Plan Review Details - Permit 05030813
Plan Review Stops For Permit 05030813
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-02 Cont ID  
Sent By jwitmer Date 2005-06-02 Time 12:53 Rev Time 1.10
Received By jwitmer Date 2005-06-02 Time 12:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-02 Cont ID  
Sent By jwitmer Date 2005-05-02 Time 17:10 Rev Time 0.55
Received By jwitmer Date 2005-05-02 Time 17:10 Sent To  
Notes
2005-05-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030813
 ADD: 1675 PALM BEACH LAKES BLVD
 1ST FL LOBBY
 CONT:MJS CONSTRUCTION
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 ) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-13 Cont ID  
Sent By jwitmer Date 2005-04-13 Time 10:00 Rev Time 2.22
Received By jwitmer Date 2005-04-13 Time 10:00 Sent To  
Notes
2005-04-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030813
 ADD: 1675 PALM BEACH LAKES BLVD
 1ST FL LOBBY
 CONT:MJS CONSTRUCTION
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 1016.1.1 MISSING THE EXIT SIGN FOR
 THE STAIR TOWER THAT LEADS DIRECTLY
 OUTSIDE. SEE E.1
  
 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-10 Cont ID  
Sent By dpalmer Date 2005-05-10 Time 14:22 Rev Time 0.30
Received By dpalmer Date 2005-05-10 Time 14:17 Sent To  
Notes
2005-05-10 00:00:00NEW SHEET E-1 ADDED INTO SETS.,

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-16 Cont ID  
Sent By dpalmer Date 2005-03-16 Time 13:53 Rev Time 0.50
Received By dpalmer Date 2005-03-16 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-10 Cont ID  
Sent By pkrauss Date 2005-05-16 Time 20:03 Rev Time 0.00
Received By mwennerg Date 2005-05-10 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-04-05 Cont ID  
Sent By mwennerg Date 2005-04-05 Time 13:45 Rev Time 0.00
Received By mwennerg Date 2005-04-05 Time 13:45 Sent To  
Notes
2005-04-05 00:00:001) ALL EXIT DOORS THAT LEAVE THE
 CORRIDOR ARE REQUIRED TO SWING IN THE
 DIRECTION OF TRAVEL. PLANS SHOW SOME OF
 THE EXIT DOORS SWINGING INTO THE
 CORRIDOR.
  
 2) ILLUMINATED EXIT SIGNS ARE REQUIRED
 ABOVE EVERY DOOR THAT SERVES AS AN EXIT.
  
 3) PLANS DON'T SHOW ANY EMERGENCY
 LIGHTING. PLEASE INDICATE THE LOCATIONS
 OF EMERGENCY LIGHTS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER REMODELS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 16:22 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 16:22 Sent To B
Notes
2005-05-24 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 09:10 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 09:09 Sent To  
Notes
2005-04-26 00:00:00TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-15 Cont ID  
Sent By mjacobs Date 2005-05-18 Time 06:27 Rev Time 0.00
Received By pkrauss Date 2005-03-15 Time 10:04 Sent To  
Notes
2005-03-15 00:00:00TO "COMM BD#51"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-16 Cont ID  
Sent By pkrauss Date 2005-05-16 Time 20:02 Rev Time 0.30
Received By pkrauss Date 2005-05-16 Time 20:02 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-12 Cont ID  
Sent By pkrauss Date 2005-04-12 Time 08:11 Rev Time 0.40
Received By pkrauss Date 2005-04-12 Time 07:14 Sent To  
Notes
2005-04-12 00:00:00DENIED:
 PLAN SHEET M1 INDICATES THE SUPPLY
 DIFFUSER WILL BE DIRECTED AWAY FROM THE
 SMOKE DETECTOR.IN ACCORDANCE WITH NFPA
 72 AND NFPA 101, SMOKE DETECTORS ARE TO
 BE INSTALLED IN ACCORDANCE TO THE
 MANUFACTURERS SPECIFICATIONS AND NOT
 LOCATED WITHIN 3 FT OF THE SUPPLY AND 5
 FT FROM A RETURN.SMOKE DETECTOR
 SPACINGSHALL BE BASED ON TABLE
 2-3.6.6.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-03-25 Cont ID  
Sent By kstevens Date 2005-03-25 Time 17:33 Rev Time 0.25
Received By kstevens Date 2005-03-25 Time 17:33 Sent To  
Notes
2005-03-25 00:00:00NO PLUMBING PLANS SUBMITTED OR PLUBMING
 WORK SHOWN.