Plan Review Details - Permit 05030668
Plan Review Stops For Permit 05030668
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-20 Cont ID  
Sent By jwitmer Date 2005-05-20 Time 15:06 Rev Time 0.55
Received By jwitmer Date 2005-05-20 Time 15:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-08 Cont ID  
Sent By jwitmer Date 2005-04-08 Time 15:39 Rev Time 2.22
Received By jwitmer Date 2005-04-08 Time 15:39 Sent To  
Notes
2005-04-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030668
 ADD: 2400 PRESIDENT WAY# 1704
 CONT: PLAZA CONSTRUCTION
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 5) 905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
  
 6) FBC 609.2PARTITIONS SHALL BE
 CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS
 IN TYPE I, II AND IV CONSTRUCTION,
 EXCEPT FRAMING MEMBERS MAY BE OF FIRE
 RETARDANT TREATED WOOD.IN ONE-STOREY
 OR FULLY SPINKLERED TYPE IV BUILDINGS,
 PARTITIONS MAY BE OF ANY MATERIAL
 PERMITTED BY THE CODE.ADD A NOTE,TO
 THE FIRST SHEET OF PLANS, STATING
 WHETHER THE BUILDING IS TYPE I, II OR IV
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 10:49 Rev Time 0.30
Received By dpalmer Date 2005-06-15 Time 10:49 Sent To M
Notes
2005-06-15 00:00:00REDLINED OCP FOR AHU PER 424.3B

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-05-16 Cont ID  
Sent By dpalmer Date 2005-05-16 Time 11:34 Rev Time 0.30
Received By dpalmer Date 2005-05-16 Time 11:03 Sent To  
Notes
2005-05-16 00:00:00***** UNSAT *******
  
 PLEASE SEE THESE ARE NEW AS THIS
 INFORMATION WAS NOT SUBMITTED ON
 ORIGINAL REVIEW.
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE.
 PLEASE SEE NUMEROUS ITEMS WHICH NEED
 CORRECTING. PLEASE SEE 20A OCP ON #14
 AWG. PLEASE SEE 15A FOR SMALL APPL
 CIRCUITS. PLEASE SEE #14 SHOWNFOR
 BATHS. PLEASE SEE CIRCUIT #23, NO ARC
 FAULT PROTECTION NOTED.
 PLEASE SEE
 210.52D,210-52,210.11C1,210.11C3,220.16,
 210.12 ETC.
 PLEASE SEE ONE SET OF PLANS HAVE MANY OF
 THESE ITEMS REDLINED FOR AREAS OF NOTES.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-17 Cont ID  
Sent By dpalmer Date 2005-03-17 Time 11:15 Rev Time 0.50
Received By dpalmer Date 2005-03-17 Time 11:15 Sent To  
Notes
2005-03-17 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE FBC 104.2.1, ALL
 PLANS ARE REQUIRED TO HAVE THE PRINTED
 NAME AND SIGNATURE OF PERSON RESPONSIBLE
 FOR PLANS.
 THIS IS REQUIRED ON ALL PLANS AND FOR
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 3)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 RENOVATIONS TO EXISTING DWELLINGS.
 PLEASE SHOW LOCATIONS OF EXISTING SD'S
 REQUIRED INSIDE AND OUTSIDE BEDRMS OR
 NEW REQUIRED TO BE INSTALLED.
 PLEASE SHOW LOCATIONS OF EITHER EXISTING
 RECEPTS PER 210.52 OR NEW .
  
 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 THIS IS A COMMON TEXT NOTE: PLEASE SEE
 NOTE #3.
  
 6)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
  
 8)NOTE: PLEASE SHOW CONTROL FOR REQUIRED
 EGRESS LIGHTING PER 210.70, LS 101 5-8
 PLEASE SEE FANS NOT SHOWN AS FANS LTS,
 SYSMBOL FOR RECESSED LTS TO CORRELATE
 WITH SYMBOL SCHEDULE.
  
 9)NOTE: PLEASE CLARIFY IF PANEL IS NEW
 OR EXSITNG? PLEASE CLARIFY EXISTING FEED
 TO PANEL, OCP? CONDUCTORS?
 215.5, 240.4,310.16
  
 10)NOTE: PLEASE CORRELATE LOAD CALCS
 WITH LOAD ON PANEL SCHEDULE FOR AHU
 HEAT.
 PLEASE SEE ONE SHOWS 10KW AND THE OTHER
 SHOWS 7.5KW
  
 11)NOTE: PLEASE SEE 220.19 FOR MIN KW
 RATING TO BE FIGURED FOR RANGES.
 PLEASE SEE ONLY 3KW SHOWN ON A 50A
 CIRCUIT?
 PLEASE ALSO SEE WATER HEATER SHOWN AT
 1.5KW?
  
 12)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 PLEASE SEE SOM OF THE ABOVE ITEMS ARE
 REDLINED ON ONE SET OF PLANS FOR
 REFERENCE OF NOTES ABOVE.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-18 Cont ID  
Sent By mwennerg Date 2005-05-18 Time 09:36 Rev Time 0.00
Received By mwennerg Date 2005-05-18 Time 09:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-04-05 Cont ID  
Sent By mwennerg Date 2005-04-05 Time 10:48 Rev Time 0.00
Received By mwennerg Date 2005-04-05 Time 10:48 Sent To  
Notes
2005-04-05 00:00:001) ALL CONSTRUCTION, RENOVATION AND
 DEMOLITION MUST BE IN ACCORDANCE WITH
 NFPA 241.
  
 2) PLEASE SHOW THE LOCATIONS OF SMOKE
 DETECTORS WHICH SHALL RECEIVE THEIR
 OPERATING POWER FROM THE BUILDING
 ELECTRICAL SYSTEM.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE ALARM AND OR
 FIRE SPRINKLER REMODELS IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 09:25 Rev Time 0.00
Received By shill Date 2005-06-08 Time 09:25 Sent To E
Notes
2005-06-08 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 08:14 Rev Time 0.00
Received By adarroug Date 2005-05-04 Time 16:11 Sent To  
Notes
2005-05-16 00:00:00TO "COMM" BD#10
2005-05-04 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-11 Cont ID  
Sent By pkrauss Date 2005-04-11 Time 09:11 Rev Time 0.00
Received By pkrauss Date 2005-03-16 Time 15:14 Sent To  
Notes
2005-03-16 00:00:00TO "COMM" BD#34

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-07-07 Cont ID  
Sent By pkrauss Date 2005-07-07 Time 09:20 Rev Time 0.35
Received By pkrauss Date 2005-07-07 Time 09:19 Sent To  
Notes
2005-07-07 00:00:00APPROVED 5-30-05

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-06-29 Cont ID  
Sent By hmoser Date 2005-06-29 Time 14:02 Rev Time 0.00
Received By hmoser Date 2005-06-29 Time 14:02 Sent To  
Notes
2005-06-29 00:00:00PLAN DENIED
 PLEASE REFER TO SECTION 601.4 BALANCED
 RETURN AIR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-05-30 Cont ID  
Sent By pkrauss Date 2005-05-30 Time 21:24 Rev Time 0.30
Received By pkrauss Date 2005-05-30 Time 21:24 Sent To P
Notes
2005-05-30 00:00:00DENIED:
 TWO COPIES OF PLANS REQUIRED PER 2001
 FBC/M 104.2.1, ONLY ONE PLAN SUBMITTED.
  
 PLAN IS CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-11 Cont ID  
Sent By pkrauss Date 2005-04-11 Time 08:51 Rev Time 0.40
Received By pkrauss Date 2005-04-11 Time 08:44 Sent To  
Notes
2005-04-11 00:00:00DENIED:
 PLANS ARE TO HAVE THE SIGNATURE AND
 PRINTED NAME OF THE PERSON THAT IS
 RESPONSIBLE FOR THE DESIGN OF SUBITTED
 PLANS AND SPECIFICATIONS IN ACCORDANCE
 WITH THE CITY AMMENDMENTS TO THE FBC
 104.2.1.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-01 Cont ID  
Sent By kstevens Date 2005-06-01 Time 16:44 Rev Time 1.00
Received By kstevens Date 2005-06-01 Time 16:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-25 Cont ID  
Sent By pkrauss Date 2005-05-30 Time 21:31 Rev Time 1.00
Received By kstevens Date 2005-03-25 Time 17:09 Sent To  
Notes
2005-03-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. THIS IS FOR ALL SHEETS.
 SECTION 104.2.1.
 2) A WASH MACHINE HOOK-UP IS REQUIRED
 PER TABLE 403.1. PLEASE INDICATE THE
 LOCATION ON THE FLOOR PLAN OR INDICATE
 IF CENTRAL WASH FACILITIES ARE AVAILABLE
 3) PROVIDE LOCATION OF BAR SINK ON FLOOR
 PLAN. IF THIS IS A NEW FIXTURE PLEASE
 SUBMIT A SANITARY RISER DIAGRAM SHOWING
 THE PIPE SIZE, VENT, POINT OF CONNECTION
 AND A WATER RISER DIAGRAM SHOWING PIPE
 SIZE, VALVES, AND POINT OF CONNECTION.
 SECTION 104.3.1.1.
 4) IT APPEARS THAT THE KITCHEN SINK HAS
 CHANGED LOCATION. PLEASE INDICATE
 LOCATION OF ALL PLUMBING FIXTURES ON THE
 PLUMBING FLOOR PLAN. SECTION 104.2.1. IF
 THE KITCHEN SINK IS LOCATED IN A NEW
 LOCATION, SUBMIT A SANITARY RISER
 DIAGRAM AND A WATER RISER DIAGRAM
 SHOWING ALL REQUIRED INFORMATION AS
 REQUESTED IN COMMENT #3. SECTION
 104.3.1.1. - ALSO SHOW ALL REQUIRED
 WATER HAMMER ARRESTORS PER SECTION 604.9
 ON THE WATER RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved