Plan Review Details - Permit 05031024
Plan Review Stops For Permit 05031024
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-20 Cont ID  
Sent By lsmith Date 2005-04-20 Time 09:20 Rev Time 0.50
Received By lsmith Date 2005-04-20 Time 09:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-17 Cont ID  
Sent By jgomez Date 2005-03-17 Time 17:44 Rev Time 0.33
Received By jgomez Date 2005-03-17 Time 17:43 Sent To PC
Notes
2005-03-17 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- GENERAL CONTRACTOR CANN'T DO METAL OR
  
 TILE ROOFING. SEE EXECUTIVE ORDER
 04-197.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
 3- PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL OR LOCAL PRODUCT APPROVAL FOR:
 A) ROOF TILE USED (NOTE: CLARIFY IF
 USING DADE COUNTY REPORT OR SBCCI
 REPORT. DON'T SUBMIT BOTH).
 B) ADHESIVE USED FOR ROOF TILE.
 C) FLAT ROOF SYSTEM USED.
  
 **NOTE: ACCORDING TO THE BUILDING
 OFFICIAL DADE COUNTY PRODUCT APPROVALS
 ALONEARE NOT AUTOMATICALLY FLORIDA
 PRODUCT APPROVALS. THEY ARE LOCAL
 PRODUCT APPROVALS FOR DADE COUNTY ONLY.
 IF MANUFACTURER APPLIED FOR FLORIDA
 PRODUCT APPROVAL, THEN, PROVIDE FLORIDA
 PRODUCT APPROVAL REPORT ALONG WITH DADE
 COUNTY NOA SUBMITTED FOR APPROVAL.
 OR , MANUFACTURER TO APPLY FOR LOCAL
 PRODUCT APPROVAL BY COMPLETELY FILLING
 UP LOCAL PRODUCT APPROVAL FORM (SEE
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 FORM) AND DADE COUNTY PRODUCT APPROVAL
 TO BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEAE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-20 Cont ID  
Sent By adarroug Date 2005-04-20 Time 08:55 Rev Time 0.00
Received By adarroug Date 2005-04-20 Time 08:55 Sent To B
Notes
2005-04-20 00:00:00TO "LSMITH" DESK