Plan Review Details - Permit 05030779
Plan Review Stops For Permit 05030779
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-11-22 Cont ID  
Sent By alange Date 2006-11-22 Time 14:03 Rev Time 0.00
Received By alange Date 2006-11-22 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 11:04 Rev Time 0.00
Received By alange Date 2006-10-23 Time 11:04 Sent To  
Notes
2006-10-23 11:28:07DOOR REVISION DENIED
  
 1.PROPER FRAME ATTACHMENT IS DEPENDENT ON BUCK SIZE
 AND ATTACHMENT.DETAILS FOR SITE SPECIFIC PRODUCT
 APPROVAL DO NOT SHOW THE SIZE OR ATTACHMENT OF THE
 BUCK.
  
 2.SIGNATURES ON ENGINEERING SHALL BE ORIGINALS AND
 NOT PHOTO COPIES.
  
 3.APPLICANTS TECHNICAL REPRESENTATIVE ON THE
 APPLICATION FOR SITE SPECIFIC APPROVAL SHOULD BE FILLED
 OUT AS ARAL CONSULTING ENGINEERS INC.
  
 4.QUALITY ASSURANCE ENTITY FOR THE SITE SPECIFIC
 PRODUCT APPROVAL FORM SHOULD BE FILLED OUT WITH THE
 NAME OF THE ARCHITECT / ENGINEER OF RECORD AND THE FORM
 MUST BE ACCOMPANIED BY A SIGNED AND SEALED LETTER FROM
 THE ARCHITECT / ENGINEER OF RECORD STATING THAT THEY
 WILL INSPECT THE INSTALLATION IN THE FIELD.
  
 5.ITEM 1. NAME REFERENCE FOR THE PRODUCT AND ITEM 10
 NAME AND TITLE OF THE PERSON AUTHORIZED TO SIGN ON
 BEHALF OF THE APPLICANT ARE NOT FILLED OUT.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-06-07 Cont ID  
Sent By alange Date 2006-06-07 Time 13:46 Rev Time 0.25
Received By alange Date 2006-06-07 Time 13:46 Sent To  
Notes
2006-06-07 00:00:00REVISED FOOTING DETAIL OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-02-16 Cont ID  
Sent By alange Date 2006-02-16 Time 07:45 Rev Time 1.00
Received By alange Date 2006-02-16 Time 07:22 Sent To  
Notes
2006-02-16 00:00:00FRONT COLUMN AND GARAGE DETAIL CHANGE OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-12-30 Cont ID  
Sent By alange Date 2005-12-30 Time 10:39 Rev Time 0.33
Received By alange Date 2005-12-30 Time 10:39 Sent To  
Notes
2005-12-30 00:00:00REC'D ENGINEERS LETTE FOR BEAM DETAIL,
 OK ALANGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-12-20 Cont ID  
Sent By alange Date 2005-12-20 Time 09:50 Rev Time 0.75
Received By alange Date 2005-12-20 Time 09:34 Sent To  
Notes
2005-12-20 00:00:00REVISION DENIED
  
 1.SUBMIT TWO COPIES OF PRODUCT
 APPROVAL FOR 16FT. OVERHEAD GARAGE DOOR
 WITH THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-21 Cont ID  
Sent By alange Date 2005-09-21 Time 07:18 Rev Time 1.66
Received By alange Date 2005-09-20 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-14 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 15:35 Rev Time 1.50
Received By alange Date 2005-06-14 Time 09:18 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-11 Cont ID  
Sent By btrobaug Date 2005-06-02 Time 14:43 Rev Time 3.50
Received By alange Date 2005-05-09 Time 14:20 Sent To AD
Notes
2005-05-11 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.MIAMI-DADE PRODUCT APPROVAL FOR PGT
 640 ALUMINUM CASEMENT WINDOW IS OK.
 THE ATTACHED STATE APPROVAL IS NOT FOR
 AN IMPACT WINDOW.PLEASE ATTACH AN
 APPROVED STATE APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SMOKE DETECTORS SHALL COMPLY WITH
 FBC 905.2 SEE ELECTRICAL NOTES.
  
 5.SUBMIT A ROOF SHEATHING NAILING
 SCHEDULE FBC2306.1 WPB AMMENDMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2006-09-11 Cont ID  
Sent By dpalmer Date 2006-09-11 Time 13:57 Rev Time 0.00
Received By dpalmer Date 2006-09-11 Time 13:52 Sent To PC
Notes
2006-09-11 00:00:00REV OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2006-08-01 Cont ID  
Sent By dpalmer Date 2006-08-01 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2006-08-01 Time 17:14 Sent To M
Notes
2006-08-01 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE STEAM GEN WAS ADDED
 TO PANEL SCHEDULE, HOWEVER THIS DOES NOT
 SEEM TO HAVE BEEN ADDED TO LOAD
 CALCULATIONS.
 PLEASE REFIGURE LOAD CALCULATIONS.
  
 220, 215.5 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2006-06-29 Cont ID  
Sent By dpalmer Date 2006-06-29 Time 17:43 Rev Time 0.00
Received By dpalmer Date 2006-06-29 Time 17:33 Sent To P
Notes
2006-06-29 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE SEE SPECS FOR NEW STEAM
 UNIT SHALL INDICATE A LISTING FROM A
 NRTL.
 PLEASE SEE PICTURES ARE SUBMITTED
 INDICATING THIS AND SHALL BE VERIFIED ON
 THE FIELD ASTHE SHEETS SUBMITTED DO
 NOT INDICATE ANY LISTING.
 **IF THIS UNIT IS NOT LISTED, IT MAY NOT
 BE INSTALLED.110.3
  
 PLEASE SEE SPECS MENTIONS NOT TO PLACE
 GFI PROTECTION *AS REQUIRED PER NEC
 210.8)??
 PLEASE SEE 210.8,680, IF GFI PROTECTION
 IS NOT INSTALLED, UNIT CAN NOT BE USED.
 PLEASE CLEALRY INDICATE WHICH UNIT IS
 BEING INSTALLED ON NEW SPECS.
  
 2) NOTE: PLEASE SEE UNIT IS NOT SHOWN ON
 PANEL SCHEDULE, ADDED TO LOAD(S)ETC.
 215.5,220.31B
 PLEASE SEE REVISEDPLANS FROM THE
 DESIGN PROFESSIONAL WERE NOT SUBMITTED
 FOR REVIEW .
 PLEASE SEE THAT ALL PLANS MUST BE
 REVISED ANDSUBMITTED.
 106.1.2
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-06-12 Cont ID  
Sent By dpalmer Date 2006-06-12 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2006-06-12 Time 19:21 Sent To P
Notes
2006-06-12 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE SEE SPECS FOR NEW STEAM
 UNIT SHALL INDICATE A LISTING FROM A
 NRTL.
 IF THIS UNIT IS NOT LISTED, IT MAY NOT
 BE INSTALLED.110.3
 PLEASE SEE SPECS SUBMITTED INDICATE UNIT
 AS 3-PHASE, YET SERVICE IS NOT?
 PLEASE SEE SPECS MENTIONS NOT TO PLACE
 GFI PROTECTION *AS REQUIRED PER NEC
 210.8)??
 PLEASE SEE 210.8,680, IF GFI PROTECTION
 IS NOT INSTALLED, UNIT CAN NOT BE USED.
 PLEASE CLEALRY INDICATE WHICH UNIT IS
 BEING INSTALLED ON NEW SPECS.
  
 2) NOTE: PLEASE SEE UNIT IS NOT SHOWN ON
 PANEL SCHEDULE, ADDED TO LOAD(S)ETC.
 215.5,220.31B
  
 3) NOTE: PLEASE SEE PREVIOUS PLANS WERE
 REDLINED FOR MISSING FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 PLEASE INDICATE AND SIZE AS EXISTING GEC
 IS SHOWN ON RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-03-10 Cont ID  
Sent By dpalmer Date 2006-03-10 Time 07:45 Rev Time 0.00
Received By dpalmer Date 2006-03-10 Time 07:31 Sent To  
Notes
2006-03-10 00:00:00****
  
 REDLINED PLANS: FOOTER STEEL REMOVED
 FROM THE GROUNDING ELECTRODE SYSTEM.
 THE FOOTER STEEL IS REQUIRED AND SHALL
 BE PART OF THE SYSTEM. 250.50,250.52

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-03-01 Cont ID  
Sent By dpalmer Date 2006-03-01 Time 20:04 Rev Time 0.00
Received By dpalmer Date 2006-03-01 Time 19:47 Sent To PC
Notes
2006-03-01 00:00:00ELEC IN FOR REVIEW, ARCHITECT TO CALLED
 ON 3/2 FOR CORRECTIONS.
 ***** UNSAT *********
  
  
  
 1)NOTE; PLEASE SEE OCP FOR MAINS A AND B
 HAVE NOW BEEN REMOVED FROM METER/MAIN.
 PLEASE INDICAT ETH OCP FOR BOTH SUB
 PANELS. (200A?)
 215.5
  
 2)NOTE: PLEASE INDICAT EOF THE SUB PANEL
 "A" AND "B" ARE MLO? OR MCB?
 (MLO)?
 215.5
  
 3)NOTE: PLEASE SEE MIN LOAD FOR LAUNDRY
 TO BE 1500VA .220.16, 210.11C
  
 4)NOTE: PLEASE SEE BATH(S) CIRCUIT(S)
 ARE NOW BEING SHOWN AS 15A?
 PLEASE SEE 210.11C3, #12, 20A MIN.
  
 5)NOTE: PLEASE SE ALL CONDUCTOR SIZES
 HAVE NOW BEEN REMOVED FROM PANEL
 SCHEDULES??
 215.5 PLEASE SHOW MIN PER 240.4,310.16
  
 6)NOTE: PLEASE SEE MISSING EGRESS LT AT
 FRONT DOOR.210.70,LS101 7.8
  
 7)NOTE: PLEASE VERIFY THE GDO HP RATING
 , THIS CAN BE REDLINED, HOWEVER IF KNOWN
 AT THIS TIME,PLEASE SEE TABLE 430.148.
 PLANS SHOW TWO DOORS WITH ONLY ONE
 CIRCUIT?
  
 8)NOTE: PLEASE SEE SMALL APPLIANCE
 CIRCUITS NOW SHOWN AT 1200VA, PLEASE SEE
 220.16, 210.52B1 FOR MIN VA TO BE 1500.
  
 ** PLEASE SUBMIT THE ABOVE REVISIONS FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-02-08 Cont ID  
Sent By dpalmer Date 2006-02-08 Time 16:02 Rev Time 0.00
Received By dpalmer Date 2006-02-08 Time 13:52 Sent To B
Notes
2006-02-08 00:00:00*** REVISIONS UNSAT 2ND REVIEW ******
  
 ** SOME NOTES FROM PREVIOUS REVIEW.
  
  
 1)NOTE: PLEASE CORRELATE RISER WITH
 PANELS SUBMITTED. PLEASE SEE RISER SHOW
 A2 AS A 400A MCB PANEL WITH 2-200A BRKRS
 FOR SUB PANELS "B" AND "C" WITH TWO
 ADDITIONAL TWO POLEBRANCHCIRCUITS?
 PLEASE SEE RISER MENTIONS ONLY
 4-CIRCUITS, PANEL SCHEDULE FOR PANEL A2
 MENTIONS 6-SPACES.
 ???
 215.5
  
 2)NOTE: PLEASE SEE ACC#1 SHOWN ON
 SCHEDULE FOR PANEL A2, HOWEVER RISER
 SHOWS THIS ACC UNIT #1 BEING FED FROM
 PANEL"B"??
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE AREAS: LOGGIA AND
 DINING RM WHICH WILL REQUIRE A MIN OF
 SOME TYPE OF LT FIXTURE FOR MEANS OF
 EGRESS. LS 101 7.8, NFPA-70 210.70.
 PLEASE SEE THESE AREAS ARE REDLINED.
  
 4)NOTE: PLEASE VERIFY SEC'S WHICH ARE
 NOTED TO FPL HAND-HOLE AND ARE NOW TO BE
 PER FPL?
 PLEASE VERIFY THIS WITH THE FPL REP, AS
 IT HAS BECOME TO THE ATTENTION OF THIS
 OFFICE, SEC'S FROM THE FPL HAND-HOLE TO
 THE DWELLING SERVICE LOCATION IS THE
 RESPONSIBILITY OF THE OWNER>
 PLEASE VERIFY AS NOT TO HAVE TO REVISE
 THE PLANS AT A LATER DATE IF INDEED
 THESE SEC'S ARE OWNER INSTALLED.
 SIZING WILL BE PER NEC IF THIS IS THE
 CASE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-12-19 Cont ID  
Sent By dpalmer Date 2005-12-19 Time 07:27 Rev Time 0.00
Received By dpalmer Date 2005-12-19 Time 06:50 Sent To P
Notes
2005-12-19 00:00:00******* UNSAT ***********
  
  
 PLEASE SEE SOME ITEMS REDLINED FROM
 PREVIOUS REVIEW(S).
  
 1)NOTE: PLEASE SEE NFPA-70, NFPA-101
 210.70, 7.8 WHICH REQUIRES A MIN CONTROL
 AND EGRESS LIGHTING.
 PLEASE SEE MANY LOCATIONS ON PLANS WHICH
 ONLY INDICATE A J-BOX, WHERE A MIN
 LIGHTING SOURCE IS REQUIRED.
  
 2)NOTE: PLEASE SEE MASTER BEDROM SD IS
 REQUIRED TO BE WITHIN 3' OF THE PEAK ON
 A SLOPED CEILING.
 NFPA-72 11.8.3.5
  
 3)NOTE: PLEASE SEE MIN LIGHTING,AND
 RECEPT(S) FOR AHU'S, 210.63,210.70
 PLEASE ALSO VERIFY IF THE AHU ON FIRST
 FLR IS IN MASTER CLOSET, ALSO PLEASE
 VERIFY THE THERE IS NO OCP AT THIS
 DISCONNECT SHOWN ONPLANS. 240.24
 110.26 ETC.
  
 4)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR SHALL BE SIZED PER
 250.66. 1/0 MIN
 SERVICE RISER HAS BEEN ADJUSTED.
  
 5)NOTE: PLEASE ALSO SEE SERVICE IS NOW
 SHOWN AS 400A'S, HOWEVER SEC'S FROM
 METER TO FPL HANDHOLE IS ONLY RATED AT
 200A'S.
 PLEASE SEE 310.15B6, 310.16
  
 6)NOTE: PLEASE VERIFY THE 2-200A
 BREAKERS SHOWN ON METER/MAIN SCHEDULE,
 PLEASE SEE BOTH DO NOT SEEM TO BE LISTED
 ONTHE SCHEDULE? ARE THESE ABOVE THE
 6-SPACES?
  
 7)NOTE: PLEASESEE POSSIBLE MISSING GFI
 FROM KITCHEN COUNTERSPACE. PLEASE SEE
 WHAT APPEARS TO BE 12" SPACE REDLINE DON
 PLANS.
 210.52C1
  
 8)NOTE: PLEASE SEE RISER SHOWS POOL
 PANEL BEING FED FROM PANEL "B" , HOWEVER
 PANEL SCHEDULE "B" DOES NOT INCLUDE POOL
 PANEL, YET METER/MAIN SCHEDULE DOES.
 PLEASE CORRELATE.
 215.5
  
 9)NOTE: PLEASE INDICATE IF THE LOAD
 SHOWN FOR POOL PUMP IS ALEADY FIGURED
 FOR CONTINUOUS LOAD. ?
 PLEASE SEE 215.3, 230.42 ETC WHICH
 REQUIRES ALL CONTINUOUS LOADS TO BE
 FIGURED AT 125%.
 PLEASE ADJUST LOAD CALCS IF NEEDED.
  
 10)NOTE: PLEASE SEE PREVIOUS REVIEW WITH
 RESPECT TO MIN CLEARENCES REQUIRED FOR
 CU DISC'S PER 110.26
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER @WPB.ORG

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-08 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 12:52 Rev Time 0.50
Received By dpalmer Date 2005-09-08 Time 07:45 Sent To P
Notes
2005-09-08 00:00:00*********** PROVISO ************
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEWS.
  
 1)NOTE: PLEASE INCLUDE ALL SMOKE
 DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS. PLEASE SEE NONE WERE
 ADDED PER PREVIOUS COMMENTS.
 NFPA-72 11.5.1.1
  
 2)NOTE: PLEASE CLARIFY METER/MAIN COMBO.
 RISER APPEARS TO SHOW MENTION A MAIN,
 HOWEVER PLEASE BE SURE THIS EQUIPMENT
 DOES NOT CONTAIN ANY MORE THAN 6 MEANS
 OF DISCONNECT. 230.71
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 4)RELINED THE FOLLOWING
 110.26, CU DISC'S.
 210.70/ 101 7-9 EGRESS LIGHTING
 REQUIRED.
 210.63 AND 210.70 FOR LT RECEPT REQUIRED
 IN ATTIC SPACE.
  
 PLEASE REVISE THE ABOVE ALONG WITH ANY
 OTHER REVISIONS BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-02 Cont ID  
Sent By shill Date 2005-06-10 Time 17:04 Rev Time 0.50
Received By btrobaug Date 2005-06-02 Time 14:40 Sent To B
Notes
2005-06-02 00:00:00 
 SAME NOTES FROM DEWEY PALMER'S REVIEW ON
 4/13. PLEASE ADDRESS COMMENTS AN
 DRESUBMIT FOR REVIEW
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-13 Cont ID  
Sent By dpalmer Date 2005-04-13 Time 18:57 Rev Time 0.75
Received By dpalmer Date 2005-04-13 Time 18:57 Sent To M
Notes
2005-04-13 00:00:00**** NOTES ****
  
 PLEASE SEE PLANS AREIN VERY GOOD
 SHAPE, HOWEVER PLANS ARE COMING BACK FOR
 ZONING COMMENTS. PLEASE SEE THE BELOW
 MINOR CHANGES TO ADJUST AT THIS TIME.
  
 1)NOTE: PLEASE SEE RISER: NOTE ON METER
 INDICATES A METER/MAIN COMBO PANEL, YET,
 RISER SHOWS METER AND THEN FUSED DISC
 BEFORE FEEDING TWO MLO FEED THROUGH
 PANELS.
 PLEASE CLARIFY IF INDEED METER MAIN
 COMBO? IF SO, PLEASE INCLUDE EQUIPMENT
 GROUNDING FROM METER MAIN TO FUSED
 DISCONNECT. 250.110,250.24,250.122
 HOWEVER, THIS APPEARS TO BE A MISPRINT
 AND IF INDEED THIS IS ONLY A METER
 FEEDING A FUSED DISCONNETC, PLEASE ONLY
 REMOVE METER/MAIN NOTE ON METER.
  
 2)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72
 8-1.4.2.8-1.4.1.6.2
 COMMON TEXT NOTE, HOWEVER PLEASE SEE
 NOTES BELOW.
  
 PLEASE SEE MISSING SD;S REQUIRED OUTSIDE
 MASTER BEDRM, BEDRM #'S 2,3,4 AND 5.
 SD MAY BE PLACED OUTSIDE 2,3 AND 4 TO
 MEET "OUTSIDE". ONE ADDITIONAL SD NEEDS
 TO BE OUTSIDE BEDRM #5.
  
 PLEASE SEE SD FOR INSIDE BEDRM #5 NEEDS
 TO BE "INSIDE" BEDRM AS HEADER IS SHOWN
 AT DOORWAY.
  
 PLEASE SEE SD MISSING OUTSIDE MASTER
 BEDRM, PLEASE ALSO SEE SD "INSIDE"
 MASTER BEDRM IS REQUIRED TO BE WITH/IN
 3' OF PEAK. NFPA-72 2-3.4.7
  
 PLEASE SEE SD'S SHOWN INSIDE AND OUTSIDE
 LAUNDRY RM? THESE ARE NOT REQUIRED, BUT
 HOWEVER THESE ARE PERMITTED.
 THE SD OUTSIDE LAUNDRY RM/BATH MUST BE A
 MIN OF 3' FROM BATH DOOR PER NFPA-72
 8-1.4.2 THIS IS ONLY A NOTE:
  
 PLEASE SEE SD LOCATIONS ARE REDLINED ON
 ONE SET OF PLANS FOR LOCATIONS OF ABOVE
 NOTES.
  
 3)NOTE: PLEASE VERIFY OF GAS STOVE AND
 GAS WH IS A 220V CIRCUIT. THIS IS ONLY A
 NOTE AND NO CHANGE IS NEEDED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALLTO GO OVER ANY
 COMMENTS.
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 09:04 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 09:04 Sent To P
Notes
2007-04-12 09:04:56TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2006-11-03 Cont ID  
Sent By adarroug Date 2006-11-03 Time 10:48 Rev Time 0.00
Received By adarroug Date 2006-11-03 Time 10:48 Sent To B
Notes
2006-11-03 10:48:33TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 09:40 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 09:40 Sent To B
Notes
2006-09-12 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 10:50 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 10:50 Sent To E
Notes
2006-09-05 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-07-28 Cont ID  
Sent By adarroug Date 2006-07-28 Time 16:35 Rev Time 0.00
Received By adarroug Date 2006-07-28 Time 16:35 Sent To E
Notes
2006-07-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 13:40 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 13:39 Sent To E
Notes
2006-06-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-06-16 Cont ID  
Sent By adarroug Date 2006-06-16 Time 11:09 Rev Time 0.00
Received By adarroug Date 2006-06-16 Time 11:09 Sent To M
Notes
2006-06-16 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 08:48 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 08:48 Sent To E
Notes
2006-06-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-05-25 Cont ID  
Sent By adarroug Date 2006-05-25 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-05-25 Time 16:39 Sent To P
Notes
2006-05-25 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 10:27 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 10:27 Sent To M
Notes
2006-05-15 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 09:00 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 09:00 Sent To M
Notes
2006-05-01 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 18:31 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 18:31 Sent To E
Notes
2006-03-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 16:19 Sent To E
Notes
2006-02-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 18:17 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 18:17 Sent To E
Notes
2006-02-02 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 18:38 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 18:38 Sent To E
Notes
2005-12-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-06 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 15:35 Rev Time 0.00
Received By adarroug Date 2005-09-06 Time 09:55 Sent To E
Notes
2005-09-06 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 17:02 Rev Time 0.00
Received By shill Date 2005-06-10 Time 17:02 Sent To B
Notes
2005-06-10 00:00:00TO AL DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-27 Cont ID  
Sent By adarroug Date 2005-05-27 Time 14:54 Rev Time 0.00
Received By adarroug Date 2005-05-27 Time 14:53 Sent To E
Notes
2005-05-27 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-13 Cont ID  
Sent By adarroug Date 2005-04-13 Time 16:16 Rev Time 0.00
Received By adarroug Date 2005-04-13 Time 16:16 Sent To E
Notes
2005-04-13 00:00:00TO "SFR" "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-07 Cont ID  
Sent By adarroug Date 2005-04-07 Time 08:42 Rev Time 0.00
Received By adarroug Date 2005-04-07 Time 08:42 Sent To Z
Notes
2005-04-07 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-18 Cont ID  
Sent By adarroug Date 2005-03-18 Time 11:42 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 16:26 Sent To  
Notes
2005-03-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2006-08-02 Cont ID  
Sent By tgordon Date 2006-08-02 Time 16:31 Rev Time 0.30
Received By tgordon Date 2006-08-02 Time 16:31 Sent To P
Notes
2006-08-02 00:00:00REVISION TO MECH. PLANS PAGE M-1 AND M-2
 *** PROVISO ***
 1) DRYER EXHAUST SHOULD NOT TERMINATE
 NEAR A/C CONDENSER UNITS.
  
 2) CLOTHES DRYER VENT MAY NOT DISCHARGE
 LINT ONTO A/C CONDENSER UNIT,PER 2001
 FBC/M 501.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-06-20 Cont ID  
Sent By tgordon Date 2006-06-20 Time 11:22 Rev Time 0.20
Received By tgordon Date 2006-06-20 Time 11:22 Sent To  
Notes
2006-06-20 00:00:00REVISION TO MECH. PLANS PAGE M-2.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-06-07 Cont ID  
Sent By tgordon Date 2006-06-07 Time 12:25 Rev Time 0.30
Received By tgordon Date 2006-06-07 Time 12:25 Sent To P
Notes
2006-06-07 00:00:00*** PROVISO ***
 1) PLEASE PROVIDE CALCULATIONS FOR
 COMCUSTION AIR IN LAUNDRY ROOM, BEFORE
 ROUGH INSPECTION (DO TO GAS DRYER).
 2) DRYER EXHAUST SHOULD NOT TERMINATE
 NEAR A/C CONDENSER UNITS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-05-16 Cont ID  
Sent By tgordon Date 2006-05-16 Time 09:53 Rev Time 0.30
Received By tgordon Date 2006-05-16 Time 09:53 Sent To P
Notes
2006-05-16 00:00:00*** PROVISO ***
 1) CLOTHES DRYER VENT MAY NOT DISCHARGE
 LINT ONTO A/C CONDENSER UNIT,PER 2001
 FBC/M 501.2 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-05-03 Cont ID  
Sent By tgordon Date 2006-05-03 Time 08:10 Rev Time 0.30
Received By tgordon Date 2006-05-03 Time 08:10 Sent To  
Notes
2006-05-03 00:00:00*** DENIED ***
 1) PLEASE PROVIDE COMBUSTION AIR FOR GAS
 CLOTHES DRYER IN LAUNDRY ROOM, AS
 REQUESTED IN LAST TWO REVIEWS PER 2004
 FBC/M 701 .
  
 2) PLEASE SHOW CLOTHES DRYER VENT
 TERMINATION ON MECHANICAL PLANS ( NOTE
 VENT MUST TERMINATE A MIN. OF 4 FEET
 FROM A/C CONDENSER UNIT.
  
 3) PLEASE PROVIED TWO COPYS OF PAGE M-2
 OF MECHANICAL PLANS FOR REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-12-20 Cont ID  
Sent By tgordon Date 2005-12-20 Time 08:54 Rev Time 0.20
Received By tgordon Date 2005-12-20 Time 08:54 Sent To B
Notes
2005-12-20 00:00:00ONLY MECH. PLAN SUBMITTED WAS M-2 WITH
 PLUMBING RISER DIAG.. MECH. PLANS PASTED
 REVIEW ON 9-12-05.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By tgordon Date 2005-09-12 Time 15:54 Rev Time 0.30
Received By tgordon Date 2005-09-12 Time 15:54 Sent To B
Notes
2005-09-12 00:00:00*** PROVISO ***
 1) PLEASE PROVIDE CALCULATIONS FOR
 COMCUSTION AIR IN LAUNDRY ROOM, BEFORE
 ROUGH INSPECTION (DO TO GAS DRYER).
 2) DRYER EXHAUST SHOULD NOT TERMINATE
 NEAR A/C CONDENSER UNITS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-18 Cont ID  
Sent By hmoser Date 2005-04-18 Time   Rev Time 0.00
Received By hmoser Date 2005-04-18 Time 09:58 Sent To P
Notes
2005-04-18 00:00:00PASS PRIVISO
 PLEASE PROVIDE CALCULATIONS FOR
 COMBUSTION AIR IN LAUNDRY ROOM DO TO GAS
 DRYER.PLEASE PROVIDE CALCULATIONS FOR
 ROUGH INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 9 Status P Date 2007-04-16 Cont ID  
Sent By jleech Date 2007-04-16 Time 07:36 Rev Time 0.00
Received By jleech Date 2007-04-16 Time 07:36 Sent To  
Notes
2007-04-16 07:37:31REVISION; BAR SINK AND BAR-B-QUE AREA TO BE FUTURE.

Review Stop P PLUMBING
Rev No 8 Status P Date 2006-08-14 Cont ID  
Sent By jleech Date 2006-08-14 Time 07:29 Rev Time 0.00
Received By jleech Date 2006-08-14 Time 07:29 Sent To  
Notes
2006-08-14 00:00:00REVISED SANITARY RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 7 Status F Date 2006-07-18 Cont ID  
Sent By jleech Date 2006-07-18 Time 12:41 Rev Time 0.00
Received By jleech Date 2006-07-18 Time 12:41 Sent To  
Notes
2006-07-18 00:00:00DENIED;
 REVISED PLANS ARE REQUIRED TO BE FROM
 THE DESIGN PROFESSIONAL OF RECORD.
 PLEASE MAKE CHANGES ON PLANS AND
 RESUBMIT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 6 Status F Date 2006-06-21 Cont ID  
Sent By jleech Date 2006-06-21 Time 10:40 Rev Time 0.00
Received By jleech Date 2006-06-21 Time 10:37 Sent To B
Notes
2006-06-21 00:00:00DENIED;
 PER. MANUFACTURE'S INSTALLATION
 INSTRUCTIONS; SHOW THE DRAIN LOCATION
 FOR THE SMITTY PAN.
 MAXIMUM INLET PRESSURE TO BE 50 PSI.
 WHAT IS HOUSE PRESSURE?
 WHERE IS STEAM HEAD LOCATED? SEE WARNING
 COMMENT INSTALLATION BOOK LAST PAGE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-06-07 Cont ID  
Sent By jleech Date 2006-06-07 Time 15:27 Rev Time 0.00
Received By jleech Date 2006-06-07 Time 15:27 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-05-17 Cont ID  
Sent By mperson Date 2006-05-17 Time 13:19 Rev Time 1.33
Received By mperson Date 2006-05-17 Time 13:19 Sent To PC
Notes
2006-05-17 00:00:00******REV DENIED******
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING REVISION:
  
 1. PER 104.2.1 REQUIREMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: THE SANITARY RISER DIAGRAM
 INDICATED ON SHEET M-2 DOES NOT REFLECT
 THE FLOOR PLAN. THERE ARE 3 BATHROOMS
 AND A BAR LOCATED ON THE SECOND FLOOR
 BUT ALL THE PLUMBING INDICATED ON THE
 SANITARY RISER DIAGRAM IS ON THE FIRST
 FLOOR. PLEASE CORRECT AND SHOW THE
 SANITARY SOIL AND WASTE STACKS TO THE
 SECOND FLOOR PLUMBING IN BATHROOM #2 AND
 3 ROOM #17, BATHROOM #4 ROOM #21,
 BATHROOM #5 ROOM #29 AND THE BAR IN ROOM
 #27.
 2. 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PLEASE INDICATE
 CLEANOUTS ON CORRECTED DRAWING.
 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 PLEASE INDICATE CLEANOUT ON DRAWING.
 708.10 ACCESS. ACCESS SHALL BE PROVIDED
 TO ALL CLEANOUTS. NOTE CLEANOUT LOCATION
 ON WASHING MACHINE PLEASE INDICATE THIS
 ON CORRECTED DRAWING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-12-20 Cont ID  
Sent By jleech Date 2005-12-20 Time 08:05 Rev Time 0.33
Received By jleech Date 2005-12-20 Time 08:05 Sent To M
Notes
2005-12-20 00:00:00REVISED PLUMBING RISER ADDED VEG SINK

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-10 Cont ID  
Sent By jleech Date 2005-09-10 Time 07:00 Rev Time 0.33
Received By jleech Date 2005-09-10 Time 06:59 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-04-21 Cont ID  
Sent By kstevens Date 2005-04-21 Time 18:41 Rev Time 0.50
Received By kstevens Date 2005-04-21 Time 18:41 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2005-09-02 Cont ID  
Sent By mmclean Date 2005-09-02 Time 15:19 Rev Time 0.00
Received By mmclean Date 2005-09-02 Time 15:19 Sent To I
Notes
2005-09-02 00:00:00APPROVING, MUST PULL A SEPERATE PERMIT
 FOR POOL/DECK/FENCE/WALL/GATE WITH CITY
 OF WEST PALM BEACH UTILITY EASEMENT
 APPROVAL (BELLSOUTH/FPL/FLORIDA PUBLIC
 UTILITIES/ADELPHIA).

Review Stop Z ZONING
Rev No 2 Status F Date 2005-06-20 Cont ID  
Sent By mmclean Date 2005-06-20 Time 15:00 Rev Time 0.00
Received By mmclean Date 2005-06-10 Time 16:11 Sent To  
Notes
2005-06-20 00:00:00DENIED,
 1. DOES NOT MEET THE FRONT SETBACK,
 VARIANCE DENIED, IN JUNE MEETING.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
2005-06-10 00:00:00ZONING WILL BE LAST TO REVIEW, GRACE OUT
 AT CONFERENCE.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-12 Cont ID  
Sent By mmclean Date 2005-04-12 Time 14:19 Rev Time 0.00
Received By mmclean Date 2005-04-12 Time 14:19 Sent To I
Notes
2005-04-12 00:00:004/12/05 APPLICANT APPLIED FOR VARIANCE
 6/2/05, GRACE JOYCE, PLANNER.
 **NOTE: PLEASE HAVE OTHER PLAN REVIEWERS
 TO REVIEW.
2005-03-18 00:00:00DENIED, DOES NOT FRONT SETBACK REQUIRE-
 MENTS. AS PER GJOYCE, CALLED APPLICANT
 3-18-05


Account Summary | Usage Policy | Privacy Policy