Plan Review Details - Permit 05030657
Plan Review Stops For Permit 05030657
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-04-25 Cont ID  
Sent By alange Date 2005-04-25 Time 11:44 Rev Time 0.50
Received By alange Date 2005-04-25 Time 11:44 Sent To  
Notes
2005-04-25 00:00:00SAME COMMENTS FROM LAST REVIEW NOT
 ADDRESSED.
  
 DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PLANS MUST CONTAIN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.FBC 104.2.1
  
 4.SUBMIT 2 COPIES OF A SITE PLAN
 SHOWING NEW AND EXISTING BUILDINGS ON
 PROPERTY.
  
 5.SUBMIT TWO COPIES OF THE FOLLOWING.
 PRODUCT APPROVALS WITH QUALITY ASSURANCE
 REQUIRED FOR THE FOLLOWING.
 ROOFING, WINDOWS, EXTERIOR DOORS, IMPACT
 PROTECTION, AND STRAPS AND TIE-DOWNS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SUBMIT ENERGY CALCS PER CHAPTER 13
 OF THE FBC.
  
 7.SHOW SMOKE DETECTORS COMPLYING WITH
 FBC 905.2
  
 8.SHOW ON PLANS EXISTING SQUARE
 FOOTAGE AND NEW SQUARE FOOTAGE ADDED.
 SQUARE FOOTAGE ON APPLICATION HAS BEEN
 REVISED TO 400SQ.FT.
  
 9.SUBMIT A SHEATHING NAILING SCHEDULE
 PER WEST PALM BEACH AMMENDMENTS TO THE
 FBC 2306.1
  
 10.SCALE ON PLANS IS INCORRECT.
 PLANS SHOW 1/4" SCALE BUT APPEAR TO BE
 1/8" SCALE.
  
 11.SUBMIT DETAILS FOR THE FOLLOWING.
 FLOOR FRAMING, FOOTINGS, EXTERIOR WALLS,
 INTERIOR BEARING WALLS, LEDGERS.
  
 12.DETAILS SUBMITTED WITH PLANS ARE
 INCOMPLETE. FOOTINGS APPEAR TO BE
 MISSING, BEARING WALLS DON'T HAVE
 SUPPORT.
  
 13.SUBMIT A SCHEDULE OF STRAPS AND
 TIE-DOWNS USED AND FASTENING
 REQUIREMENTS.SHOW UP LIFT ON PLANS.
  
 14.VAPOR BARRIER OF A MIN OF 6 MILS IS
 REQUIRED UNDER FLOOR FRAMING.
  
 15.ALL WOOD FRAMING AND SHEATHING LESS
 THAN 8 INCHES FROM EXPOSED EARTH SHALL
 COMPLY WITH FBC 2304.3.2
  
 16.BASED ON SBCCI BUILDING VALUATION
 DATE THE BUILDING VALUATION HAS BEEN
 REVISED TO $28,288.00.ADDITIONAL
 PERMIT FEES OF $2121.20 ARE DUE PRIOR TO
 ISSUING OF PERMIT.
  
 17. SHOW ON PLANS PRESSURES FOR DOOR AND
 WINDOW OPENINGS.
  
 18.SHOW HOW ROOF VENTILATION WILL
 COMPLY WITH FBC 2309.7.2
  
 19.SUBMIT TWO COPIES OF A SOILS REPORT
 FBC 1804.2.2
  
 20.EXISTING SLAB DETAIL NOT SHOWN.
 FOOTINGS ARE REQUIRED ON BEARING SLABS
 AND SHALL BE A MINUMUM OF 12" BELOW
 GRADE.
  
 21.CEILING GYPSUM BOARD SHOWN AS 1/2"
 AND 5/8"PLEASE VERIFY ON PLANS.
  
 22.TERMIT PROTECTION REQUIRED PER
 FBC 2326.5
  
 23.PLEASE SHOW HOW EXISTING BUILDING
 WILL COMPLY FOR SMOKE DETECTORS AND GFCI
 OUTLETS PER FBC 3401.7.1.2.1
  
 24.SHOW ON EXISTING PLANS IF THERE ARE
 ANY EXISTING DOORS OR WINDOWS FROM
 EXISTING CONSTRUCTION TO NEW AREA.
  
 25.SHOW HOW NEW AREA WILL BE ACCESSED
 FROM EXISTING BUILDING.
  
 NOTE:ADDITIONAL COMMENTS MAY FOLLOW
 AFTER CORRECTED PLANS HAVE BEEN
 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-22 Cont ID  
Sent By alange Date 2005-03-22 Time 11:14 Rev Time 2.75
Received By alange Date 2005-03-22 Time 10:07 Sent To  
Notes
2005-03-22 00:00:00 
 DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PLANS MUST CONTAIN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.FBC 104.2.1
  
 4.SUBMIT 2 COPIES OF A SITE PLAN
 SHOWING NEW AND EXISTING BUILDINGS ON
 PROPERTY.
  
 5.SUBMIT TWO COPIES OF THE FOLLOWING.
 PRODUCT APPROVALS WITH QUALITY ASSURANCE
 REQUIRED FOR THE FOLLOWING.
 ROOFING, WINDOWS, EXTERIOR DOORS, IMPACT
 PROTECTION, AND STRAPS AND TIE-DOWNS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SUBMIT ENERGY CALCS PER CHAPTER 13
 OF THE FBC.
  
 7.SHOW SMOKE DETECTORS COMPLYING WITH
 FBC 905.2
  
 8.SHOW ON PLANS EXISTING SQUARE
 FOOTAGE AND NEW SQUARE FOOTAGE ADDED.
 SQUARE FOOTAGE ON APPLICATION HAS BEEN
 REVISED TO 400SQ.FT.
  
 9.SUBMIT A SHEATHING NAILING SCHEDULE
 PER WEST PALM BEACH AMMENDMENTS TO THE
 FBC 2306.1
  
 10.SCALE ON PLANS IS INCORRECT.
 PLANS SHOW 1/4" SCALE BUT APPEAR TO BE
 1/8" SCALE.
  
 11.SUBMIT DETAILS FOR THE FOLLOWING.
 FLOOR FRAMING, FOOTINGS, EXTERIOR WALLS,
 INTERIOR BEARING WALLS, LEDGERS.
  
 12.DETAILS SUBMITTED WITH PLANS ARE
 INCOMPLETE. FOOTINGS APPEAR TO BE
 MISSING, BEARING WALLS DON'T HAVE
 SUPPORT.
  
 13.SUBMIT A SCHEDULE OF STRAPS AND
 TIE-DOWNS USED AND FASTENING
 REQUIREMENTS.SHOW UP LIFT ON PLANS.
  
 14.VAPOR BARRIER OF A MIN OF 6 MILS IS
 REQUIRED UNDER FLOOR FRAMING.
  
 15.ALL WOOD FRAMING AND SHEATHING LESS
 THAN 8 INCHES FROM EXPOSED EARTH SHALL
 COMPLY WITH FBC 2304.3.2
  
 16.BASED ON SBCCI BUILDING VALUATION
 DATE THE BUILDING VALUATION HAS BEEN
 REVISED TO $28,288.00.ADDITIONAL
 PERMIT FEES OF $2121.20 ARE DUE PRIOR TO
 ISSUING OF PERMIT.
  
 17. SHOW ON PLANS PRESSURES FOR DOOR AND
 WINDOW OPENINGS.
  
 18.SHOW HOW ROOF VENTILATION WILL
 COMPLY WITH FBC 2309.7.2
  
 19.SUBMIT TWO COPIES OF A SOILS REPORT
 FBC 1804.2.2
  
 20.EXISTING SLAB DETAIL NOT SHOWN.
 FOOTINGS ARE REQUIRED ON BEARING SLABS
 AND SHALL BE A MINUMUM OF 12" BELOW
 GRADE.
  
 21.CEILING GYPSUM BOARD SHOWN AS 1/2"
 AND 5/8"PLEASE VERIFY ON PLANS.
  
 22.TERMIT PROTECTION REQUIRED PER
 FBC 2326.5
  
 23.PLEASE SHOW HOW EXISTING BUILDING
 WILL COMPLY FOR SMOKE DETECTORS AND GFCI
 OUTLETS PER FBC 3401.7.1.2.1
  
 24.SHOW ON EXISTING PLANS IF THERE ARE
 ANY EXISTING DOORS OR WINDOWS FROM
 EXISTING CONSTRUCTION TO NEW AREA.
  
 25.SHOW HOW NEW AREA WILL BE ACCESSED
 FROM EXISTING BUILDING.
  
 NOTE:ADDITIONAL COMMENTS MAY FOLLOW
 AFTER CORRECTED PLANS HAVE BEEN
 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-04-13 Cont ID  
Sent By dpalmer Date 2005-04-13 Time 15:44 Rev Time 0.25
Received By dpalmer Date 2005-04-13 Time 15:44 Sent To B
Notes
2005-04-13 00:00:00*** UNSAT ***
  
 PLEASE SEE SOMEOF THE SAME COMMENTS FROM
 FIRST REVIEW.
  
 1)NOTE: PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPINSIBLE FOR PLANS.
  
 2)NOTE: PLEASE SEE ZONING NOTES: IF A
 MENAS OF EGRESS IS GOING TO BE REQUIRED
 FROM MAIN HOUSE,CONTROL FOR EGRESS
 LIGHTING IS CONTROLLED.
 210.70,LS 101 5-8
  
 3)NOTE: PLEASE SEE THIS AN ADAPTABLE
 SLEEPING RM. ROOMS CONTAINING A CLOSET
 AND/OR BATHRM REQUIRES A SMOKE DETECTOR.
 THIS IS REQUIRED TO BE AN ELECTRICAL
 120VW/ BATTERY BACK UP. IF ACCESS TO
 MAIN HOUSE IS DONE (PER ZONING) THEN A
 SD WILL ALSO BE REQUIRED OUTSIDE ROOM.
 NFPA-72 8-1.4.1.6.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By dpalmer Date 2005-03-21 Time 11:35 Rev Time 0.30
Received By dpalmer Date 2005-03-21 Time 11:35 Sent To B
Notes
2005-03-21 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE FBC 104.2.1. ALL
 PLANS MUST CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
  
 2)NOTE: PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING PER 210.70, LS 101 5-8
 PLEASE ALSO VERIFY MEANS OF EGRESS
 LIGHTING CONTROL FROM MAIN HOUSE TO NEW
 ADDITION. PLEASE SEE ZOING COMMENTS FOR
 REQUIRED EGRESS FROM MAIN HOUSE.
  
 3)NOTE:PLEASE SEE THESE ARE CONSIDERED
 ADAPTABLE SLEEPING ROOMS AND WILL
 REQUIRE A SD INSIDE AND OUTSIDE ROOMS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-13 Cont ID  
Sent By adarroug Date 2005-04-13 Time 15:10 Rev Time 0.00
Received By adarroug Date 2005-04-13 Time 15:10 Sent To E
Notes
2005-04-13 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-04 Cont ID  
Sent By mmclean Date 2005-04-11 Time 14:10 Rev Time 0.00
Received By adarroug Date 2005-04-04 Time 14:47 Sent To Z
Notes
2005-04-04 00:00:00TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 15:54 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 15:53 Sent To E
Notes
2005-03-17 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-22 Cont ID  
Sent By alange Date 2005-03-22 Time 11:15 Rev Time 0.00
Received By alange Date 2005-03-14 Time 13:20 Sent To  
Notes
2005-03-14 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status F Date 2005-04-12 Cont ID  
Sent By mmclean Date 2005-04-12 Time 08:39 Rev Time 0.00
Received By mmclean Date 2005-04-11 Time 14:18 Sent To I
Notes
2005-04-12 00:00:004/12/05 DENIED - RESUB
 1.MUST HAVE ACCESS FROM THE ADDITION TO
 THE EXISITNG STRUCTURE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
2005-04-11 00:00:00RETURNED RESUB TO NEYITA, NEED TO HAVE
 THE PLANS WITH THE SURVEYS FOR COMPLETE
 REVIEW.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-11 Cont ID  
Sent By mmclean Date 2005-03-16 Time 16:37 Rev Time 0.00
Received By mmclean Date 2005-03-16 Time 16:37 Sent To I
Notes
2005-03-16 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF SURVEY
 SHOWING THE ADDITION PROVIDING THE
 SETBACK FOR THE SIDE AND REAR FROM
 PROPERTY LINE.
 2. MUST PROVIDE A FULL FLOOR PLAN,
 SHOWING HOW THE PLAY ROOM WILL BE
 CONNECTED TO EXISTING PROPERTY. CALLED
 OWNER.
  