| Plan Review Stops For Permit 05031080 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-09-29 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-09-29 |
Time |
07:40 |
Rev Time |
0.75 |
| Received By |
alange |
Date |
2005-09-28 |
Time |
16:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-09-09 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-09-09 |
Time |
07:57 |
Rev Time |
0.75 |
| Received By |
alange |
Date |
2005-09-09 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2005-09-09 00:00:00 | DENIED | | | SECOND REVIEW: | | | | | | 1. PLEASE SHOW ON PLAN BASIC WIND SPEED | | | AS 140MPH.ARCHITECT OF RECORD TO | | | INITIAL CHANGES ON PLANS. | | | | | | 2.ALL PRODUCT APPROVALS REQUIRE THE | | | FOLLOWING TO BE ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 4.INCLUDE A ROOF SHEATHING NAILING | | | SCHEDULE COMPLYING WITH WEST PALM BEACH | | | AMMENDMENTS TO THE FBC 2306.1 | | | NEW PAGE SUBMITTED SHALL HAVE SEAL AND | | | SIGNATURE FROM ARCHITECT OF RECORD. | | | ROOF SHEATHING IS STILL SHOWN AS 1/2" | | | AND SHOULD BE 5/8". | | | | | | NOTE: TRUSS PLANS ARE NOT REQUIRED FOR | | | REVIEW.PLEASE HAVE AT JOB SITE FOR | | | INSPECTORS DURING ROOF FRAMING | | | INSPECTIONS. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-05-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-03 |
Time |
08:59 |
Rev Time |
0.75 |
| Received By |
alange |
Date |
2005-05-03 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2005-05-03 00:00:00 | DENIED | | | | | | 1. PLEASE SHOW ON PLAN BASIC WIND SPEED | | | AS 140MPH. | | | | | | 2.SUBMIT 2 COPIES OF PRODUCT APPROVALS | | | FOR ROOFING.ALL PRODUCT APPROVALS | | | REQUIRE THE FOLLOWING TO BE ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 3.SHOW SIZE AND LOCATION OF ATTIC | | | ACCESS COMPLYING WITH FBC 2309.6 | | | | | | 4.INCLUDE A ROOF SHEACHING NAILING | | | SCHEDULE COMPLYING WITH WEST PALM BEACH | | | AMMENDMENTS TO THE FBC 2306.1 | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-09-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-08 |
Time |
19:02 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-09-08 |
Time |
18:56 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-04-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-11 |
Time |
17:23 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-04-11 |
Time |
17:19 |
Sent To |
B |
|
| Notes |
| 2005-04-11 00:00:00 | ******* UNSAT ****** | | | | | | 1)NOTE: PLEASE SEE ALL OUTLETS OUTSIDE | | | ARE REQUIRED TO BE GFI/GFI PROTECTED. | | | 210.8A3 | | | | | | 2)NOTE: PLEASE SEE PLANS APPEAR TO SHOW | | | SOME SORT OF "WALL SCONCE" ON 3 1/2' | | | WALL? | | | PLEASE VERIFY. | | | | | | 3)NOTE: PLEASE SEE PLANS ARE COMING BACK | | | WITH COMMENTS FROM OTHER REVIEWER(S), | | | PLEASE ADDRESS THE ABOVE AT THIS TIME. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-09-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-27 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-27 |
Time |
13:36 |
Sent To |
B |
|
| Notes |
| 2005-09-27 00:00:00 | TO "ALANGE" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-20 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-20 |
Time |
16:54 |
Sent To |
Z |
|
| Notes |
| 2005-09-20 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-06 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-06 |
Time |
09:17 |
Sent To |
E |
|
| Notes |
| 2005-09-06 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-29 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-29 |
Time |
15:40 |
Sent To |
Z |
|
| Notes |
| 2005-08-29 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-04-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-11 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-11 |
Time |
09:15 |
Sent To |
E |
|
| Notes |
| 2005-04-11 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-05-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-05-03 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-04-06 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2005-04-06 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2005-10-04 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-10-04 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-10-04 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2005-10-04 00:00:00 | OK TO APPROVE PER ANGELLA JONES-VANN, | | | ADMINISTRATOR (PLANNING & ZONING). | | | | | | NOTE: NO PLUMBING OR 20/20 ELECTRIC | | | ALLOWED IN PROPOSED LANAI. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2005-09-26 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-26 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-26 |
Time |
16:19 |
Sent To |
I |
|
| Notes |
| 2005-09-26 00:00:00 | DENIED, | | | 1. PLEASE PROVIDE FLOOR PLANS (2) COPY | | | SHOWING THE EXISTING STRUCTURE AND | | | PROPOSED LANAI. | | | 2. MUST SHOW THE INTERIOR ACCESS OF THE | | | EXISTING STRUCTURE TO PROPOSED LANAI. | | | 3. MUST SHOW THE AREA THAT THE ACCESS | | | WILL BE FROM (MAIN STRUCTRUE). | | | | | | THESE MUST BE SHOWN ON THE FLOOR PLAN. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2005-09-02 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-02 |
Time |
19:55 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-02 |
Time |
19:55 |
Sent To |
I |
|
| Notes |
| 2005-09-02 00:00:00 | DENIED. | | | 1. MUST SHOW THE INTERIOR ACCESS OF THE | | | MAIN STRUCTURE TO NEW ADDITION (LANAI) | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-04-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-04-08 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-04-08 |
Time |
12:49 |
Sent To |
I |
|
| Notes |
| 2005-04-08 00:00:00 | DENIED, | | | 1. NEED TO SHOW THE ADDITION ON (2) COPY | | | OF SURVEY PROVIDING THE SETBACK SIDE & | | | REAR. | | | NOTE: SITE PLAN IS NOT A COMPLETE SITE | | | PLAN OF THE PROPERTY WITH DIMENSIONS. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|