Plan Review Details - Permit 05030540
Plan Review Stops For Permit 05030540
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-27 Cont ID  
Sent By rmcdouga Date 2005-04-27 Time 12:50 Rev Time 0.00
Received By rmcdouga Date 2005-04-27 Time 12:50 Sent To  
Notes
2005-04-27 00:00:00PROVISO
  
 1) SUBMIT A RE-RECORDED NOC PRIOR TO
 CALLING FOR THE FIRST INSPECTION. THE
 NOC SUBMITTED EXPIRED 90 DAYS AFTER DATE
 OF RECORDING BECAUSE WORK HAD NOT
 COMMENCED. FS 713.13

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-27 Cont ID  
Sent By rmcdouga Date 2005-03-29 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2005-03-29 Time 14:33 Sent To  
Notes
2005-03-29 00:00:00 
 SUBMIT TWO COPIES OF A KEY PLAN AND AN
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-04-23 Cont ID  
Sent By jleahy Date 2005-04-23 Time 16:01 Rev Time 0.30
Received By jleahy Date 2005-04-23 Time 16:02 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-28 Cont ID  
Sent By dpalmer Date 2005-03-28 Time 15:26 Rev Time 0.30
Received By dpalmer Date 2005-03-28 Time 15:26 Sent To P
Notes
2005-03-28 00:00:00****** UNSAT *****
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING FROM MAIN TO MLO PANEL.
 250.110,250.24, 250.122
  
 2)NOTE: PLEASE SEE MISSING CWP AS PART
 OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 3)NOTE: PLEASE INCLUDE CONDUCOTRS TO NEW
 A/C EQUIPMENT/DISCS'.
  
 4)NOTE: PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
  
 5)NOTE: PLEASE ALSO SEE TWO SETS MIN
 REQUIRED FOR REVIEW AND STAMPING.
  
 6)NOTE: PLEASE PROVIDE A LAYOUT FOR
 ADDITIONAL ELECTRICAL WORK AS PROPOSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-19 Cont ID  
Sent By adarroug Date 2005-04-19 Time 10:11 Rev Time 0.00
Received By adarroug Date 2005-04-19 Time 10:11 Sent To E
Notes
2005-04-19 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-28 Cont ID  
Sent By adarroug Date 2005-03-28 Time 13:48 Rev Time 0.00
Received By adarroug Date 2005-03-28 Time 13:48 Sent To E
Notes
2005-03-28 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 13:08 Rev Time 0.00
Received By adarroug Date 2005-03-23 Time 13:08 Sent To Z
Notes
2005-03-23 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 15:08 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 15:08 Sent To B
Notes
2005-03-10 00:00:00TO "MISC" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-03-29 Cont ID  
Sent By rmcdouga Date 2005-03-29 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2005-03-29 Time 14:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2005-03-25 Cont ID  
Sent By mmclean Date 2005-03-25 Time 16:36 Rev Time 0.00
Received By mmclean Date 2005-03-25 Time 16:35 Sent To I
Notes
2005-03-25 00:00:00APPROVING DRIVEWAY #05030569.
 ALL STRUCTURAL WORK IS INTERIOR NO
 ZONING REQUIRED.