| Plan Review Stops For Permit 05030493 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-06-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-11 |
Time |
12:25 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-06-11 |
Time |
12:25 |
Sent To |
P |
|
| Notes |
| 2005-06-11 00:00:00 | TO PS DESK (TAKEN OFF OF BOARD) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-05 |
Time |
16:27 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-05-05 |
Time |
16:27 |
Sent To |
PC |
|
| Notes |
| 2005-05-05 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC. | | | | | | 2.)THIS PERMIT CANNOT BE ISSUED UNTIL | | | THE ALARM FEES ARE PAID.SEE EPHRAIM | | | GARCED, FINANCE, 561-822-1311. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-03-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-29 |
Time |
11:16 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-03-29 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2005-03-29 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED, FS713.13. | | | | | | 2.)CONTACT EPHRAIM GARCED, FINANCE, | | | 561-822-1311 IN REGARDS TO HOLDS ON THIS | | | PROPERTY.A PERMIT CANNOT BE RELEASED | | | UNTIL THE FEES HAVE BEEN RESOLVED. | | | | | | 3.)DOCUMENTS PREPARED BY AN ENGINEER | | | ARE TO BE SIGNED, SEALED AND DATED, | | | FS61G15-23.002 (ENERGY CALC). | | | | | | 4.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC. | | | | | | 5.)PROVIDE KNEE CLEARANCE BENEATH THE | | | LOUNGE SINK, FBC11-4.24.3. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-04-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-18 |
Time |
16:09 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-04-18 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-03-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-14 |
Time |
16:27 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-03-14 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2005-03-14 00:00:00 | ******** UNSAT ******** | | | | | | 1)NOTE: PLEASE INCLUDE LOAD ON EXISTING | | | GUTTER OR MAIN FOR 2ND FLR.RISER DOES | | | NOT INDICATE ANY TYP OF DISC FROM | | | BUS-DUCT RISER TO 2ND FLR ELECTRICAL RM | | | GUTTER. | | | PLEASE ALSO INCLUDE CONDUCTORS SIZES FOR | | | GUTTER FEED. | | | 215.5 | | | | | | 2)NOTE: PLAN NOTE MENTIONS LOCATION OF | | | TRANSFORMER TO BE ABOVE CEILING,PLEASE | | | SHOW ON PLANS LOCATION OF TRNASFORMER. | | | 215.5/450.13,450.21 ETC. | | | DIRECTLY ABOVE PANELS? | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-04-19 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-04-19 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-04-19 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2005-03-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-03-28 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-03-28 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2005-03-28 00:00:00 | PASSED | | | | | | 1) PLEASE BE ADVISED THAT ANY NEW DUCT | | | SMOKE DETECTOR INSTALLATIONS SHALL IN | | | ADDITION TO PROVIDING FAN SHUT DOWN, BE | | | WIRED INTO THE FIRE ALARM SYSTEM TO | | | CAUSE A GENERAL FIRE ALARM WHEN | | | ACTIVATED. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-05-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-19 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-19 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2005-05-19 00:00:00 | IN INCOMING AWAITING SPACE ON "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-04-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-11 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-11 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2005-04-11 00:00:00 | TO "COMM" BD#9 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-04-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-02 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-14 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2005-03-14 00:00:00 | TO "COMM" BD#35 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2005-04-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-04-02 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-06-11 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-06-11 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-06-11 |
Time |
13:25 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-04-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-26 |
Time |
08:23 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-04-26 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2005-04-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: | | | 3) SHT A-4 DETAIL SHOW SINK DEPTH PER | | | SECTION 11-4.24.4 AND FAUCET | | | REQUIREMENTS PER SECTION 11-4.24.7 | | | ****NEW COMMENTS**** | | | 1B) SHTS P-1 & P-3 SANT. DOES NOT MEET | | | CODE REQUIREMENTS: | | | A) DENTAL SINKS AND MIXING ROOM SINK | | | SHALL NOT DRAIN INTO THE WET-VENT FOR | | | THE TOILET ROOMS. SECTION 909.1 - SEE | | | RED LINE CORRECTIONS ON ONE SET OF PLANS | | | FOR THE FLAT LAYOUT AND THE SANT. RISER | | | DIAGRAM. | | | 2) SHT P-2 FULL OPEN VALVES REQUIRED ON | | | ALL DOWN FEED WATER LINES. SECTION | | | 606.1(4). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-03-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-03-24 |
Time |
16:39 |
Rev Time |
1.20 |
| Received By |
kstevens |
Date |
2005-03-24 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2005-03-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-1 CODE REFERENCED IS THE 1994 | | | STANDARD PLUMBING CODE. CODE ADOPTED IS | | | THE FBC-2001. PLEASE INDICATE ON PLANS. | | | SECTION 104.2.1. | | | 2) SHT A-3 DETAIL 8 SHOW CLEAR FLOOR | | | SPACE FOR W/C 11-4.16.3, FLUSH CONTROLS | | | 11-4.16.5. FOR THE LAV SHOW FAUCETS | | | 11-4.19.5. | | | 3) SHT A-4 DETAIL 4 SHOW KNEE CLEARANCE | | | 11-4.24.3, SINK DEPTH 11-4.24.4, CLEAR | | | FLOOR SPACE 11-4.24.5 WHICH SHALL BE | | | PROVIDEDIN FRONT OF A SINK TO ALLOW | | | FORWARD APPROACH WHICH SHALL EXTEND A | | | MAXIMUM OF 19" UNDERNEATH THE SINK, | | | EXPOSED PIPES & SURFACES 11-4.24.6, | | | FAUCETS 11-4.24.7. | | | 4) SUBMIT A SANITARY RISER DIAGRAM | | | SHOWING ALL PIPE SIZES, VENTS, & TRAPS. | | | SECTION 104.3.1.1. | | | 5) SUBMIT A WATER RISER DIAGRAM SHOWING | | | ALL PIPE SIZES, VALVES, WATER HAMMER | | | ARRESTORS (IF REQUIRED BY 604.9) AND | | | POINT OF CONNECTION. SECTION 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|