Plan Review Details - Permit 05030502
Plan Review Stops For Permit 05030502
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-02-24 Cont ID  
Sent By jgomez Date 2006-02-24 Time 13:26 Rev Time 0.40
Received By jgomez Date 2006-02-24 Time 13:26 Sent To M
Notes
2006-02-24 00:00:00FIREPLACE REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-01-31 Cont ID  
Sent By jgomez Date 2006-01-31 Time 08:17 Rev Time 0.33
Received By jgomez Date 2006-01-18 Time 15:31 Sent To  
Notes
2006-01-31 00:00:001-31-06 OWNER BROUGHT BACK SIGNED AND
 SEALED DRAWINGS.
2006-01-18 00:00:00CALLED OWNER. STRUCTURAL DRAWINGS
 SUBMITTED FOR RE-STAMP BECAUSE FIELD SET
 WAS STOLEN NEEDS TO BE SIGNED AND SEALED
 BY THE ENGINEER OF RECORD.
 OWNER SAID HE WILL P/U PLANS TO BRING
 THEM TO THE ENGINEER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-08-25 Cont ID  
Sent By jgomez Date 2005-08-25 Time 11:03 Rev Time 0.33
Received By jgomez Date 2005-08-25 Time 11:03 Sent To PC
Notes
2005-08-25 00:00:00BUILDING REVISION. BEAM CHANGES ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-08-25 Cont ID  
Sent By jgomez Date 2005-08-25 Time 10:49 Rev Time 0.33
Received By jgomez Date 2005-08-25 Time 10:49 Sent To PC
Notes
2005-08-25 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1- PRODUCT APPROVALS SUBMITTED ARE
 REVISIONS NOT SUBMITTAL. PRODUCT
 APPROVALS FROM ANOTHER MANUFACTURER WERE
 ALREADY APPROVED. IF YOU WANT TO USE
 THESE PRODUCT, THEN SUBMIT THEM UNDER
 REVISION PROCEDURE AND PAY APPLICABLE
 FEES.
  
 2- IF APPLYING FOR LOCAL PRODUCT
 APPROVAL, THEN NEED TO PROVIDE COMPLETE
 LOCAL PRODUCT APPROVAL FORM FOR EACH
 PRODUCT SUBMITTED. CONTACT JIM WITMER AT
 805-6715 FOR PROCEDURE TO FOLLOW AND
 TIME FRAME.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-08 Cont ID  
Sent By jgomez Date 2005-06-08 Time 12:11 Rev Time 2.00
Received By jgomez Date 2005-06-08 Time 12:11 Sent To PC
Notes
2005-06-08 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- TRUSS ANCHOR SCHEDULE: CONNECTOR F IN
 ENGINEER'S LETTER SAYS THAT CONNECTOR IS
 (2)B+USP HD2X-2X WHILE ANCHOR SCHEDULE
 SHOWS (2)B + USP HDPT. THESE ARE 2
 DIFFERENT CONNECTORS. REVISE AS REQ'D.
  
 2- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR BAHAMA SHUTTERS
 SHOWING INSTALLATION FOR 140MPH WIND
 LOAD ZONE.
  
 3- SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION IN STAIR SECTION AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-24 Cont ID  
Sent By jgomez Date 2005-05-24 Time 14:33 Rev Time 3.00
Received By jgomez Date 2005-05-24 Time 14:33 Sent To PC
Notes
2005-05-24 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- ENTRY DOOR TO HAVE LEAF THAT ALLOWS
 32" MIN. CLEAR OPENING AS REQ'D BY TABLE
 1004 FBC 2001. 32" WIDE DOOR DOESN'T
 PROVIDE THE 32" CLEAR OPENING. REVISE
 DOOR SCHEDULE AS REQUIRED.
  
 2- UPDATE TRUSS ANCHOR SCHEDULE. SEE
 2005 SIMPSON OR USP CATALOGUE THAT WERE
 REVISED TYPE AND NUMBER OF FASTENERS TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 IF TRUSS ANCHOR SCHEDULE AND CONNECTORS
 SPECIFIED ON PLANS SHOW DIFFERENT TYPE
 AND NAILING NUMBER OTHER THAN THOSE
 TESTED & PUBLISHED BY THE MANUFACTURER,
 THEN, COMPLETE ENGINEERING ANALYSIS IS
 REQUIRED TO DEMONSTRATE COMPLIANCE WITH
 SEC. 1609.4.3 FBC 2001.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001. (NOTE: REVISE TRUSS ANCHOR
 SCHEDULEIN SHEET S3 AND SD1).
  
 3- ENERGY CALCULATIONS: UNDER ATTIC AREA
 WAS NOT REVISED AS REQUESTED ON PREVIOUS
 CHECKLIST. SEE SEC. 602.1.ABC.1.2
 CHAPTER 13 FBC 2001 AND REVISE AS REQ'D.
  
 4- ARCHITECTURAL PLANS SHOW LICENSE
 #33849. WHAT'S THIS LICENSE FOR?. UNABLE
 TO MATCH THIS LICENSE # WITH THE FLORIDA
 WEBSITE.
  
 5- SPECIFY IN PLANS HOW OPERABLE
 SHUTTERS WILL COMPLY WITHSEC. 1005.4.4
 FBC 2001. HOW ARE MIN. CLEAR OPENINGS
 MAINTAINED.
  
 6- POSTS SHOWN ON BALCONY GUARDRAIL
 DON'T MATCH STRUCTURAL PLANS. REVISE AS
 REQUIRED.
  
 7- ELEVATIONS ON SHEET A-4 ARE NAMED
 INCORRECTLY. SEE SURVEY FOR PROPER
 ORIENTATION AND REVISE AS REQUIRED.
  
 8- SPECIFY FIREBLOCKING IN ALL AREAS AS
 REQUIRED BY SEC. 2305.1 FBC 2001. SHOW
 FIREBLOCKING IN ALL BLDG SECTIONS,
 STAIRS ETC.
  
 9- SPECIFY DRAFSTOPPING LOCATION AND
 MATERIAL IN 2ND FLOOR FRAMING PLAN AS
 REQUIRED BY SEC. 2305.2.2 FBC 2001.
 (NOTE: THIS DRAFSTOPPPING HAS NOTHING TO
 DO WITH THE FIREPLACE).
  
 10- 2ND FLOOR FRAMING PLAN IS MISSING
 INFORMATION. SPECIFY ALL CONNECTORS
 AROUND STAIRWELL OPENING FRAMING
 MEMBERS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 11- DETAIL 13/SD2 DON'T MATCH 2ND FLOOR
 FRAMING PLAN. REVISE AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 12- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL ONLY FOR DOORS AND WINDOWS TO
 BE USED. TO EXPEDITE REVIEW PROCESS AND
 AVOID CONFUSION CLEARLY IDENTIFY WHICH
 DOOR/WINDOW PRODUCT APPROVAL WILL BE
 USED. DON'T SUBMIT PRODUCT APPROVALS
 THAT WILL NOT BE USED.
 ***SAME THING APPLIES TO MULLIONS THERE
 ARE SEVERAL PRODUCT APPROVALS SUBMITTED.
  
 13- OWES $280.76 FOR UPDATED VALUATION
 AND RADON FEES.
  
 14- SHEET SD1: UPDATE ALL GENERAL NOTES.
 SEE COMMENTS ON PLANS. SEE CHAPTER 19
 AND 35 FOR PROPER REFERENCES AND
 EDITIONS TO BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-05 Cont ID  
Sent By jgomez Date 2005-04-05 Time 16:44 Rev Time 5.00
Received By jgomez Date 2005-04-05 Time 14:34 Sent To PC
Notes
2005-04-01 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- ENTRY DOOR TO HAVE LEAF THAT ALLOWS
 32" MIN. CLEAR OPENING AS REQUIRED BY
 TABLE 1004 FBC 2001. 30"WIDE DOOR
 DOESN'T PROVIDE 32" MIN. CLEAR OPENING.
  
 4- SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 104.2.1.1 OF CITY
 AMENDMENTS TO FBC 2001.
  
 5- UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE FOR TYPE AND NUMBER OF
 FASTENERS SPECIFIED. PROVIDE COMPLETE
 ENGINEERING CALCULATIONS THAT COMPLY
 WITH SEC. 1609.4.3 FBC 2001 FOR TYPE AND
 NUMBER OF FASTENERS THAT DIFFER FROM
 THOSE TESTED AND PUBLISHED BY
 MANUFACTURER TO COMPLY WITH ABOVE
 BUILDING CODE SECTION.
  
 6- PROVIDE SOIL TEST REPORT.
  
 7- ENERGY CALCULATIONS: A) REVISE UNDER
 ATTIC AREA. SEE SEC. 602.1.ABC.1.2
 CHAPTER 13 FBC 2001.
 B) PROVIDE COMPLETE INFORMATION ON TOP
 OF FORM. NEED OWNER & BUILDER INFO.
  
 7- SPECIFY CEILING FAN SIZES ON PLANS
 AS REQUIRED BY TABLE 6-6 CHAPTER 13 FBC
 2001 WHEN CEILING FAN CREDIT IS TAKEN
 IN THE ENERGY CALCULATIONS.
  
 8- ARCHITECTURAL PLANS NEED TO HAVE NAME
 AND SIGNATURE OF PERSON RESPONSIBLE FOR
 THE DESIGN. SEC. 104.2.1 CITY AMENDMENTS
 TO FBC 2001.
  
 9- ENGINEER TO DATE PLANS WHEN SIGNING
 AND SEALING DOCUMENTS AS REQUIRED BY
 CHAPTER 471 FL. STATUTES.
  
 10- SPECIFY WHAT ARE DOORS DO1 AND DO2.
 THEY ARE NOT INCLUDED IN THE DOOR
 SCHEDULE. SPECIFY SIZE, MATERIAL, ETC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 11- PROVIDE COMPLETE SPECS FOR FURRING
 OF WALL AT LOGGIA AND BALCONY ABOVE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 12- PRIVACY/FENCE WALL REQUIRES SEPARATE
 PERMIT AND EASEMENT RELEASE FROM
 UTILITIES.
  
 13- REVISE STAIRS RATIO TO COMPLY WITH
 SEC. 1007.3.1 EXCEPTION #1 FBC 2001.
  
 14- EGRESS WINDOWS ON BEDROOMS 1 AND 2
 NEED PROVIDE 5.7S.F. MIN. NET CLEAR
 OPENING TO COMPLY WITH SEC. 1005.4.4 FBC
 2001. PROVIDE MANUFATURER CUT SHEETS
 THAT SHOW NET CLEAR OPENING OF WINDOW
 SPECIFIED ON PLANS.
  
 15- EXTERIOR WEST ELEVATION SHOWS
 DECORATIVE SHUTTERS ATTACHED TO WINDOWS
 ON BEDROOM #1. THESE SHUTTERS ARE
 BLOCKING THE EGRESS REQ'D BY SEC.
 1005.4.4 FBC. REVISE AS REQUIRED.
  
 16- ATTIC ACCESS TO BE 20"X36" MIN.
 REVISE SIZE OF ATTIC ACCESS SHOWN ON THE
 SECOND FLOOR ROOF. SEC. 2309.6 FBC 2001.
  
 17- PROVIDE COMPLETE DETAILS & SPECS
 FOR BALCONY GUARDRAIL. SEE SEC. 1015 FBC
 2001 FOR REQUIREMENTS.
  
 18- SHEET A-3. CLARIFY HOW ARE GARAGE
 DOORS GOING TO BE OPEN IF THEY ARE
 OBSTRUCTED BY DECORATIVE SHUTTERS.
  
 19- POSTS SHOWN ON BALCONY GUARDRAIL
 SHOWN ON PLANS DON'T MATCH LOCATION AND
 NUMBER OF POSTS SHOWN ON EXTERIOR
 ELEVATION. REVISE AS REQUIRED.
  
 20- PROVIDE MANUFATURER'S SPECS THAT
 ALLOW CHIMNEY CAP AS SHOWN ON
 ELEVATIONS. AND, IF ALLOWED BY
 MANUFACTURER, THEN, PROVIDE COMPLETE
 SPECS AND CLEARANCES AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 21- CEARLY PROVIDE FASTENING SPECS FOR
 ROOF SHEATHING. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001 FOR REQUIRED TYPE
 AND SPACING OF NAILS FOR MEAN ROOF
 HEIGHT OVER 25'-0".
 ALSO, MAKE SURE THAT SPECS ON ALL
 RELATED DETAILS MATCH SPECS SHOWN ON
 SHEET S3.
  
 22- CHIMNEY HEIGHT TO COMPLY WITH SEC.
 2804.2.4. 2'-0" ABOVE 10'-0" HORIZONTAL
 DIRECTION (SEE ATTACHED SAMPLE).
 NOTE: KEEP IN MIND ZONING HEIGHT
 RESTRICTIONS TOO.
  
 23- SPECIFY FIREBLOCKING IN ALL AREAS AS
 REQUIRED BY SEC.2305.1 FBC 2001.
  
 24- SPECIFY DRAFSTOPPING LOCATION AND
 MATERIAL IN SECOND FLOOR FRAMING PLAN AS
 REQ'D BY SEC. 2305.2.2 FBC 2001.
  
 25- SECOND FLOOR FRAMING PLAN IS MISSING
 FRAMING AROUND OPENING FOR STAIRS.
  
 26- DETAIL 13/SD2 DON'T MATCH CONDITIONS
 SHOWN ON 2ND FLOOR FRAMING PLAN. REVISE
 AS REQUIRED. SEE TOP OF DETAIL AND
 SPECIFY ALL FASTENERS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 27- PROVIDE DETAIL/SECTION SHOWING HOW
 IS STRUCTURAL DOOR BUCK DETAIL ATTACHED
 TO STEEL COLUMN @ FAMILY ROOM. SPECIFY
 SIZE OF BUCK, FASTENER TYPE AND SPACING.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 28- PROVIDE COMPLETE SECTION DETAILS FOR
 CANTILEVERED BALCONIES. CLARIFY HOW IS
 THE 48" HOOK INSTALLED. SPACING , ETC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 29- HOUSE IS IN FLOOD ZONE A5. PROVIDE
 CURRENT SURVEY SHOWING NEW HOUSE LAYOUT
 AND FINISH FLOOR ELEVATIONS.
  
 30- PRODUCT APPROVALS: A)PROVIDE ONLY
 PRODUCT APPROVAL FOR TYPE OF DOORS AND
 WINDOWS TO BE INSTALLED IN THIS HOUSE.
 B) PROVIDE PRODUCT APPROVAL FROM ONE
 COMPANY ONLY. DECIDE IF USING PGT
 WINDOWS OR CONSTRUCTION GLASS
 INDUSTRIES.
 NOTE: PLANS CALL FOR PGT WINDOWS/DOORS.
 C) SPECIFY SIZE OF GARAGE DOORS. DOOR
 SCHEDULE DON'T SHOW ANY D13 & D14 DOORS.
 NOTE; PROVIDE GARAGE DOOR PRODUCT
 APPROVAL THAT MEET DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD.
 D) MAKE SURE THAT DADE COUNTY NOA
 REPORTS SUBMITTED MATCH NOA REPORTS THAT
 WERE SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL AND MAKE SURE DRAWINGS ARE
 LEGIBLE.
 E) HANSON ROOF TILE APPLIED FOR FLORIDA
 PRODUCT APPROVAL WITH SBCCI REPORT.
 PROVIDE COPY OF SAME SBCCI REPORT
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
  
 31- OWES $280.76 FOR UPDATED VALUATION
 AND RADON FEES.
  
 32- SHEET A-4: PROVIDE CORRECT NAME FOR
 ELEVATIONS. THEY ARE WEST AND NORTH
 ELEVATIONS.
  
 33- SHEET A-7: SPECIFY HOW IS LOW WALL
 AT MEZZANINE ATTACHED TO THE FLOOR. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 34- MAKE SURE SCALE NOTED ON DRAWINGS IS
 THE RIGHT SCALE. EG: REVISE SCALE ON
 SHEET A-7 AND A-8.
  
 35- SHEET S1:A) FOOTING F4 IS NOT
 DRAWWN TO SCALE IN THE FOUNDATION PLAN.
 B) COLUMN SCHEDULE HAS INFORMATION
 WRITTEN BY HAND. ENGINEER NEED TO SIGN
 THAT CHANGE OR INCLUDE INFORMATION ON
 ORIGINAL CAD DRAWING.
 C) FOOTING SCHEDULE: FOOTING F1 DOESN'T
 MATCH DETAIL 4/SD1. CLARIFY NUMBER OF
 REBARS. 3 OR 4. REVISE AS REQUIRED.
 D) FOOTING TE1: CLARIFY IF USING ONE OR
 TWO REBARS. DWG SHOWS 1. NOTE SHOWS 2.
 REVISE AS REQUIRED.
  
 36- SHEET SD1: UPDATE ALL GENERAL NOTES.
 SEE COMMENTS ON PLANS AND REFERENCE
 CURRENT STANDARD EDITIONS. SEE CHAPTERS
 19 AND 35 OF FBC 2001.
  
 37- SHEET SD2: SPECIFY SIZE OF NAILS TO
 FASTEN WINDOW/SGD BUCK. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001 AND SECTION
 1707.4.4.2 FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-09 Cont ID  
Sent By btrobaug Date 2006-03-09 Time 09:37 Rev Time 0.50
Received By btrobaug Date 2006-03-09 Time 08:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-12 Cont ID  
Sent By btrobaug Date 2006-01-12 Time 13:55 Rev Time 0.50
Received By btrobaug Date 2006-01-12 Time 11:51 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-01 Cont ID  
Sent By btrobaug Date 2005-12-01 Time 09:59 Rev Time 0.25
Received By btrobaug Date 2005-12-01 Time 09:59 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-05 Cont ID  
Sent By btrobaug Date 2005-05-05 Time 12:38 Rev Time 0.75
Received By btrobaug Date 2005-05-05 Time 07:53 Sent To M
Notes
2005-05-05 00:00:00 
  
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 CORRECT ON NEXT REVISION. SUBMIT PRIOR
 TO ROUGH ELECTRICAL INSPECTION.
  
  
 1} PANEL "A" CIRCUITS 1,3-2,4 & 5,7-6,8
 FOR THE A/C SYSTEM DO NOT CORRELATE WITH
 THE UNITS.
  
 2} MASTER CLOSET RECEPTACLES INCORRECTLY
 MARKED #20 (BATH CIRCUIT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-17 Cont ID  
Sent By btrobaug Date 2005-03-17 Time 15:14 Rev Time 0.50
Received By btrobaug Date 2005-03-16 Time 10:30 Sent To P
Notes
2005-03-17 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PER 210.11.C.3 THERE MUST BE A
 MINIMUM OF TWO SMALL APPLIANCE CIRCUITS
 IN THE KITCHEN.
  
 2} PLEASE NOTE THAT THE 20 AMP CIRCUIT
 FEEDING THE BATHROOM(S) SHALL HAVE NO
 OTHER OUTLETS. ALL THOSE CIRCUITS FEED
 SOMETHING OUTSIDE THE BATHS ON THE
 SECOND FLOOR. SEE REVIEWED SET OF PLANS.
 SEE 210.11(C)(3).
  
 3} THE LIVING ROOM IS MISMARKED ON SHEET
 E1.
  
 4} NOTE REQUIREMENTS FOR KITCHEN
 COUNTERTOP RECEPTACLE SPACING PER
 210.52(C), ALSO GFI'S PER 210.8.A.6.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-03-08 Cont ID  
Sent By adarroug Date 2006-03-08 Time 15:27 Rev Time 0.00
Received By adarroug Date 2006-03-08 Time 15:27 Sent To E
Notes
2006-03-08 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 11:36 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 11:36 Sent To B
Notes
2006-02-19 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-01-11 Cont ID  
Sent By adarroug Date 2006-01-11 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-01-11 Time 09:31 Sent To B
Notes
2006-01-11 00:00:00TO "JGOMEZ" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 14:01 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 14:01 Sent To M
Notes
2005-12-16 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 17:53 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 17:53 Sent To E
Notes
2005-11-30 00:00:00TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 20:11 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 20:11 Sent To B
Notes
2005-08-24 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-25 Cont ID  
Sent By adarroug Date 2005-07-25 Time 13:24 Rev Time 0.00
Received By adarroug Date 2005-07-25 Time 13:24 Sent To B
Notes
2005-07-25 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-28 Cont ID  
Sent By adarroug Date 2005-04-28 Time 10:59 Rev Time 0.00
Received By adarroug Date 2005-04-28 Time 10:59 Sent To E
Notes
2005-04-28 00:00:00TO "BT" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 08:27 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 08:27 Sent To I
Notes
2005-04-26 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-15 Cont ID  
Sent By adarroug Date 2005-03-15 Time 13:55 Rev Time 0.00
Received By adarroug Date 2005-03-15 Time 13:55 Sent To E
Notes
2005-03-15 00:00:00TO "SFR""E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 14:59 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 14:59 Sent To Z
Notes
2005-03-09 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-02-27 Cont ID  
Sent By tgordon Date 2006-02-27 Time 09:38 Rev Time 0.20
Received By tgordon Date 2006-02-27 Time 09:38 Sent To Z
Notes
2006-02-27 00:00:00SUBMITTAL FOR WOOD BURNING FIRE PLACE.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-01-12 Cont ID  
Sent By tgordon Date 2006-01-12 Time 13:47 Rev Time 0.20
Received By tgordon Date 2006-01-12 Time 13:47 Sent To P
Notes
2006-01-12 00:00:00RESTAMP, OLD PLANS LOST.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-12-19 Cont ID  
Sent By tgordon Date 2005-12-19 Time 09:51 Rev Time 0.30
Received By tgordon Date 2005-12-19 Time 09:51 Sent To  
Notes
2005-12-19 00:00:00*** PROVISO ***
 1)DETAILED MANUFACTURE INSTALLATION
 INSTRUCTIONS FOR ICYNENE INSULATION MUST
 BE ON JOB SITE FOR INSPECTOR.
  
 NOTE; MECH. REV. TO MECH. PLAN M1 AND
 E-CAL.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-10 Cont ID  
Sent By hmoser Date 2005-05-10 Time   Rev Time 0.00
Received By hmoser Date 2005-05-10 Time 18:54 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2005-03-31 Time   Rev Time 0.00
Received By hmoser Date 2005-03-31 Time 07:44 Sent To B
Notes
2005-03-31 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PANS.DRAIN PANI MUST HAVE A DEPTH
 OF 1 1/2 IN.
 2) NO SIZE ON RETURN AIR GRILL IN MASTER
 BEDROOM.
 3) NEED EXHAUST FAN IN IN MASTER BATH
 ROOM # 213.
 4) NEED SIZE OF DUCT FOR RETURN AIR IN
 BEDROOM #3.
 5) REFER TO SECTION 306.3. NEED 30IN
 CLEARANCE FOR SERVICE.
 6)SERVICE PLNALS FOR AIRHANDLERS MUST BE
 NO MORE THAN 6 FT. FROM ATTIC
 ACCESS.SECTION 610.1. ABC.3.5.2 FLORIDA
 ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-01-13 Cont ID  
Sent By jleech Date 2006-01-13 Time 06:59 Rev Time 0.25
Received By jleech Date 2006-01-13 Time 06:59 Sent To B
Notes
2006-01-13 00:00:00RE-STAMP

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-05-18 Cont ID  
Sent By kstevens Date 2005-05-18 Time 08:58 Rev Time 1.25
Received By kstevens Date 2005-05-17 Time 14:52 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-26 Cont ID  
Sent By kstevens Date 2005-03-26 Time 14:46 Rev Time 1.00
Received By kstevens Date 2005-03-26 Time 14:43 Sent To M
Notes
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ALL ARCHITECTURAL SHEET AND PM&E
 PLANS, SECTION 104.2.1. ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
 2) SHTS S1, S2, S3, SD1 & SD2 REQUIRE A
 CERTIFICATE OF AUTHORIZATION NUMBER IN
 THE TITLE BLOCK PER 61G15-23-002(2) AND
 FS 471.025. - ALSO THE DATE THAT THE
 SIGNATURE AND SEAL ARE AFFIXED TO THE
 PLANS SHALL BE ENTERED ON THE SEAL PER
 FAC 61G15-23.002(1) & FS 471.025.
 3) SHT P2 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE RQUIREMENTS.
 A) THE W/M IS NOT VENTED SEC 901.2.1.
 B) W/M CLEANOUT SHALL BE LOCATED 4' AFF
 FOR ACCESS. SECTION 708.10
 C) BIDET AND SHOWER ARE NOT VENTED IN
 THE MASTER BATH. SECTION 901.2.1.
 D) TUB NOT IDENTIFIED IN MASTER
 BATHROOM. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2006-03-07 Cont ID  
Sent By mmclean Date 2006-03-07 Time 10:32 Rev Time 0.00
Received By mmclean Date 2006-03-07 Time 10:32 Sent To  
Notes
2006-03-07 00:00:00REVISION - TO RETROFIT FIREPLACE.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-01-17 Cont ID  
Sent By mmclean Date 2006-01-17 Time 18:47 Rev Time 0.00
Received By mmclean Date 2006-01-17 Time 18:47 Sent To B
Notes
2006-01-17 00:00:00RE-STAMP PLANS, ORIGINALS STOLEN.
 GIVEN TO JULIO GOMEZ, BLGD PLAN REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-04-28 Cont ID  
Sent By mmclean Date 2005-04-28 Time 10:31 Rev Time 0.00
Received By mmclean Date 2005-04-27 Time 17:34 Sent To I
Notes
2005-04-28 00:00:00RECEIVED SITEPLANS (2)
2005-04-27 00:00:00NEED TO PROVIDE TWO COPY OF
 SITEPLAN/SURVEY OF PROPERTY WITH
 SETBACKS.
  
 NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE. SEPERATE
 PERMIT MUST BE PULLED FOR FENCE/WALL
 WITH CITY OF WEST PALM BEACH UTILITY
 EASMENT APPROVAL AND A SITE WALL DETAIL
 PLANS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-15 Cont ID  
Sent By mmclean Date 2005-03-15 Time 11:15 Rev Time 0.00
Received By mmclean Date 2005-03-15 Time 11:15 Sent To I
Notes
2005-03-15 00:00:00DENIED,
 1. MUST MEET THE HEIGHT REQUIREMENT OF
 33FT WITH CHIMENY. MEASURING FROM THE
 GRADE TO THE TOP OF THE CHIMENEY.
 DRAWINGS (ALL ELEVATIONS) SHOWS 34+ FT.
 NEED TO PROVIDE NEW ELEVATION DRAWINGS
 MEETING THE ZONING HEIGHT REQUIRMENTS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720