Plan Review Details - Permit 05031016
| Plan Review Stops For Permit 05031016 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-04-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-04-11 |
Time |
13:21 |
Rev Time |
0.75 |
| Received By |
mjacobs |
Date |
2005-04-11 |
Time |
13:21 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-04-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-04-04 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-04-04 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2005-04-04 00:00:00 | DENIED | | | | | | 1) THE NOA SUBMITTED FOR THE ELK | | | SHINGLES DOES NOT MATCH THE ONE ON THE | | | STATE PRODUCT APPROVAL WEBSITE FOR FL | | | 728. | | | | | | 2) INDICATE THE APPROVED ASSEMBLY THAT | | | WILL BE USED FOR THE FLAT ROOF FROM THE | | | NOA. | | | | | | 3) THE NOA SUBMITTED WITH THE | | | CERTAINTEED FL PRODUCT COVER SHEET DOES | | | NOT HAVE THE APPROVED SYSTEM PAGES WITH | | | IT. | | | | | | 4) THE JOHNS MANVILLE NOA DOES NOT HAVE | | | THE FL PRODUCT APPROVAL COVER SHEET AND | | | THE APPROVED SYSTEM THAT YOU WILL USE IS | | | NOT INDICATED. | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-03-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-03-23 |
Time |
12:47 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2005-03-23 |
Time |
12:47 |
Sent To |
PC |
|
| Notes |
| 2005-03-23 00:00:00 | CHECKLIST: | | | | | | 1- MISSING FLORIDA PRODUCT APPROVAL FOR | | | FLAT ROOF SYSTEM TO BE USED. DADE COUNTY | | | PRODUCT APPROVAL ALONE IS NOT A | | | STATEWIDE PRODUCT APPROVAL. CHECK WITH | | | WWW.FLORIDABUILDING.ORG TO SEE IF | | | MANUFACTURER HAS APPLIED FOR FLORIDA | | | PRODUCT APPROVAL OR APPLY FOR LOCAL | | | PRODUCT APPROVAL BY USING LOCAL PRODUCT | | | APPROVAL FORM FROM THE FLORIDA WEBSITE. | | | | | | 2- CLEARLY INDICATE WHICH FLAT ROOF | | | SYSTEM IS GOING TO BE USED. CONTRACT | | | PAPERWORK DON'T INCLUDE INSULATION, BUT | | | ROOF SYSTEMS SUBMITTED ARE FOR SYSTEMS | | | WITH INSULATION. ALSO, VERIFY THAT ROOF | | | SYSTEM TO BE USED IS NOT LIMITED BY | | | GENERAL LIMITATION #9 WHICH DOESN'T | | | ALLOW ANY ENHANCEMENT TO INCREASE THE | | | DESIGN PRESSURES FOR UPLIFT. SEE GENERAL | | | LIMITATIONS SPECIFIED ON DADE COUNTY | | | PRODUCT APPROVAL. | | | | | | 3- CLARIFY ROOF PITCH. APPLICATION SAYS | | | 5:12 WHILE CONTRACT SAYS 3:12. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-04-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-18 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-03-18 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2005-03-18 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | MODIFIED FOR LWC LACKING A STATE PRODUCT | | | APPROVAL. | | | | | | 2.)CONFIRM THAT THE FLAT DECK IS A | | | LIGHTWEIGHT CONCRETE DECK AS PER TEST | | | REPORT SUBMITTED.INDICATE ON | | | APPLICATION. |
|
|
|