Plan Review Details - Permit 05031081
Plan Review Stops For Permit 05031081
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-18 Cont ID  
Sent By mwennerg Date 2005-04-18 Time 09:33 Rev Time 0.00
Received By mwennerg Date 2005-04-18 Time 09:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-03-24 Cont ID  
Sent By mwennerg Date 2005-03-24 Time 15:41 Rev Time 0.00
Received By mwennerg Date 2005-03-24 Time 15:41 Sent To  
Notes
2005-03-24 00:00:001) PLANS DON'T SHOW THE LOCATIONS OF
 AUDIBLE/VISUAL DEVICES. PLEASE SHOW THE
 LOCATIONS, AND INDICATE IF THESE DEVICES
 ARE EXISTING OR NEW.
  
 2) PLEASE BE ADVISED THAT IN ADDITION TO
 FAN SHUT DOWN, THE ACTIVATION OF ANY
 DUCT SMOKE DETECTOR SHALL CAUSE THE FIRE
 ALARM SYSTEM TO SOUND A GENERAL FIRE
 ALARM.
  
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 15:46 Sent To FIRE
Notes
2005-04-15 00:00:00TO "F" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-18 Cont ID  
Sent By adarroug Date 2005-03-18 Time 10:56 Rev Time 0.00
Received By adarroug Date 2005-03-18 Time 10:56 Sent To FIRE
Notes
2005-03-18 00:00:00TO "F" BOX