Plan Review Details - Permit 05031046
Plan Review Stops For Permit 05031046
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-15 Cont ID  
Sent By rbrown Date 2005-04-15 Time 17:15 Rev Time 0.00
Received By rbrown Date 2005-04-15 Time 17:15 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-28 Cont ID  
Sent By rbrown Date 2005-03-28 Time 17:27 Rev Time 0.00
Received By rbrown Date 2005-03-28 Time 17:27 Sent To  
Notes
2005-03-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED (140
 MPH), WIND IMPORTANCE FACTOR (1.0) AND
 WIND EXPOSURE CATEGORY (B).ADD THIS
 INFORMATION TO THE PLANS.
  
 2) THE SUBMITTED LIGHT POLE ORDERING
 INFORMATION SHEET ONLY COVERS WIND LOAD
 RATINGS UPTO 120 MPH.THE DESIGN WIND
 SPEED FOR WEST PALM BEACH IS 140 MPH SO
 HOW IS THE MAXIMUM ALLOWABLE EPA OF THE
 LIGHT FIXTURE DETERMINED?
  
 3) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.PLEASE COMPLY.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop DEMO DEMO/BOARD/SEC/EMERGENCY
Rev No 1 Status P Date 2005-04-18 Cont ID  
Sent By btrobaug Date 2005-04-18 Time 11:35 Rev Time 0.50
Received By btrobaug Date 2005-04-18 Time 11:28 Sent To  
Notes
2005-04-18 00:00:00ADDED DEMO STOP IN ERROR./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-04-18 Cont ID  
Sent By btrobaug Date 2005-04-18 Time 11:43 Rev Time 0.50
Received By btrobaug Date 2005-04-18 Time 11:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-22 Cont ID  
Sent By btrobaug Date 2005-03-22 Time 16:14 Rev Time 0.50
Received By btrobaug Date 2005-03-22 Time 15:59 Sent To B
Notes
2005-03-22 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FORCODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PLEASE INDICATE THE PANEL AND CIRCUIT
 NUMBERS BEING USED.
  
 2}INDICATE CONDUIT AND CONDUTOR SIZE AND
 TYPE.
  
 3}INDICATE OCP RATING.
  
 4}THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN THEIR NAME
 PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 09:33 Rev Time 0.00
Received By rbrown Date 2005-04-14 Time 09:33 Sent To B
Notes
2005-04-14 00:00:00TO "RBROWN" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 17:27 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 17:27 Sent To E
Notes
2005-03-17 00:00:00TO "E" BOX