Plan Review Details - Permit 05030625
Plan Review Stops For Permit 05030625
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-24 Cont ID  
Sent By shill Date 2005-05-24 Time 16:37 Rev Time 2.00
Received By shill Date 2005-05-24 Time 16:16 Sent To PC
Notes
2005-05-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)THE ONLY CHANGE MADE TO A1 THROUGH
 A4 WAS TO ADD THE DOOR LEGEND.ALL
 OTHER COMMENTS NOT ADDRESSED ON THE PLAN
 WITH THE EXCEPTION OF ADDING BUILDING
 TYPE ONTO THE COVER PAGE.THIS CHANGE
 WAS NOT CLOUDED AND NUMBERED.
  
 2.)THERE ARE SOME HAND DRAWN NOTES ON
 ONE OF THE PLANS.TWO IDENTICAL SETS
 ARE TO BE SUBMITTED.THE HAND DRAWN
 CHANGES WERE NOT INITIALED.
  
 3.)SOME COMMENTS WERE ADDRESSED
 THROUGH A TRANSMITTAL LETTER.THE PLANS
 ARE TO SHOW CODE COMPLIANCE.THESE
 ISSUES SHOULD BE ADDRESSED ON THE PLAN.
  
 4.)FOR THE FIRE RATED WALL (PREVIOUS
 LIST ITEM 1D) AND JOINT SYSTEMS
 (PREVIOUS LIST ITEM 1F) PROVIDE AN
 ASSEMBLY OR GYPSUM LISTING AS REQUESTED
 BY PREVIOUS REVIEWER.NO DETAILS WERE
 PROVIDED.
  
 5.)THE PERMIT APPLICATION IS NOT IN
 THE PACKAGE.
  
 6.)THE TRANSMITTAL SHEET STATES THAT
 SHEET M2 WAS CHANGED.NOTHING IS
 CLOUDED AND THERE ISN'T A REVISION
 NUMBER.ALL REVISIONS ARE TO BE CLEARLY
 INDICATED.
  
 7.)SHEET M2 SHOWS 2 12X12 GRILLES IN
 THE STAIRWAY.SEE PREVIOUS LIST ITEM
 1E, FBC705.2.3.5 IN REGARDS TO OPENINGS
 IN THE STAIRWELL SHAFT.
  
 8.)SEE ATTACHED FS553.80(2)(B).
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.A TRANSMITTAL LETTER WILL
 HELP EXPEDITE PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-11 Cont ID  
Sent By jwitmer Date 2005-04-11 Time 12:53 Rev Time 2.22
Received By jwitmer Date 2005-04-11 Time 12:52 Sent To  
Notes
2005-04-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030625
 ADD: 2240 PALM BEACH LAKES
 CONT:PLAN REVIEW/ ROBERT SHORR
 TEL: (561)301-4011
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A) PROVIDE THE MINIMUM BUILDING TYPE?
 B) PROVIDE FLOOR PLAN INDICATING TENANT
 SEPERATION,704.3. 1ST & 2ND FLOOR
 INDICATE TENANT SEPERATION BUT 3RD AND
 4TH FLOOR DO NOT.
 C) GENERAL NOTE# 4," REPLACE DOORS IN
 COORIDOR WITH 20 MINUTE FIRE RATED
 ASSEMBLIES AS NECESSARY", PROVIDE A DOOR
 SCHEDULE OR OTHER MEANS TO IDENTIFY
 WHICH DOOR ASSEMBLIES WILL BE REPLACED
 UNDER THIS PERMIT.
 D) WHERE RATED WALLS ARE TO HAVE "FIRE
 WALL RESTORATION" PROVIDE THE UL LISTING
 OR GYPSUM LISTING NUMBERAND RATING IN
 HRS.704.2.1.2.
 E) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 F) 705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 2) SEE M-2 STAIRWELL SHAFT CONSTRUCTION,
 SEE 705.2.3.5 OPENINGS IN SHAFT
 ENCLOSURES SHALL BE PERMITTED WHEN
 LIMITED TO THOSE NESSECARY FOR THE
 PURPOSES OF THE SHAFT. PERMITTED
 OPENINGS IN SHAFT ENCLOSURES SHALL BE
 PROTECTED WITH OPENING PROTECTIVES
 HAVING A FIRE RESISTANCE IN ACCORDANCE
 WITH TABLE 705.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-05-03 Time 17:31 Rev Time 0.40
Received By dpalmer Date 2005-05-03 Time 17:10 Sent To  
Notes
2005-05-03 00:00:00****** NOTES ******
  
 PLEASE SEE PROJECT IS STILL ONLY
 SUBMITTED FOR "PLAN REVIEW" AND NOT FOR
 PERMIT.
  
 1)NOTE: PLEASE CORRELATE FEEDERS FROM
 1ST FLR PANEL FOR HOUSE PANEL WITH
 FEEDER LABELED ON HOUSE PANEL SCHEDULE.
 ONE SHOWS 3-#1'S AND THE OTHER 3-#3'S.
  
 PLEASE SEE ALL OTHER COMMENTS FROM
 PREVIOUS REVIEW WERE ADDRESSED.
 SINCE PLANS ARE SUBMITTED FOR "PLAN
 REVIEW" ONLY THEN ALL MUST BE 100%
 CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-22 Cont ID  
Sent By dpalmer Date 2005-03-22 Time 14:56 Rev Time 1.50
Received By dpalmer Date 2005-03-22 Time 14:56 Sent To  
Notes
2005-03-22 00:00:00***** UNSAT *****
  
  
 PLEASE SEE PLANS ARE ONLY IN FOR "PLAN
 REVIEW" AT THIS TIME AND NOT FOR PERMIT.
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G15-23.002.
 PLEASE SEE THE PRINTED NAME AND LICENSE
 # FOR ENGINEER IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE SEE "NEW " PANEL A/C-2
 DOES NOT SHOW CLEARENCE REQUIRED UNDER
 110.26.
  
 3)NOTE: PLEASE CORRELATE ELECTRICAL
 RISER WITH MDP SCHEDULE FOR GROUNDING
 CONDUCTOR.ONE SHOWS #2, THE OTHER #3.
  
 4)NOTE: PLEASE CLARIFY SIZE OF EXISTING
 A/C PANEL.
 PLEASE SEE RISER SHOWS MDP AS 225A AND
 MDP PANEL SCHEDULE AS 400A?
  
 5)NOTE: PLEASE CORRELATE "EXISTING
 HOUSE' PANEL.?? PLEASE SEE RISER SHOWS
 THIS PANEL BEING FED FROM MDP, HOWEVER,
 MDP PANEL SCHEDULE DOES NOT INDICATE ANY
 FEED FOR THIS PANEL?
 PLEASE SEE "EXISTING HOUSE" PANEL
 SCHEDULE, PANEL DETAILS MENTIONS, "FED
 FROM FIRST FLR PANEL"??
 215.5
  
 6)NOTE: PLEASE SHOW LOAD CALCULATION FOR
 NEW A/C-2 PANEL, INCLUDING LARGEST MOTOR
 LOAD AT 125%.
 PLEASE SUBMIT LOAD CALCULATION FOR MDP,
 SHOWING.
 215.5,220
  
 PLEASE SEE ONE SET HAS SOME OF THE ABOVE
 ITEMS REDLINED AT AREAS OF NOTES.
  
 PLEASE SEE ANY POSSIBEL COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-30 Cont ID  
Sent By mwennerg Date 2005-03-30 Time 14:47 Rev Time 0.00
Received By mwennerg Date 2005-03-30 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-24 Cont ID  
Sent By shill Date 2005-04-02 Time 16:15 Rev Time 0.00
Received By shill Date 2005-03-17 Time 08:15 Sent To  
Notes
2005-03-17 00:00:00TO "COMM" BD#9

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-05-16 Cont ID  
Sent By pkrauss Date 2005-05-16 Time 22:03 Rev Time 0.55
Received By pkrauss Date 2005-05-16 Time 22:03 Sent To  
Notes
2005-05-16 00:00:00DENIED:PLAN CHECK ONLY
 1.PLAN SHEET M-1, FLEX DUCT
 PENETRATING RATED PARTITION AT THE
 CORRIDOR & CONFERENCE ROOM SHALL COMPLY
 WITH 2001 FBC/M 607.1.3 #3 ITEMS 1
 THROUGH 4.ALSO 10" FLEXD PENETRATING
 BOTH CONFERENCE ROOMS MISSING A FIRE
 DAMPER.PLEASE NOTE FLEX DUCT SHALL NOT
 PENETRATE RATED WALL OR PARTITIONS PER
 2001 FBC/M 603.5.5.
  
 2.PLAN SHEET M-2, DUCTS PENETRATING
 JURY ROOM SHALL COMPY WITH 2001 FBC/M
 607.1.3 #3 ITEMS 1 THROUGH 4.
  
 3.M-2, 6" SUPPLY DUCT FROM THE COPY
 ROOM INTO THE COORIDOR (RATED WALL).
  
 4.PROVIDE FIRE DAMPERS AT PENTRATION
 THROUGH THE EXTERIOR WALL FOR COMPLIANCE
 WTIH 2001 FBC/M607.1.2 & 607.4
  
 5.PROVIDE ENERGY CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13 SUB
 CHAPTER 400.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-02 Cont ID  
Sent By hmoser Date 2005-04-02 Time   Rev Time 0.00
Received By hmoser Date 2005-04-02 Time 08:33 Sent To  
Notes
2005-04-02 00:00:00PLAN DENIED
 1) PLEASE SUBMIT A FULL SET OF
 ARCHITECTURALS SHOWING ALL FIRE WALL
 LOCATIONS.
 2) PLEASE SHOW A/C DROPS IN CORRIDORS IF
 ERQUIRED.
 3)PAGE M-2 CAN NOT RUN DUCT THROUGH
 STATWELL
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-03-24 Cont ID  
Sent By kstevens Date 2005-03-24 Time 17:52 Rev Time 0.25
Received By kstevens Date 2005-03-24 Time 17:52 Sent To  
Notes
2005-03-24 00:00:00NO PLUMBING PLANS SUBMITTED NO PLUMBING
 WORK SHOWN

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***