Plan Review Details - Permit 05030373
Plan Review Stops For Permit 05030373
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-12 Cont ID  
Sent By shill Date 2005-05-12 Time 19:58 Rev Time 0.75
Received By shill Date 2005-05-12 Time 19:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-25 Cont ID  
Sent By shill Date 2005-03-25 Time 09:41 Rev Time 1.00
Received By shill Date 2005-03-25 Time 09:34 Sent To  
Notes
2005-03-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE ACCESSIBILITY DETAILS FOR
 THE ACCESSIBLE BATHROOM STALL.IN
 ADDITION TO INFORMATION REQUESTED BY
 PLUMBING, ALSO PROVIDE GRAB BAR
 INFORMATION FOR ACCESSIBLE STALL
 FBC11-4.17.6.
  
 2.)PROVIDE INFORMATION (SIDE VIEW WITH
 DIMENSIONS, LEVERS, CLEAR FLOOR SPACE)
 FOR THE SINK IN THE BREAK ROOM
 FBC11-4.24.
  
 3.)SHOW FIREBLOCKING FOR SOFFIT WHERE
 THE HORIZONTAL MEETS VERTICAL, 9-A4,
 FBC705.3.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-10 Cont ID  
Sent By dpalmer Date 2005-03-10 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2005-03-10 Time 15:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-12 Cont ID  
Sent By mwennerg Date 2005-05-12 Time 14:49 Rev Time 0.00
Received By mwennerg Date 2005-05-12 Time 14:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-30 Cont ID  
Sent By mwennerg Date 2005-03-30 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2005-03-30 Time 10:39 Sent To  
Notes
2005-03-30 00:00:001) THE CITY OF WEST PALM BEACH REQUIRES
 THE DUCT SMOKE DETECTORS TO BE WIRED
 INTO THE FIRE ALARM SYSTEM TO CAUSE A
 GENERAL FIRE ALARM UPON ACTIVATION. NOTE
 FA0.1 #17.
  
 2) FIRE EXTINGUISHERS SIZED 2A-10B-C ARE
 REQUIRED NOT TO EXCEED A TRAVEL DISTANCE
 OF 75 FEET.
  
  
 MIKE WENNERGREN, A/CAPTAIN WPBFR(561)
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 09:00 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 09:00 Sent To  
Notes
2005-04-15 00:00:00TO "COMM" BD#55

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-04 Cont ID  
Sent By adarroug Date 2005-04-02 Time 08:45 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 09:58 Sent To  
Notes
2005-03-10 00:00:00TO "COMM" BD#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-02 Cont ID  
Sent By hmoser Date 2005-04-02 Time   Rev Time 0.00
Received By hmoser Date 2005-04-02 Time 07:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-05-23 Cont ID  
Sent By kstevens Date 2005-05-23 Time 07:48 Rev Time 1.00
Received By kstevens Date 2005-05-23 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-22 Cont ID  
Sent By kstevens Date 2005-03-22 Time 08:37 Rev Time 0.54
Received By kstevens Date 2005-03-22 Time 08:37 Sent To  
Notes
2005-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-3 ACCESSIBLE SINKS. THE
 FOLLOWING INFORMATION IS REQUIRED ON THE
 SINK DETAILS:
 A) SINK DEPTH 11-4.24.4
 B) CLEAR FLOOR SPACE 11-4.24.5 - SHALL
 BE FORWARD APPROACH, MAXIMUM 19"
 UNDERNEATH THE SINK.
 C) PROVIDE CROSS SECTIONAL VIEW OF THE
 PLAM. APRON TO SHOW COMPLIANCE WITH
 FIGURE 31 CLEARANCES.
 D) FAUCETS 11-4.24.7
 2) SHT P0.1 WATER ISOMETRICS, THE WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. (SEE PLUMBING
 NOTE #13)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]