Plan Review Details - Permit 05021482
Plan Review Stops For Permit 05021482
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-22 Cont ID  
Sent By shill Date 2005-04-22 Time 11:16 Rev Time 1.00
Received By shill Date 2005-04-22 Time 11:12 Sent To PC
Notes
2005-04-22 00:00:00PROVISO - SUBMIT CORRECTED ENERGY CALC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-17 Cont ID  
Sent By alange Date 2005-03-17 Time 11:07 Rev Time 0.50
Received By alange Date 2005-03-17 Time 10:52 Sent To  
Notes
2005-03-17 00:00:00DENIED
  
 1. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.SHOW A FRAMING DETAIL AND INCLUDE
 STRAPS USED.
  
 3.SPECIFY TYPE OF SIDING USED.
  
 4.FBC 2304.2.5 CLEARANCE BETWEEN WOOD
 SIDING AND EARTH ON THE EXTERIOR OF A
 BUILDING SHALL BE NOT LESS THAN 6"
 EXCEPT WHERE SIDING, SHEATHING AND WALL
 FRAMING ARE OF APPROVED
 PRESERVATIVE-TREATED WOOD OR APPROVED
 NATURALLY DURABLE WOOD.
 SHOW ON PLANS HOW THIS WILL BE COMPLIED
 WITH.
  
 5.SUBMIT 2 SETS OF PRODUCT APPROVALS.
 ALL PRODUCT APPROVALS SUBMITTED REQUIRE
 THE FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SUBMIT 2 COPIES OF ENERGY CALCS PER
 CHAPTER 13 OF THE FBC.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-04-14 Cont ID  
Sent By dpalmer Date 2005-04-14 Time 17:49 Rev Time 0.30
Received By dpalmer Date 2005-04-14 Time 17:49 Sent To P
Notes
2005-04-14 00:00:00REDLINED A MEANS OF DISC AT DETACHED
 BLDG. 225.31,-36

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-15 Cont ID  
Sent By dpalmer Date 2005-03-15 Time 10:44 Rev Time 0.50
Received By dpalmer Date 2005-03-15 Time 10:44 Sent To P
Notes
2005-03-15 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED IN TITLE BLOCK.
 PLEASE SEE THIS IS UNDER FAC 61G1-16.004
 AND FS 481.219
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENTS IS
 MADE BY OTHER REVIEWER(S).
 PLEASE SEE ONE COPY RETAINED.
  
 2)NOTE: PLEASE VERIFY SIZE OF EXISTING
 METERCAN. SERVICE IS SHOWN AS EXISTING
 METER NOW FEEDING A NEW 125A MAIN.
 PLEASE VERIFY/SHOW SIZES OF EXISTING
 SEC'S PER 310.15B6MIN. FOR 250A SERVICE.
 PLEASE ALSO SEE 250.66 FOR MIN SIZE OF
 GROUNDING ELECTRODE FOR 250A SERVICE.
 #2.
  
 3)NOTE: PLEASE SHOW GROUNDING AT
 DETACHED BLDG PER 250.32.
 CWP/GRND ROD. ETC
  
 4)NOTE: PLEASE SEE RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM METER
 TO NEW MAIN. PLEASE SEE 250.6, 250.24,
 AN EQUIPMENT GROUNDING CONDUCTOR SHALL
 NOT BE INSTALLED UNTIL AFTER THE FIRST
 MEANS OF DISCONNECT.THE GROUNDING OF
 ELECTRICAL SYSTEMS, CIRCUIT CONDUCTORS,
 SURGE ARRESTERS, AND CONDUCTIVE
 NON?CURRENT-CARRYING MATERIALS AND
 EQUIPMENT SHALL BE INSTALLED AND
 ARRANGED IN A MANNER THAT WILL PREVENT
 OBJECTIONABLE CURRENT OVER THE GROUNDING
 CONDUCTORS OR GROUNDING PATHS.
  
 5)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCUALTIONS FOR EXISTING
 DWELLINGS/SERVICES.
  
 6)NOTE: PLEASE SEE 210.12 2002 NEC FOR
 REQUIRED ARC FAULT IN CABANNA . THIS IS
 CONSIDERED AN ADAPTABLE SLEEPING RM.
  
 7)NOTE: PLEASE SEE SD TO BE A MIN OF 3'
 FROM BATH ROOM DOOR.
 NFPA-72 8-1.4.2
  
 8)NOTE: PLEASE SEE RECEPT IN BATH RM TO
 BE GFI. 210.8
  
 9)NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL/ FIXTURE PER 210.70, LS
 101 5-8
  
 PLEASE SEE ONE SET OF PLANS HAVE BEEN
 REDLINED AT AREAS OF NOTES.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-11 Cont ID  
Sent By adarroug Date 2005-04-11 Time 15:23 Rev Time 0.00
Received By adarroug Date 2005-04-11 Time 15:23 Sent To E
Notes
2005-04-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-11 Cont ID  
Sent By adarroug Date 2005-03-11 Time 10:06 Rev Time 0.00
Received By adarroug Date 2005-03-11 Time 10:06 Sent To E
Notes
2005-03-11 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 10:46 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 10:47 Sent To Z
Notes
2005-02-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-04-20 Cont ID  
Sent By pkrauss Date 2005-04-20 Time 10:01 Rev Time 0.20
Received By pkrauss Date 2005-04-20 Time 09:59 Sent To B
Notes
2005-04-20 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH BUILDING PERMIT
 APPLICAITON.PLEASE PROVIDE PLANS AND
 EQUIPMENT SCHEDULE WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-17 Cont ID  
Sent By pkrauss Date 2005-03-17 Time 07:23 Rev Time 0.35
Received By pkrauss Date 2005-03-17 Time 07:15 Sent To B
Notes
2005-03-17 00:00:00DENIED:
 1.PROVIDE EQUIPMENT SCHEDULE FOR THE
 AHU & CU INDICATED ON PLAN SHEET P/E.
  
 2.PROVIDE ENERGY CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13
 SUB-SECTION 600.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-04-21 Cont ID  
Sent By kstevens Date 2005-04-21 Time 09:24 Rev Time 0.33
Received By kstevens Date 2005-04-21 Time 09:24 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-16 Cont ID  
Sent By gsalfeld Date 2005-03-16 Time 11:15 Rev Time 0.50
Received By gsalfeld Date 2005-03-16 Time 11:15 Sent To M
Notes
2005-03-16 00:00:003/16/05 FBC 2001104.2.1 DWG.
 REQUIREMENTS.
 1-TWO OR MORE COPIES OF SPECIFICATIONS
 AND OF DRAWINGS SHALL ACCOMPANY THE
 APPLICATION FOR PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-10 Cont ID  
Sent By mmclean Date 2005-03-10 Time 10:56 Rev Time 0.00
Received By mmclean Date 2005-03-03 Time 11:25 Sent To I
Notes
2005-03-10 00:00:00HISTORIC REVIEWED AND APPROVE N/C 3/9/05
2005-03-03 00:00:00SENT TO HISTORIC FOR REVIW & STAMPS.