Plan Review Details - Permit 05030903
Plan Review Stops For Permit 05030903
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-12-13 Cont ID  
Sent By alange Date 2005-12-13 Time 14:08 Rev Time 0.66
Received By alange Date 2005-12-13 Time 14:08 Sent To  
Notes
2005-12-13 00:00:00RESTAMP OKALANGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-03 Cont ID  
Sent By alange Date 2005-06-03 Time 07:57 Rev Time 1.00
Received By alange Date 2005-06-03 Time 07:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-24 Cont ID  
Sent By alange Date 2005-05-24 Time 09:11 Rev Time 1.00
Received By alange Date 2005-05-24 Time 09:02 Sent To  
Notes
2005-05-24 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.PRODUCT APPROVALS FOR STRAPS AND
 TIE-DOWNS REQUIRED.
 ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE REQUIRE THE FOLLOWING
 TO BE ATACHED
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4. PLEASE SIGN OWNER/AGENT ON ENERGY
 CALS AND SUBMIT TWO COPIES.
  
 7.ATTIC ACCESS NOT REQUIRED IF ROOF
 PEAK IS LESS THAN 24" WITH IN THE ATTIC
 AREA.
  
 8.SHOW WINDOW AND DOOR PRESSURES.
 "0" IS NOT CORRECT.
  
 9.SHOW WINDOW SIZES AND SILL HEIGHT.
 FBC 1005.4WINDOW SIZES TO SMALL TO
 COMPLY WITH THIS SECTION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-25 Cont ID  
Sent By alange Date 2005-03-25 Time 14:24 Rev Time 1.00
Received By alange Date 2005-03-25 Time 13:17 Sent To  
Notes
2005-03-25 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS FOR STRAPS AND
 TIE-DOWNS REQUIRED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER FBC CHAPTER 13
  
 5.PRINTED NAME AND SIGNATURE REQUIRED
 BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. FBC 104.2.1
  
 6.SHOW FINISH FLOOR A MIN. 4' ABOVE
 GRADE.WPB AMMENDMENT TO THE FBC
 1804.1.7
  
 7.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS FBC 2309.6
  
 8.SHOW WINDOW AND DOOR PRESSURES.
  
 9.SHOW WINDOW SIZES AND SILL HEIGHT.
 FBC 1005.4
  
 10.SHOW ROOF SHEATHING NAILING
 SCHEDULE PER WPB AMMENDMENT TO THE
 FBC 2306.1
  
 11.SHOW ON A SITE PLAN LOCATION OF
 ROOM ADDITION AND LOCATION OF OTHER
 STRUCTURES ON PROPERTY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-23 Cont ID  
Sent By btrobaug Date 2005-05-23 Time 10:40 Rev Time 0.50
Received By btrobaug Date 2005-05-23 Time 10:27 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-23 Cont ID  
Sent By btrobaug Date 2005-03-23 Time 14:24 Rev Time 0.50
Received By btrobaug Date 2005-03-23 Time 13:23 Sent To M
Notes
2005-03-23 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST ALL THE REQ'D DEDICATED
 BATH(S) CIRCUIT(S) ON PANEL SCHEDULE.
 PER 210.52D, 210.11C3
  
 2} NOTE THAT THE BEDROOM OUTLETS MUST
 COMPLY WITH 210.12, INDICATE ON PANEL
 SCHEDULE. THE EXISTING PANEL WILL
 PROBABLTY NOT ALLOW FOR THIS.
  
 3} SEE CHAPTER 34 FBC FOR GFI AND SMOKE
 DETECTOR REQUIREMENTS.
  
 4} THE WINDOW A/C SHOWN IN THE ADDITION
 IS NOT SHOWN IN THE CALCULATION. SEE
 220.31(B).
  
 5} RECEPTACLE SPACING IN THE ADDED ROOM
 MUST COMPLY WITH 210.52(A)(1) & (2).
  
 6} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT THEIR NAME AND SIGN
 THE PLANS PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-02 Cont ID  
Sent By adarroug Date 2005-12-02 Time 16:39 Rev Time 0.00
Received By adarroug Date 2005-12-02 Time 16:39 Sent To B
Notes
2005-12-02 00:00:00TO "ALANGE" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-27 Cont ID  
Sent By adarroug Date 2005-05-27 Time 11:47 Rev Time 0.00
Received By adarroug Date 2005-05-27 Time 11:47 Sent To B
Notes
2005-05-27 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-20 Cont ID  
Sent By adarroug Date 2005-05-20 Time 13:57 Rev Time 0.00
Received By adarroug Date 2005-05-20 Time 13:57 Sent To E
Notes
2005-05-20 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-12 Cont ID  
Sent By adarroug Date 2005-05-12 Time 16:27 Rev Time 0.00
Received By adarroug Date 2005-05-12 Time 16:27 Sent To Z
Notes
2005-05-12 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-22 Cont ID  
Sent By adarroug Date 2005-03-22 Time 10:44 Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 10:44 Sent To E
Notes
2005-03-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-25 Cont ID  
Sent By alange Date 2005-03-25 Time 13:44 Rev Time 0.00
Received By alange Date 2005-03-16 Time 16:27 Sent To  
Notes
2005-03-16 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-03-23 Cont ID  
Sent By lsmith Date 2005-03-23 Time 15:44 Rev Time 0.00
Received By lsmith Date 2005-03-23 Time 15:44 Sent To  
Notes
2005-03-23 00:00:00CONTRACTOR SAYS THERE IS NO PLUMBING LS

Review Stop Z ZONING
Rev No 2 Status P Date 2005-05-19 Cont ID  
Sent By mmclean Date 2005-05-19 Time 16:31 Rev Time 0.00
Received By mmclean Date 2005-05-19 Time 16:31 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By mmclean Date 2005-03-21 Time 08:32 Rev Time 0.00
Received By mmclean Date 2005-03-21 Time 08:32 Sent To I
Notes
2005-03-21 00:00:00DENIED,
 1. MUST SHOW THE ADDITION ON THE SURVEY
 (2 COPIES) WITH SETBACKS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720