Plan Review Details - Permit 05030986
Plan Review Stops For Permit 05030986
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-10-18 Cont ID  
Sent By shill Date 2005-10-18 Time 12:44 Rev Time 0.50
Received By shill Date 2005-10-18 Time 12:44 Sent To  
Notes
2005-10-18 00:00:00REVISED WINDOW PRESSURE CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-10-07 Cont ID  
Sent By shill Date 2005-10-06 Time 17:28 Rev Time 0.00
Received By shill Date 2005-10-06 Time 17:28 Sent To PC
Notes
2005-10-07 00:00:00ARCHITECT REMOVED LANGUAGE FROM TITLE
 BLOCK, WILL INFORM AS TO GUIDANCE FROM
 ATTORNEY
2005-10-06 00:00:00FAXED RESPONSE FROM ARCHITECT TO LES
 SMITH, ATTORNEY FOR FLORIDA BOARD OF
 ARCHITECTS.ON SMH DESK PENDING
 RESPONSE

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-09-23 Cont ID  
Sent By shill Date 2005-09-23 Time 00:03 Rev Time 0.50
Received By shill Date 2005-09-23 Time 00:03 Sent To  
Notes
2005-09-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 REVISION, A1
  
 1.)SEE ATTACHED FROM THE DBPR WEBSITE,
 BOARD OF ARCHITECTS, FREQUENTLY ASKED
 QUESTIONS.A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED FOR MAURICE
 MENASCHE, AIA ARCHITECTURE & PLANNING.
  
 PLEASE NOTE THAT I CALLED MR. MENASCHE
 AND LEFT A MESSAGE TO TRY TO DISCUSS
 OVER THE TELEPHONE, BUT DID NOT RECEIVE
 A RETURN CALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-09-20 Cont ID  
Sent By shill Date 2005-09-20 Time 11:41 Rev Time 0.50
Received By shill Date 2005-09-20 Time 11:41 Sent To PC
Notes
2005-09-21 00:00:00REVISED A2

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-07-24 Cont ID  
Sent By shill Date 2005-07-24 Time 14:04 Rev Time 0.50
Received By shill Date 2005-07-24 Time 14:04 Sent To PC
Notes
2005-07-24 00:00:00****CORRECTIONS****
 BUTT GLASS ENGINEERING
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) THE PERMIT WAS ISSUED WITH A PROVISO
 THAT THE BUTT GLASS WINDOWS WOULD BE ON
 A SEPARATE PERMIT.APPLY FOR A SEPARATE
 PERMIT FOR THESE ITEMS WITH THE
 APPROPRIATE PAPERWORK.
  
 2.)THE SAME ENGINEERING THAT WAS
 DENIED PREVIOUSLY WAS RESUBMITTED.THE
 PRESSURES ON THE PLAN FOR THESE OPENINGS
 ARE +31/-41, SHEET A2.THE ENGINEERING
 HAS A DP OF +30.1/-32.8.PLEASE ADDRESS
 BEFORE APPLYING FOR A PERMIT - DO NOT
 SUBMIT THE SAME PAPERWORK UNLESS YOU
 REVISE SHEET A2 AS DISCUSSED WITH THE
 ENGINEER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-23 Cont ID  
Sent By shill Date 2005-06-23 Time 11:52 Rev Time 1.00
Received By shill Date 2005-06-23 Time 11:36 Sent To PC
Notes
2005-06-23 00:00:00****PROVISO****
 SEPARATE PERMIT FOR 2 BUTT GLASS
 OPENINGS 36X47 & 53X95

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-06-13 Cont ID  
Sent By shill Date 2005-06-13 Time 18:29 Rev Time 2.00
Received By shill Date 2005-06-13 Time 17:24 Sent To P
Notes
2005-06-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE GROUND FLOOR ENGINEERING
 CALCULATIONS FOR SOME OF THE BEAMS SAY
 "NO GOOD" INSTEAD OF "OK".IT APPEARS
 THAT THOSE ITEMS ARE NOT OK.PLEASE
 ADDRESS.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 3.)SEE THE PREVIOUS LIST, ITEM 5C.
 THE DESIGN PRESSURE FOR THE 36X47 AND
 53X95 BUTT GLASS OPENINGS IS +31/-41 ON
 SHEET A2.THE ENGINEERING HAS A DESIGN
 PRESSURE LIMITATION OF +30.1/-32.8.
  
 4.)PROVIDE TWO COPIES OF THE MULLION
 PRODUCT APPROVALS.ONLY ONE COPY WAS IN
 THE PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-06 Cont ID  
Sent By jgomez Date 2005-05-06 Time 14:42 Rev Time 4.00
Received By jgomez Date 2005-05-06 Time 14:42 Sent To E
Notes
2005-05-06 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
  
 2- PROVIDE RE-RECORDED NOTICE OF
 COMMENCEMENT. (IT'S EXPIRED).
  
 3- GROUND FLOOR ENGINEERING CALCULATIONS
 CAN'T BE ACCEPTED BECAUSE PROGRAM SHOWS
 THAT CALCULATIONS ARE DONE USING ASCE
 7-02. EDITION ADOPTED BY FBC 2001 IS
 ASCE 7-98. SEE CHAPTER 35 FBC 2001.
  
 4- UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE WHICH WAS REVISED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 CONNECTOR HTA16 WAS REVISED TO USE 10
 NAILS. ADDING MORE NAILS WILL NOT
 INCREASE THE UPLIFT CAPACITY OF THE
 CONNECTOR. REVISE AS REQUIRED.
  
 5- BUTT GLAZING SYSTEM:
 A) THERE ARE 2 ASSEMBLIES SYSTEMS SHOWN
 ON PLANS. ONLY ONE SUBMITTED AND IT
 DOESN'T MATCH PLANS.
  
 B) NEED COMPLETE ENGINEERING ANALYSIS,
 DRAWINGS AND CALCULATIONS. SEE SECTION
 2406.2 FBC 2001.
 **NOTE: DADE COUNTY NOA SUBMITTED CANN'T
 BE USED BECAUSE THE INSTALLATION IS NOT
 THE SAME AS APPROVED ON SUCH NOA.
 ENGINEER NEEDS TO PRODUCE COMPLETE SET
 OF DRAWINGS WITH COMPLETE SPECIFICATIONS
 FOR ASSEMBLIES SHOWN ON PLANS.
  
 C) DESIGN PRESSURES DON'T MEET THE
 DESIGN PRESSURES CALCULATED ON PLANS.
  
 D) SIZE OF ASSEMBLY TESTED IS SMALLER
 THAN THOSE SHOWN ON PLANS. THEREFORE, IT
 DOESN'T COVER THEM.
  
 6- PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE FOR THE FOLLOWING USP
 CONNECTORS: UMH358 AND TDX8.
  
 7- SHUTTERS DRAWINGS NEED TO BE SIGNED
 AND SEALED BY THE ENGINEER AS REQUIRED
 BY HIM ON GENERAL NOTE #11(E).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-13 Cont ID  
Sent By jgomez Date 2005-04-13 Time 17:41 Rev Time 3.00
Received By jgomez Date 2005-04-13 Time 17:40 Sent To PC
Notes
2005-04-13 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
  
 2- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS. NEED RE-RECORDED ONE.
  
 3- PROVIDE ENGINEERING CALCULATIONS FOR
 DESIGN PRESSURES AT ALL EXTERIOR
 OPENINGS SHOWING HOW PRESSURES GIVEN ON
 WINDOW AND DOOR SCHEDULES WERE OBTAINED.
 SEE TABLES 1606.2B AND 1606.2E FBC 2001.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 4- A) GROUNDFLOOR ENGINEERING LETTER
 SAYS THAT STRUCTURE WAS REVIEWED FOR
 140MPH DESIGN SPEED ANDEXPOSURE C.
 DESIGN PRESSURES CALCULATED ON PLANS DO
 NOT CORRESPOND TO EXPOSURE C CATEGORY.
 REVISE AS REQUIRED AND PROVIDE DESIGN
 PRESSURES CALCULATIONS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 B) GROUND FLOOR ENGINEERING LETTER SAYS
 THAT HE IS THE ENGINEER OF RECORD.
 ENGINEER OF RECORD IS THE ONE WHO SEALS
 THE DRAWINGS AND SPECS. SEE CHAPTER 471
 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORD
 AND PROVIDE HIS INFORMATION ACCORDINGLY.
  
 5- A) UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE THAT WAS UPDATED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS AND CALCS THAT COMPLY WITH SEC.
 1609.4.3 FBC FOR TYPE AND NUMBER OF
 FASTENERS THAT DIFFER FROM THOSE TESTED
 AND PUBLISHED BY THE MANUFACTURER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 B) USP RT20T CONNECTOR RESISTS NOT
 LATERAL LOADS. HOW IS THE TRUSS
 SUPPORTED TO RESIST LATERAL LOADS?. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 C) USP USC64 DON'T RESIST THE LOADS
 CALCULATED ON GIRDER TRUSS AT MASTER
 BEDROOM. SEE COMMENTS ON PLANS AND
 RETURN REVIEWED SET AFTER CHANGES ARE
 DONE TO ORIGINAL DRAWINGS TO EXPEDITE
 REVIEW.
  
 D) SPECIFY TRUSS CONNECTOR FOR TRUSSES
 BETWEEN COVERED PATIO AND LIVING ROOM.
 SEE PLANS FOR COMMENTS.
  
 E) USP UMH358 DOESN'T WORK FOR 4 PLY
 MIN. GIRDER TRUSS SPECIFIED ON ROOF
 FRAMING PLAN. REVISE AS REQUIRED.
  
 6- PROVIDE BBQ LISTING AND SPECS SEC.
 2808 FBC 2001.
 **NOTE; BBQ SPECS SAY THAT BBQ ARE
 DESIGNED FOR OUTDOOR USE ONLY. NEED
 MANUFATURER SPECIFICATIONS CERTIFYING
 THAT BBQ GRILLS ARE SAFE TO BE INSTALLED
 IN THE PORCH.
  
 7- BUTT GLAZING ASSEMBLIES: A) PROVIDE
 COMPLETE ENGINEERING ANALYSIS AND
 CALCULATIONS REQUIRED BY SEC. 2406.2 FBC
 2001. INCLUDING GLASS THICKNESS.
 **NOTE: DADE COUNTY NOA'S CANN'T BE USED
 IF THEY ARE ALTERED.
  
 B) THERE ARE TWO DIFFERENT BUTT GLAZING
 ASSEMBLIES. SEE PLANS. NEED ANALYSIS FOR
 BOTH ASSEMBLIES.
  
 C) PROVIDE CALCULATIONS FOR DESIGN
 PRESSURESAT OPENINGS WERE ASSEMBLIES
 ARE GOING TO BE INSTALLED. THIS IS PART
 OF THE ENGINEERING ANALYSIS FOR SITE
 SPECIFIC APPLICATIONS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 8- ROOF TILE: PROVIDE REPORT THAT WAS
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
 SBCCI REPORT, NOT DADE COUNTY NOA.
  
 9- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR ALL
 CONNECTORS SPECIFIED ON THE TRUSS ANCHOR
 SCHEDULE.
  
 10- STORM SHUTTERS: A) DADE COUNTY NOA
 SUBMITTED IS EXPIRED.
  
 B) GENERAL NOTE 11(E) REQUIRES DRAWINGS
 TO BE SIGNED AND SEALED BY THE ENGINEER.
  
 11- FLORIDA PRODUCT APPROVAL FOR FIXED
 WINDOWS IS NOT LEGIBLE.
  
 12- MULLIONS: CLEARLY INDICATE ON
 DRAWINGS SPECIFIC MULLION SIZE AND
 ANCHORING TO VERIFY ADEQUACY ACCORDING
 TO THE CALCULATED DESIGN PRESSURES.
 **NOTE: PAY ATTENTION TO LARGE AREAS
 LIKE FAMILY ROOM AND DINING ROOM
 ASSEMBLIES. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001. SEE PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-05-03 Cont ID  
Sent By dpalmer Date 2006-05-03 Time 07:23 Rev Time 0.00
Received By dpalmer Date 2006-05-02 Time 19:06 Sent To PC
Notes
2006-05-03 00:00:00*** REDLINED PLANS ***
  
  
 REVISED PLANS AFTER ROUGH INSPECTION,
 MAY REQUIRE NEW ROUGH INSPECTIONS FOR
 ITEMS CHANGED, ADDED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 20:28 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 20:05 Sent To PC
Notes
2005-12-21 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE THE 1-POLE 20A
 CIRCUIT FOR THE POOL LTS EXCEED THE MAX
 PF 1920VA PERMITTED ON A 20A CIRCUIT.
 PLEASE VERIFY LOAD.
 240.4, 310.16
  
 2)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OF WALL SPACE IN KITCHEN. 210.52
  
 3)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THAT SHOWN ON
 PANEL SCHEDULE AND ADJUST LOADS AS
 NEEDED.
 220.4B3
  
 4)NOTE: PLEASE SEE NEW INSTA-HOT
 INDICATED ON PLANS, BUT NOT ON PANEL
 SCHEDULE OR LOAD CALCS.
 PLEASE ADJUST.
 215.5
  
 5)NOTE: PLEASE SEE LT FIXTURE IN BEDRM
 CLOSET #4, THIS SEEMS TO BE TOO CLOSE TO
 SHELVING PER 410.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASEDO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-09 Cont ID  
Sent By dpalmer Date 2005-05-09 Time 15:26 Rev Time 0.25
Received By dpalmer Date 2005-05-09 Time 15:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-22 Cont ID  
Sent By dpalmer Date 2005-03-22 Time 13:25 Rev Time 0.33
Received By dpalmer Date 2005-03-22 Time 13:25 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 08:50 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 08:49 Sent To E
Notes
2006-05-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-01-11 Cont ID  
Sent By adarroug Date 2006-01-11 Time 09:09 Rev Time 0.00
Received By adarroug Date 2006-01-11 Time 09:09 Sent To P
Notes
2006-01-11 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-01-05 Cont ID  
Sent By adarroug Date 2006-01-05 Time 14:07 Rev Time 0.00
Received By adarroug Date 2006-01-05 Time 14:07 Sent To E
Notes
2006-01-05 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-12-15 Cont ID  
Sent By adarroug Date 2005-12-15 Time 16:09 Rev Time 0.00
Received By adarroug Date 2005-12-15 Time 16:09 Sent To E
Notes
2005-12-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 10:39 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 10:39 Sent To B
Notes
2005-10-12 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 10:07 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 10:07 Sent To B
Notes
2005-10-04 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 15:37 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 15:37 Sent To B
Notes
2005-09-21 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-07-13 Cont ID  
Sent By adarroug Date 2005-07-13 Time 15:49 Rev Time 0.00
Received By adarroug Date 2005-07-13 Time 15:49 Sent To B
Notes
2005-07-13 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 11:10 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 11:10 Sent To B
Notes
2005-06-23 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 15:31 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 15:31 Sent To B
Notes
2005-06-21 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 09:51 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 09:51 Sent To B
Notes
2005-06-08 00:00:00TO 'JG' DESSK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-01 Cont ID  
Sent By adarroug Date 2005-06-01 Time 13:51 Rev Time 0.00
Received By adarroug Date 2005-06-01 Time 13:51 Sent To B
Notes
2005-06-02 00:00:00PLANS GIVEN BACK TO NAT (INCORRECT
 PAPERWORK SUBMITTED) OK PER DEAN
2005-06-01 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 14:00 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 14:00 Sent To B
Notes
2005-04-29 00:00:00TO "JGOMEZ" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-22 Cont ID  
Sent By adarroug Date 2005-03-22 Time 08:30 Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 08:30 Sent To E
Notes
2005-03-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-15 Cont ID  
Sent By jgomez Date 2005-04-15 Time 09:43 Rev Time 0.00
Received By jgomez Date 2005-03-18 Time 08:58 Sent To PC
Notes
2005-03-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-03-22 Time   Rev Time 0.00
Received By hmoser Date 2005-03-22 Time 16:20 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-20 Cont ID  
Sent By jleech Date 2005-06-20 Time 17:02 Rev Time 0.33
Received By jleech Date 2005-06-20 Time 17:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-03-22 Cont ID  
Sent By jleech Date 2005-03-22 Time 18:12 Rev Time 0.33
Received By jleech Date 2005-03-22 Time 18:12 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-21 Cont ID  
Sent By mmclean Date 2005-03-21 Time 15:08 Rev Time 0.00
Received By mmclean Date 2005-03-21 Time 15:08 Sent To I
Notes
2005-03-21 00:00:00APPROVING SURVEY MEETING SETBACKS.
 NOTE: SITE PLAN & SURVEY SETBACKS ARE
 SHOWN DIFFERENTLY WITH SETBACKS.