Plan Review Details - Permit 05031123
Plan Review Stops For Permit 05031123
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-20 Cont ID  
Sent By jwitmer Date 2005-05-20 Time 12:47 Rev Time 0.77
Received By jwitmer Date 2005-05-20 Time 12:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-14 Cont ID  
Sent By jwitmer Date 2005-04-14 Time 08:54 Rev Time 1.11
Received By jwitmer Date 2005-04-14 Time 07:58 Sent To  
Notes
2005-04-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031123
 ADD: 1515 N FLAGLER 3RD FL CORRIDOR
 CONT: POINTE SITE DEV
 TEL: (954) 709-1926
 2001 FL BLD CODE= 2001 FLORIDA BUILDING
 CODE * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) PLANS INDICATE THE USE OF A "C LABEL"
 DOOR, 705.1.3.2.1 FIRE DOORS ARE
 CLASSIFIED AS 3HR, 1 1/2 HR, 1HR OR 20
 MIN DOORS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 4) PLANS INDICATE
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-20 Cont ID  
Sent By dpalmer Date 2005-05-10 Time 12:40 Rev Time 0.00
Received By dpalmer Date 2005-05-10 Time 12:40 Sent To  
Notes
2005-05-20 00:00:00NEW SHEETS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-23 Cont ID  
Sent By dpalmer Date 2005-03-23 Time 12:09 Rev Time 0.20
Received By dpalmer Date 2005-03-23 Time 12:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-11 Cont ID  
Sent By mwennerg Date 2005-05-11 Time 10:45 Rev Time 0.00
Received By mwennerg Date 2005-05-11 Time 10:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-04-06 Cont ID  
Sent By mwennerg Date 2005-04-06 Time 09:59 Rev Time 0.00
Received By mwennerg Date 2005-04-06 Time 09:59 Sent To  
Notes
2005-04-06 00:00:001) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO BE IN ACCORDANCE WITH NFPA
 241.
  
 2) PLANS DON'T SHOW ANY EXIT LIGHTS OR
 EMERGENCY LIGHTING. ARE YOU USING
 EXISTING EQUIPMENT OR WILL THIS BE A NEW
 INSTALLATION?
  
 3) PLEASE PROVIDE ADDITIONAL INFORMATION
 ON FIRE DOORS AND ASSOCIATED HARDWARE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-27 Cont ID  
Sent By adarroug Date 2005-04-27 Time 15:27 Rev Time 0.00
Received By adarroug Date 2005-04-27 Time 15:27 Sent To  
Notes
2005-04-27 00:00:00TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-18 Cont ID  
Sent By pkrauss Date 2005-04-18 Time 10:19 Rev Time 0.00
Received By pkrauss Date 2005-03-22 Time 14:02 Sent To  
Notes
2005-03-22 00:00:00TO "COMM" BD#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-18 Cont ID  
Sent By pkrauss Date 2005-04-18 Time 10:13 Rev Time 0.30
Received By pkrauss Date 2005-04-18 Time 10:13 Sent To  
Notes
***NONE***