARE REQUIRED FOR DUCTS
 PENETRATING FIRE RATED WALLS OR SHAFT
 WALLS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-14 Cont ID  
Sent By kstevens Date 2005-07-14 Time 07:55 Rev Time 0.33
Received By kstevens Date 2005-07-14 Time 07:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-05-27 Cont ID  
Sent By kstevens Date 2005-05-27 Time 06:31 Rev Time 1.25
Received By kstevens Date 2005-05-26 Time 19:46 Sent To  
Notes
2005-05-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT TWO SETS OF PLANS FOR REVIEW.
 INDIVIDUAL SHEETS NOT APPROVED. REMOVE
 ALL OLD/VOID SHEETS AND SUBMIT ONE SET
 FOR COMPARISON. SECTION 104.2.1.
 2) BREAK ROOM SINK NOW INDICATED AS A
 WORK SINK. SECTION 11-4.1.1(3) STATES
 "AREAS USED ONLY BY EMPLOYEES AS WORK
 AREAS"THIS AREA IS ALSO SHOWS A
 REFRIGERATOR SEEMS TO BE ALSO A BREAK
 ROOM AREA. SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS
 UNLESS THE AREA IS A WORK AREA ONLY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-26 Cont ID  
Sent By kstevens Date 2005-03-26 Time 12:15 Rev Time 0.55
Received By kstevens Date 2005-03-26 Time 12:15 Sent To  
Notes
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A1 ACCESSIBLE TOILET ROOM DETAIL,
 SHOW COMPLIANCE WITH THE FOLLOWING:
 A) 11-4.16.5 FLUSH CONTROLS
 B) HEIGHT & CLEARANCES 11-4.19.3 (29")
 C) EXPOSED PIPES & SURFACES 11-4.19.4
 D) FAUCEST 11-4.19.5
 E) MEASUREMENT FORM CENTERLINE OF LAV
 TO VANITY TO BE MIN. 15" TO CENTER ON
 30" DIMENSION OF CLEAR FLOOR SPACE. (SEE
 FIGURE 32).
 2) SUBMIT A DETAIL FOR THE BREAK ROOM
 SINK SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 A) HEIGHT 11-4.24.2
 B) KNEE CLEARANCE 11-4.24.3
 C) SINK DEPTH 11-4.24.4
 D) CLEAR FLOOR SPACE 11-4.24.5 -
 FORWARD APPROACH REQUIRED. MAXIMUM 19"
 UNDERNEATH THE SINK. NO CABINET DOORS
 ALLOWED IN THE CLEAR FLOOR SPACE.
 E) EXPOSED PIPES & SURFACES 11-4.24.6
 F) FAUCETS 11-4.24.7
 3) SHT P1 WATER RISER, FULL OPEN VALVES
 ARE REQUIRED ON EVERY WATER DOWN-FEED
 LINE. SECTION 606.1(4)
 4) SHT P1 INSTA-HOT WATER HEATERS SHALL
 BE LISTED. SUBMIT MANUF. SPECIFICATION
 SHEETS TO VERIFY. SECTION 303.4
 5) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. IF A DRINKING FOUNTAIN IS
 AVAILABLE IN THE COMMON AREA PLEASE
 INDICATE ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]