| 2005-03-15 00:00:00 | ******** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION REQUIRED IN TITLE BLOCK. |
| | PLEASE SEE THIS IS UNDER FAC 61G1-16.004 |
| | AND FS 481.219 |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENTS IS |
| | MADE BY OTHER REVIEWER(S). |
| | PLEASE SEE ONE COPY RETAINED. |
| | |
| | 2)NOTE: PLEASE VERIFY SIZE OF EXISTING |
| | METERCAN. SERVICE IS SHOWN AS EXISTING |
| | METER NOW FEEDING A NEW 125A MAIN. |
| | PLEASE VERIFY/SHOW SIZES OF EXISTING |
| | SEC'S PER 310.15B6MIN. FOR 250A SERVICE. |
| | PLEASE ALSO SEE 250.66 FOR MIN SIZE OF |
| | GROUNDING ELECTRODE FOR 250A SERVICE. |
| | #2. |
| | |
| | 3)NOTE: PLEASE SHOW GROUNDING AT |
| | DETACHED BLDG PER 250.32. |
| | CWP/GRND ROD. ETC |
| | |
| | 4)NOTE: PLEASE SEE RISER SHOWS AN |
| | EQUIPMENT GROUNDING CONDUCTOR FROM METER |
| | TO NEW MAIN. PLEASE SEE 250.6, 250.24, |
| | AN EQUIPMENT GROUNDING CONDUCTOR SHALL |
| | NOT BE INSTALLED UNTIL AFTER THE FIRST |
| | MEANS OF DISCONNECT.THE GROUNDING OF |
| | ELECTRICAL SYSTEMS, CIRCUIT CONDUCTORS, |
| | SURGE ARRESTERS, AND CONDUCTIVE |
| | NON?CURRENT-CARRYING MATERIALS AND |
| | EQUIPMENT SHALL BE INSTALLED AND |
| | ARRANGED IN A MANNER THAT WILL PREVENT |
| | OBJECTIONABLE CURRENT OVER THE GROUNDING |
| | CONDUCTORS OR GROUNDING PATHS. |
| | |
| | 5)NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCUALTIONS FOR EXISTING |
| | DWELLINGS/SERVICES. |
| | |
| | 6)NOTE: PLEASE SEE 210.12 2002 NEC FOR |
| | REQUIRED ARC FAULT IN CABANNA . THIS IS |
| | CONSIDERED AN ADAPTABLE SLEEPING RM. |
| | |
| | 7)NOTE: PLEASE SEE SD TO BE A MIN OF 3' |
| | FROM BATH ROOM DOOR. |
| | NFPA-72 8-1.4.2 |
| | |
| | 8)NOTE: PLEASE SEE RECEPT IN BATH RM TO |
| | BE GFI. 210.8 |
| | |
| | 9)NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING CONTROL/ FIXTURE PER 210.70, LS |
| | 101 5-8 |
| | |
| | PLEASE SEE ONE SET OF PLANS HAVE BEEN |
| | REDLINED AT AREAS OF NOTES. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |