| Plan Review Stops For Permit 05030571 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-03-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2005-03-15 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-03-10 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-03-10 |
Time |
10:40 |
Rev Time |
0.25 |
| Received By |
alange |
Date |
2005-03-10 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2005-03-10 00:00:00 | DENIED | | | | | | 1. PLEASE ATTACH STATE APPROVAL TO EACH | | | MIAMI-DATE QUALITY ASSURANCE APPROVAL. | | | | | | 2. BITUMEN ROOF CHECKED OF ON STATE | | | APPROVAL IS FOR A CONCETE DECK? | | | SUBMIT TWO COPIES OF PRODUCT APPROVALS | | | WITH QUALITY ASSURANCE WITH THE | | | FOLLOWING ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 3. SHOW ROOF SLOPE ON APPLICATION. | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | | | | |
|
|
|