Plan Review Details - Permit 05030960
Plan Review Stops For Permit 05030960
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-10 Cont ID  
Sent By shill Date 2005-11-10 Time 09:52 Rev Time 0.50
Received By shill Date 2005-11-10 Time 09:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-11 Cont ID  
Sent By shill Date 2005-06-11 Time 10:12 Rev Time 1.50
Received By shill Date 2005-06-11 Time 10:04 Sent To  
Notes
2005-06-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 FROM PREVIOUS LIST; COMMENTS NOT
 ADDRESSED:
  
 1.)PROVIDE A TITLE BLOCK ON SHEETS E1F
 AND S1E.THE SEAL IS ILLEGIBLE.TITLE
 BLOCK TO INCLUDE ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.
  
 2.) "FRANK W. NEAL & ASSOC" IS REQUIRED
 TO HAVE AN ENGINEERING CERTIFICATE OF
 AUTHORIZATION.INCLUDE THE NUMBER AS
 REQUIRED ON THE TITLE BLOCK.
  
  
 3.)SEAL STRUCTURAL AND ELECTRIC
 SHEETS.THE COVER SHEET ONLY OF
 CALCULATIONS CAN BE SEALED IN LIEU OF
 SEALING EACH SHEET BUT ALL ENGINEERED
 DETAILS SHOWING CODE COMPLIANCE MUST BE
 SEALED WITH A TITLE BLOCK.
  
 4.)PREVIOUS LIST ITEM #3 REQUESTED
 THAT INFORMATION ABOUT THE EXISTING
 BUILDING BE PROVIDED (BUILDING TYPE).
 THIS ITEM HAS NOT BEEN ADDRESSED BUT THE
 ENGINEER HAS ADVISED ME (BY TELEPHONE
 CONVERSATION) THAT THIS IS A TYPE II
 BUILDING.SEE FBC1511.5.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-25 Cont ID  
Sent By shill Date 2005-03-25 Time 16:02 Rev Time 1.00
Received By shill Date 2005-03-25 Time 15:52 Sent To  
Notes
2005-03-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE A TITLE BLOCK ON SHEETS E1F
 AND S1E.THE SEAL IS ILLEGIBLE.TITLE
 BLOCK TO INCLUDE ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.
  
 2.) "FRANK W. NEAL & ASSOC" IS REQUIRED
 TO HAVE AN ENGINEERING CERTIFICATE OF
 AUTHORIZATION.INCLUDE THE NUMBER AS
 REQUIRED ON THE TITLE BLOCK.
  
 3.)SHOW COMPLIANCE WITH FBC1511.2.1.
 NO INFORMATION ABOUT THE EXISTING
 BUILDING WAS PROVIDED.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2005-11-10 Cont ID  
Sent By dpalmer Date 2005-11-10 Time 11:27 Rev Time 0.00
Received By dpalmer Date 2005-11-10 Time 11:27 Sent To  
Notes
2005-11-10 00:00:00***** PLANS REDLINED***********
  
  
 ** LIGHTNING PROTECTION SHOWN CAN NOT BE
 INSTALLED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-09 Cont ID  
Sent By dpalmer Date 2005-06-09 Time 14:25 Rev Time 0.25
Received By dpalmer Date 2005-06-09 Time 14:25 Sent To  
Notes
2005-06-09 00:00:00********** UNSAT 2ND REVIEW **********
  
 1)NOTE: PLEASE SEE SAME NOTES AS
 PREVIOUS REVIEW.
  
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL AND REPEAT COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-25 Cont ID  
Sent By dpalmer Date 2005-03-25 Time 16:56 Rev Time 0.25
Received By dpalmer Date 2005-03-25 Time 16:56 Sent To  
Notes
2005-03-25 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SEE ANY LIGHTNING
 PROTECTION MUST CONFORM TO UL96A AND
 NFPA-780.
 PLEASE INCLUDE ALL INFORMATION PER ABOVE
 FOR REVIEW.
 PLEASE ALSO SEE AN ELECTRICLA PERMIT
 WILL BE REQUIRED FOR SYSTEM.
  
 2)NOTE: PLEASE SEE MISSING TITLE BLOCK
 INFORMATION AS REQUIRED UNDER FAC
 61G15-23.002, FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-11-10 Cont ID  
Sent By mcarsill Date 2005-11-10 Time 10:30 Rev Time 0.00
Received By mcarsill Date 2005-11-10 Time 10:23 Sent To  
Notes
2005-11-10 00:00:00PLANS REVIEWED WERE FOR THE REMOVAL
 AND REPLACEMENT OF THE STEEPLE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-06-10 Cont ID  
Sent By mwennerg Date 2005-06-10 Time 15:26 Rev Time 0.00
Received By mwennerg Date 2005-06-10 Time 15:26 Sent To B
Notes
2005-06-10 00:00:00****DENIED****
  
 PLEASE NOTE THAT COMMENTS FROM PREVIOUS
 REVIEW HAVE NOT BEEN ADDRESSED. PLEASE
 SUBMIT ALL REQUIRED INFORMATION.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-04-04 Cont ID  
Sent By mwennerg Date 2005-04-04 Time 15:48 Rev Time 0.00
Received By mwennerg Date 2005-04-04 Time 15:48 Sent To  
Notes
2005-04-04 00:00:001) PLEASE BE ADVISED THAT ALL
 CONTSRUCTION, RENOVATION AND DEMOLITION
 MUST BE IN COMPLIANCE WITH NFPA 241.
  
 2) PLEASE PROVIDE ADDITIONAL INFORMATION
 REGARDING THE EXISTING STRUCTURE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-11-17 Time 14:24 Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 14:24 Sent To  
Notes
2005-11-17 00:00:00TAKEN OFF BD AND SENT TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 18:42 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 18:42 Sent To  
Notes
2005-11-09 00:00:00TO "COMM" BD#35
2005-10-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-06 Cont ID  
Sent By mjacobs Date 2005-06-06 Time 14:43 Rev Time 0.00
Received By mjacobs Date 2005-06-06 Time 14:41 Sent To  
Notes
2005-06-06 00:00:00TO COMM BD#49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 16:44 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 16:44 Sent To  
Notes
2005-05-26 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-03-25 Time   Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 10:35 Sent To  
Notes
2005-03-22 00:00:00TO "COMM" BD/#16

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-04 Cont ID  
Sent By mmclean Date 2005-04-04 Time 09:34 Rev Time 0.00
Received By mmclean Date 2005-04-04 Time 09:34 Sent To  
Notes
2005-04-04 00:00:00APPROVING THE REMOVAL & REPLACING OF
 STEEPLE