Plan Review Details - Permit 05030995
Plan Review Stops For Permit 05030995
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2005-04-15 Cont ID  
Sent By kstevens Date 2005-04-15 Time 09:30 Rev Time 0.50
Received By kstevens Date 2005-04-15 Time 09:30 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2005-04-13 Cont ID  
Sent By kstevens Date 2005-04-13 Time 06:11 Rev Time 0.50
Received By kstevens Date 2005-04-13 Time 06:11 Sent To  
Notes
2005-04-13 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 FROM PREVIOUS REVIEW:
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - THE BTU RATING FOR THE
 GENERATOR HAS NOT BEEN PROVIDED. THIS IS
 REQUIRED FOR SIZING OF THE PIPING. ALSO
 THE BTU RATING FOR THE EXISTING WATER
 HEATER SHALL BE RECHECKED. PAST
 EXPERIANCE INDICATES MORE BTU'S FOR A
 WATER HEATER THAN THE 3.200 INDICATED.
 THIS WILL BE VERIFIED BY THE FIELD
 INSPECTOR.
 7) AN APPLICATION FOR A GENERATOR SHALL
 BE SUBMITTED, AS A BUILDING REVIEW,
 ELECTRICAL REVIEW, ZONING REVIEW, AND
 MECHANICAL REVIEW WILL BE REQUIRED.
 (THIS IS A CITY REQUIREMENT).
 ****************NEW COMMENT************
 1B) UPON READING THE MANUFACTURE
 INFORMATION SUBMITTED, IT INDICATES THAT
 THE MAXIMUM GAS PRESSURE FOR THE
 GENERATOR SHALL BE 1/4 LB. AND 1/2 LB IS
 PROVIDED. A REGULATOR SHALL BE REQUIRED.
 SUBMIT MANUF. SPECIFICATION FOR
 REGULATOR AND SHOW ON ISOMETRIC THE
 REGULATOR DOWNSTREAM OF THE SHUT OFF
 VALVE FOR THE GENERATOR.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-03-24 Cont ID  
Sent By kstevens Date 2005-03-24 Time 08:22 Rev Time 0.50
Received By kstevens Date 2005-03-24 Time 08:21 Sent To  
Notes
2005-03-24 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - THIS SHALL INCLUED THE TOTAL
 BTU'S ON THE LINE TO THE HOUSE.
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - THIS IS TO
 INCLUDE THE DISTANCE TO THE MOST REMOTE
 OUTLET ON THE LINE TO THE HOUSE.
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 7) AN APPLICATION FOR A GENERATOR SHALL
 BE SUBMITTED, AS A BUILDING REVIEW, (FOR
 THE SLAB AS WELL AS THE ANCHORING),
 ELECTRICAL REVIEW, (I SEE HAS BEEN
 APPLIED FOR), ZONING REVIEW, (WHICH I
 SEE HAS BEEN APPROVED), AND A MECHANICAL
 REVIEW, (FOR EXHAUST), IS REQUIRED. THIS
 IS AN INFORMATIONAL COMMENT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 10:23 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 10:23 Sent To G
Notes
2005-03-29 00:00:00TO "KSTEVENS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 15:21 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 15:21 Sent To G
Notes
2005-03-17 00:00:00TO "G" BOX