| Plan Review Stops For Permit 05030668 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-05-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-05-20 |
Time |
15:06 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2005-05-20 |
Time |
15:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-04-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-04-08 |
Time |
15:39 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2005-04-08 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2005-04-08 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05030668 | | | ADD: 2400 PRESIDENT WAY# 1704 | | | CONT: PLAZA CONSTRUCTION | | | TEL: (561)###-#### | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) ALL INFORMATION, DRAWINGS, SPECIF- | | | ICATIONS AND ACCOMPANYING DATA SHALL | | | BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | CITY AMENDMENTS 104.2.1 | | | | | | 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 4)TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY | | | | | | 5) 905.2.1 APPROVED SINGLE-STATION OR | | | MULTIPLE STATION SMOKE DETECTORS SHALL | | | BE INSTALLED IN ACCORDANCE WITH NFPA 72, | | | CHAPTER 2, WITHIN EVERY DWELLING UNIT | | | WITHIN AN APARTMENT HOUSE, CONDOMINIMUM, | | | OR TOWNHOUSE AND EVERY GUEST OR SLEEPING | | | ROOM IN A MOTEL, HOTEL, OR DORMITORY & | | | SLEEPING ROOMS IN RESIDENTIAL CARE/ | | | ASSISTED LIVING OCCUPANCIES. WHERE MORE | | | THAN ONE DETECTOR IS REQUIRED TO BE | | | INSTALLED WITHIN INDIVIDUAL DWELLING | | | UNIT, THE DETECTOR SHALL BE WIRED IN | | | SUCH A MANNER THAT THE ACTUATION OF ONE | | | ALARM WILL ACTIVATE ALL THE ALARMS IN | | | THE INDIVIDUAL UNIT. | | | | | | 6) FBC 609.2PARTITIONS SHALL BE | | | CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS | | | IN TYPE I, II AND IV CONSTRUCTION, | | | EXCEPT FRAMING MEMBERS MAY BE OF FIRE | | | RETARDANT TREATED WOOD.IN ONE-STOREY | | | OR FULLY SPINKLERED TYPE IV BUILDINGS, | | | PARTITIONS MAY BE OF ANY MATERIAL | | | PERMITTED BY THE CODE.ADD A NOTE,TO | | | THE FIRST SHEET OF PLANS, STATING | | | WHETHER THE BUILDING IS TYPE I, II OR IV | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-06-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-15 |
Time |
10:49 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-06-15 |
Time |
10:49 |
Sent To |
M |
|
| Notes |
| 2005-06-15 00:00:00 | REDLINED OCP FOR AHU PER 424.3B |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-05-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-16 |
Time |
11:34 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-05-16 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2005-05-16 00:00:00 | ***** UNSAT ******* | | | | | | PLEASE SEE THESE ARE NEW AS THIS | | | INFORMATION WAS NOT SUBMITTED ON | | | ORIGINAL REVIEW. | | | | | | 1)NOTE: PLEASE SEE PANEL SCHEDULE. | | | PLEASE SEE NUMEROUS ITEMS WHICH NEED | | | CORRECTING. PLEASE SEE 20A OCP ON #14 | | | AWG. PLEASE SEE 15A FOR SMALL APPL | | | CIRCUITS. PLEASE SEE #14 SHOWNFOR | | | BATHS. PLEASE SEE CIRCUIT #23, NO ARC | | | FAULT PROTECTION NOTED. | | | PLEASE SEE | | | 210.52D,210-52,210.11C1,210.11C3,220.16, | | | 210.12 ETC. | | | PLEASE SEE ONE SET OF PLANS HAVE MANY OF | | | THESE ITEMS REDLINED FOR AREAS OF NOTES. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-03-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-17 |
Time |
11:15 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-03-17 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2005-03-17 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE FBC 104.2.1, ALL | | | PLANS ARE REQUIRED TO HAVE THE PRINTED | | | NAME AND SIGNATURE OF PERSON RESPONSIBLE | | | FOR PLANS. | | | THIS IS REQUIRED ON ALL PLANS AND FOR | | | ALL SHEETS WHEATHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE. | | | | | | 3)NOTE: PLEASE SEE FBC CHAPTER 34 FOR | | | RENOVATIONS TO EXISTING DWELLINGS. | | | PLEASE SHOW LOCATIONS OF EXISTING SD'S | | | REQUIRED INSIDE AND OUTSIDE BEDRMS OR | | | NEW REQUIRED TO BE INSTALLED. | | | PLEASE SHOW LOCATIONS OF EITHER EXISTING | | | RECEPTS PER 210.52 OR NEW . | | | | | | 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | 5)NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | | UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 | | | THIS IS A COMMON TEXT NOTE: PLEASE SEE | | | NOTE #3. | | | | | | 6)NOTE: PLEASE SEE RECEPTS SERVING | | | KITCHEN COUNTERSPACE TO MEET 210.52C- | | | SEC'S 1,2,3,4 AND 5 | | | | | | 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS | | | ON PLANS. | | | | | | 8)NOTE: PLEASE SHOW CONTROL FOR REQUIRED | | | EGRESS LIGHTING PER 210.70, LS 101 5-8 | | | PLEASE SEE FANS NOT SHOWN AS FANS LTS, | | | SYSMBOL FOR RECESSED LTS TO CORRELATE | | | WITH SYMBOL SCHEDULE. | | | | | | 9)NOTE: PLEASE CLARIFY IF PANEL IS NEW | | | OR EXSITNG? PLEASE CLARIFY EXISTING FEED | | | TO PANEL, OCP? CONDUCTORS? | | | 215.5, 240.4,310.16 | | | | | | 10)NOTE: PLEASE CORRELATE LOAD CALCS | | | WITH LOAD ON PANEL SCHEDULE FOR AHU | | | HEAT. | | | PLEASE SEE ONE SHOWS 10KW AND THE OTHER | | | SHOWS 7.5KW | | | | | | 11)NOTE: PLEASE SEE 220.19 FOR MIN KW | | | RATING TO BE FIGURED FOR RANGES. | | | PLEASE SEE ONLY 3KW SHOWN ON A 50A | | | CIRCUIT? | | | PLEASE ALSO SEE WATER HEATER SHOWN AT | | | 1.5KW? | | | | | | 12)NOTE: PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | | | PLEASE SEE SOM OF THE ABOVE ITEMS ARE | | | REDLINED ON ONE SET OF PLANS FOR | | | REFERENCE OF NOTES ABOVE. | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR | | | REFERENCE ONLY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-05-18 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-05-18 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-04-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-04-05 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-04-05 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2005-04-05 00:00:00 | 1) ALL CONSTRUCTION, RENOVATION AND | | | DEMOLITION MUST BE IN ACCORDANCE WITH | | | NFPA 241. | | | | | | 2) PLEASE SHOW THE LOCATIONS OF SMOKE | | | DETECTORS WHICH SHALL RECEIVE THEIR | | | OPERATING POWER FROM THE BUILDING | | | ELECTRICAL SYSTEM. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR THE FIRE ALARM AND OR | | | FIRE SPRINKLER REMODELS IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-06-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-08 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-08 |
Time |
09:25 |
Sent To |
E |
|
| Notes |
| 2005-06-08 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-05-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-16 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-04 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2005-05-16 00:00:00 | TO "COMM" BD#10 | | 2005-05-04 00:00:00 | IN INCOMING AWAITING SPACE ON "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-04-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-04-11 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-03-16 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2005-03-16 00:00:00 | TO "COMM" BD#34 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2005-07-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-07 |
Time |
09:20 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2005-07-07 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2005-07-07 00:00:00 | APPROVED 5-30-05 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-06-29 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-06-29 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2005-06-29 00:00:00 | PLAN DENIED | | | PLEASE REFER TO SECTION 601.4 BALANCED | | | RETURN AIR. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-05-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-05-30 |
Time |
21:24 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2005-05-30 |
Time |
21:24 |
Sent To |
P |
|
| Notes |
| 2005-05-30 00:00:00 | DENIED: | | | TWO COPIES OF PLANS REQUIRED PER 2001 | | | FBC/M 104.2.1, ONLY ONE PLAN SUBMITTED. | | | | | | PLAN IS CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-04-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-04-11 |
Time |
08:51 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-04-11 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2005-04-11 00:00:00 | DENIED: | | | PLANS ARE TO HAVE THE SIGNATURE AND | | | PRINTED NAME OF THE PERSON THAT IS | | | RESPONSIBLE FOR THE DESIGN OF SUBITTED | | | PLANS AND SPECIFICATIONS IN ACCORDANCE | | | WITH THE CITY AMMENDMENTS TO THE FBC | | | 104.2.1. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-06-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-01 |
Time |
16:44 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-06-01 |
Time |
16:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-03-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-05-30 |
Time |
21:31 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-03-25 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2005-03-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) ALL DRAWINGS SHALL BEAR THE NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. THIS IS FOR ALL SHEETS. | | | SECTION 104.2.1. | | | 2) A WASH MACHINE HOOK-UP IS REQUIRED | | | PER TABLE 403.1. PLEASE INDICATE THE | | | LOCATION ON THE FLOOR PLAN OR INDICATE | | | IF CENTRAL WASH FACILITIES ARE AVAILABLE | | | 3) PROVIDE LOCATION OF BAR SINK ON FLOOR | | | PLAN. IF THIS IS A NEW FIXTURE PLEASE | | | SUBMIT A SANITARY RISER DIAGRAM SHOWING | | | THE PIPE SIZE, VENT, POINT OF CONNECTION | | | AND A WATER RISER DIAGRAM SHOWING PIPE | | | SIZE, VALVES, AND POINT OF CONNECTION. | | | SECTION 104.3.1.1. | | | 4) IT APPEARS THAT THE KITCHEN SINK HAS | | | CHANGED LOCATION. PLEASE INDICATE | | | LOCATION OF ALL PLUMBING FIXTURES ON THE | | | PLUMBING FLOOR PLAN. SECTION 104.2.1. IF | | | THE KITCHEN SINK IS LOCATED IN A NEW | | | LOCATION, SUBMIT A SANITARY RISER | | | DIAGRAM AND A WATER RISER DIAGRAM | | | SHOWING ALL REQUIRED INFORMATION AS | | | REQUESTED IN COMMENT #3. SECTION | | | 104.3.1.1. - ALSO SHOW ALL REQUIRED | | | WATER HAMMER ARRESTORS PER SECTION 604.9 | | | ON THE WATER RISER DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|