Plan Review Details - Permit 05030289
Plan Review Stops For Permit 05030289
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 08:24 Rev Time 0.00
Received By pschmitz Date 2005-08-18 Time 14:16 Sent To  
Notes
2005-08-07 00:00:00PLANS REVIEWED AND STAMPEDJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By jwitmer Date 2005-03-21 Time 10:34 Rev Time 1.55
Received By jwitmer Date 2005-03-21 Time 10:33 Sent To  
Notes
2005-03-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030289
 ADD: 1401 FORUM WAY/ 4TH FL
 CONT:LTI DEVELOPMENT
 TEL:(561)718-6243
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) PLANS DO NOT INDICATE THE TENANT/
 CORRIDOR RATING OF WALL OR DOORS. SEE
 TABLE 705.2.1.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-10 Cont ID  
Sent By dpalmer Date 2005-03-10 Time 11:39 Rev Time 0.33
Received By dpalmer Date 2005-03-10 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-29 Cont ID  
Sent By mwennerg Date 2005-03-29 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2005-03-29 Time 15:28 Sent To  
Notes
2005-03-29 00:00:00PASSED
  
 1) PLEASE BE ADVISED THAT ALL LIFE
 SAFETY SHALL BE IN ACCORDANCE WITH NFPA
 101, 2003 EDITION EFFECTIVE JAN.1, 2005.
  
 2) THE CITY OF WEST PALM BEACH REQUIRES
 DUCT SMOKE DETECTORS TO BE WIRED INTO
 THE FIRE ALARM TO CAUSE A GENERAL FIRE
 ALARM IN ADDITION TO FAN SHUT DOWN WHEN
 ACTIVATED.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 17:08 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 17:08 Sent To P
Notes
2006-02-15 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 16:43 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 16:43 Sent To  
Notes
2005-08-05 00:00:00TO "COMM" BD#11
2005-08-03 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 15:13 Rev Time 0.00
Received By shill Date 2005-06-08 Time 15:13 Sent To  
Notes
2005-06-16 00:00:00COMM BOARD #52
2005-06-08 00:00:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 15:41 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 15:41 Sent To  
Notes
2005-03-09 00:00:00TO "COMM" BD#5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-15 Cont ID  
Sent By pkrauss Date 2005-07-15 Time 15:21 Rev Time 0.40
Received By pkrauss Date 2005-07-15 Time 15:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-28 Cont ID  
Sent By hmoser Date 2005-03-28 Time 14:01 Rev Time 0.00
Received By hmoser Date 2005-03-28 Time 13:29 Sent To  
Notes
2005-03-28 00:00:00PLSN DENIED
 1) PLAESE SHOW NEW LOCATION OF AHU,AND
 HOW EXISTING DUCT WILL BE TIED IN TO
 AHU.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-02-21 Cont ID  
Sent By mperson Date 2006-02-21 Time 13:29 Rev Time 1.25
Received By mperson Date 2006-02-17 Time 10:53 Sent To PC
Notes
2006-02-21 00:00:00REVISION: CHANGED SANITARY WASTE FROM
 GRAVITY FEED TO PUMP DUE TO TENANT BELOW
 WOULD NOT ALLOW ACCESS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-08-18 Cont ID  
Sent By pschmitz Date 2005-08-18 Time 15:03 Rev Time 0.00
Received By pschmitz Date 2005-08-18 Time 15:03 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-07-09 Cont ID  
Sent By kstevens Date 2005-07-09 Time 09:31 Rev Time 0.30
Received By kstevens Date 2005-07-09 Time 09:31 Sent To  
Notes
2005-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA STATUTES
  
 COMMENTS FROM PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED.
 1) SHT A-2 DETAIL A. THE FOLLOWING
 INFORMATION REQUIRED FOR THE ACCESSIBLE
 SINK IS NOT SHOWN ON THE DETAIL OR FLOOR
 PLAN:
 A) KNEE CLEARANCE 11-4.24.3
 B) SINK DEPTH 11-4.24.4
 C) CLEAR FLOOR SPACE 11-4.24.5 -
 FORWARD APPROACH REQUIRED, MAXIMUM 19"
 UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED PER THE BLDG. OFFICIAL, AS
 THEY SHALL NOT BE IN THE CLEAR FLOOR
 SPACE.
 D) FAUCETS 11-4.24.7
 2) A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE IF THERE ARE HI/LOW
 DRINKING FOUNTAINS EXISTING, AND THE
 LOCATION OF DRINKING FOUNTAINS. SECTION
 104.2.1.
 3) SHT P0.1 PLUMBING ISOMETRICS. WATER
 ISOMETRIC, WATER HAMMER ARRESTOR SHALL
 BE LOCATED NEAR THE FIXTURE, IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201. (SEE NOTE #13)
 ****************NEW COMMENTS************
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS553.80(2)B)
 2B. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By kstevens Date 2005-03-21 Time 17:15 Rev Time 0.55
Received By kstevens Date 2005-03-21 Time 17:12 Sent To  
Notes
2005-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 DETAIL A. THE FOLLOWING
 INFORMATION REQUIRED FOR THE ACCESSIBLE
 SINK IS NOT SHOWN ON THE DETAIL OR FLOOR
 PLAN:
 A) KNEE CLEARANCE 11-4.24.3
 B) SINK DEPTH 11-4.24.4
 C) CLEAR FLOOR SPACE 11-4.24.5 -
 FORWARD APPROACH REQUIRED, MAXIMUM 19"
 UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED PER THE BLDG. OFFICIAL, AS
 THEY SHALL NOT BE IN THE CLEAR FLOOR
 SPACE.
 D) FAUCETS 11-4.24.7
 2) A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE IF THERE ARE HI/LOW
 DRINKING FOUNTAINS EXISTING, AND THE
 LOCATION OF DRINKING FOUNTAINS. SECTION
 104.2.1.
 3) SHT P0.1 PLUMBING ISOMETRICS. WATER
 ISOMETRIC, WATER HAMMER ARRESTOR SHALL
 BE LOCATED NEAR THE FIXTURE, IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201. (SEE NOTE #13)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]