Plan Review Details - Permit 05021387
Plan Review Stops For Permit 05021387
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-08-25 Cont ID  
Sent By lursu Date 2006-08-25 Time 11:06 Rev Time 0.00
Received By lursu Date 2006-08-25 Time 11:06 Sent To  
Notes
2006-08-25 00:00:00THE LOCATION OF THE STRUCTURE ON THE
 SITE PLANS CORRESPONDS TO THIS ADDRESS:
 641 7TH ST ( IN THE RCORDS OF UTILITY
 BILLING ) THE SECOND FLOOR USED FOR
 RESIDENTIAL IS KNOWN AS 641 7TH ST AND
 THE FIRST FLOOR IS 800 N SAPODILLA
 AVE.NEED CLARIFICATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-09-27 Cont ID  
Sent By shill Date 2006-09-27 Time 13:08 Rev Time 0.00
Received By shill Date 2006-09-26 Time 15:43 Sent To  
Notes
2006-09-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 THE FOLLOWING COMMENTS ARE FROM THE
 PREVIOUS LIST, NOT PROPERLY ADDRESSED.
 NUMBERING HAS REMAINED THE SAME FOR
 CONSISTENCY.NOTE THAT SOME OF THE NEW
 COMMENTS WERE PREVIOUSLY ADDRESSED BUT
 ARE NOT ON THIS SET OF PLANS; OLD SHEETS
 NOT SUBMITTED:
  
 1.)FROM PREVIOUS LISTS:
  
 THE EXTERIOR STAIR IS TO COMPLY
 WITH FBC1006.2.4.PROVIDE ELEVATIONS
 AND INDICATE, TO SCALE, ALL OPENINGS
 WHICH REQUIRE FIRE RESISTANCE.SHOW ONE
 HOUR RATING REQUIRED ON THE PLAN.
  
 ONE HOUR RATING REQUIREMENT NOT SHOWN.
 YOUR RESPONSE LETTER THAT THE WALL IS
 BLOCK AND IS 1 HOUR IS ACKNOWLEDGED BUT
 IS TO BE SHOWN ON THE PLAN (1 HOUR
 REQUIRED).THE OPENINGS ON THE SECOND
 FLOOR WHICH ARE REQUIRED TO BE PROTECTED
 ARE NOTED BUT NOTHING IS SHOWN FOR THE
 FIRST FLOOR.PROVIDE ELEVATIONS AS
 REQUESTED IN EACH PLAN REVIEW AND NOTE
 THE 1 HOUR REQUIREMENT ON THE PLAN.
  
 2.)ADDRESSED
  
 3.)DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G15-23.002 (ENERGY CALCS).
  
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALCS, FBC*103.1.
  
 4.)SEE PREVIOUS LISTS IN REGARDS TO
 HURRICANE SHUTTERS.THERE IS A
 STATEMENT ON THE PLAN THAT ALL SHUTTERS
 WILL BE ACCORDION, BUT STORM PANEL
 PRODUCT APPROVALS WERE SUBMITTED AND A
 STORAGE AREA SHOWN FOR THE SHUTTERS.
 SEE THE ATTACHED WIND-BORNE DEBRIS
 IMPACT PROTECTION STANDARD, ITEMS 13 AND
 14.SUBMIT AN INSTALLATION PLAN AS
 REQUIRED.THE PLAN MAY BE SUBMITTED
 SEPARATELY FROM THE PERMIT APPLICATION.
 A PRELIMINARY REVIEW CAN BE DONE BY
 EMAIL; SUBMIT TO [email protected]
 PRELIMINARY REVIEW, THE PLAN IS
 FORWARDED TO THE BUILDING OFFICIAL.THE
 PLAN MUST BE APPROVED PRIOR TO PERMIT
 ISSUANCE.CONTINUED FAILURE TO ADDRESS
 THIS COMMENT WILL RESULT IN ADDITIONAL
 PERMIT DELAYS.
  
 5.)COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE (SHUTTERS), OR PROVIDE ALL
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.
  
 6.)PRODUCT APPROVALS FOR JELD-WEN
 DOORS WERE SUBMITTED.THERE ARE THREE
 DIFFERENT PRODUCT APPROVALS IN THE
 BROCHURE.SUBMIT ONLY THE DOOR YOU WILL
 INSTALL.
  
 7.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED IN ADDITION TO NOAS
 SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 THIS WAS ADDRESSED WITH FBC2001 PRODUCT
 APPROVALS.NOTE THAT A NEW APPLICATION
 WILL BE UNDER FBC2004, PROVIDE CURRENT
 (2004) PRODUCT APPROVALS.
  
 FBC2004 REQUIRES THAT PRODUCT APPROVALS
 BE REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 8.)SEE PREVIOUS LIST, ITEM #6.
 PROVIDE FIRE RATING INFORMATION FOR THE
 PRODUCT YOU ARE INSTALLING.THE PRODUCT
 APPROVALS FOR THE DOORS DO NOT INDICATE
 THAT THEY HAVE A FIRE RATING.
  
 9.)SEE PREVIOUS LIST, ITEM #6.THE
 ENTRY DOORS ARE TO BE APPROVED BY
 HISTORIC PRIOR TO RESUBMITTAL AS PER
 THEIR LETTER DATED 11/20/03, WHICH IS NO
 LONGER IN THE PACKAGE.
  
 HAVE HISTORIC STAMP THE PRODUCT
 APPROVAL.THEY HAVE STATED THAT THEY
 DID NOT DO A REVIEW, ONLY THAT THEY
 STAMPED THE RESUBMITTAL SHEET.
  
 10.)YOU HAVE DONE A CHANGE TO THE
 EXTERIOR OF THE BUILDING (ADDED
 ACCORDION SHUTTERS).THIS REQUIRES
 APPROVAL FROM HISTORIC PRESERVATION
 DEPARTMENT.
  
 11.)PRODUCT APPROVAL FOR TRACO SINGLE
 HUNG EGRESS WINDOW WAS SUBMITTED.THIS
 IS ACCEPTABLE FOR THE WINDOWS WHICH ARE
 NOT REQUIRED TO BE FIRE RATED; HOWEVER,
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72.PLEASE PROVIDE.
 WWW.FLORIDABUILDING.ORG
  
 12.)PROVIDE PRODUCT APPROVALS AND FIRE
 RATING
 INFORMATION FOR THE FIRE RATED WINDOWS.
  
 13.-17.)ADDRESSED.
  
 18.)REVISE THE PERMIT APPLICATION
 DESCRIPTION OF WORK.THIS IS NOT ONLY
 AN INTERIOR REMODEL.
  
 19.)SEE ELECTRIC REVIEW #2 AND THE
 ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE HAS BEEN CHARGED AS REQUIRED
 BY FLORIDA STATUTE.A RESUB FEE WILL
 NOT BE CHARGED.A BILL IS ATTACHED AND
 MUST BE PAID PRIOR TO RESUBMITTAL.THIS
 AMOUNT WILL CHANGE WHEN CORRECT
 VALUATION IS DETERMINED.
  
 NEW COMMENTS:
  
 20.)OCCUPANCY SEPARATION REQUIRED.
 SPECIFY THE HORIZONTAL SEPARATION
 BETWEEN THE BUSINESS AND RESIDENTIAL
 OCCUPANCIES, FBC TABLE 704.1.
  
 21.)THIS PERMIT APPLICATION HAS
 EXPIRED, FBC*104.1.6, OVER SIX MONTHS
 WITH NO ACTIVITY (12/22/05 TO 8/7/06).
 SUBMIT A NEW PERMIT APPLICATION WITH NEW
 PLANS.NOTE THAT GOVERNING CODE HAS
 CHANGED EFFECTIVE OCTOBER 1, 2006
 (FBC2004).
  
 22.)THE ROOF AND ROOF FRAMING PERMIT
 04100264, 04050602 ARE ALSO EXPIRED.
 APPLY FOR NEW PERMITS.A LICENSED
 ROOFING CONTRACTOR WILL BE REQUIRED FOR
 THE ROOF PERMIT; A CBC CANNOT DO ROOFING
 WORK ON A MODIFIED SYSTEM (NAIL-ON
 SYSTEMS ONLY).INCLUDE ALL WORK
 REQUIRED TO COMPLY WITH THE CBAA ORDER
 WHEN RESUBMITTING (2ND FLOOR FRAMING,
 ROOF FRAMING, ROOF).
  
 23.)DECLARE AN OCCUPANCY
 SUBCLASSIFICATION, FBC311.
  
 24.)THE HANDRAIL IS TO BE 34 TO 38IN,
 FBC1007.5 UNLESS A PART OF THE
 GUARDRAIL.
  
 25.)HANDRAIL EXTENSIONS REQUIRED AT
 TOP AND BOTTOM OF THE STAIR, PROVIDE
 DETAILS AND SHOW ON THE FLOOR PLAN,
 FBC1007.5.5.
  
 26.)HANDRAILS AND GUARDRAILS TO COMPLY
 WITH FBC1608.2.1.1 AND FBC1608.2.2
 RESPECTIVELY.PLEASE STATE DESIGN
 CRITERIA ON THE PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-12-22 Cont ID  
Sent By shill Date 2005-12-22 Time 10:57 Rev Time 3.00
Received By shill Date 2005-12-21 Time 17:59 Sent To  
Notes
2005-12-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE PREVIOUS LIST, ITEM #5.NOTE
 THE 1 HOUR FIRE RATING REQUIREMENT FOR
 THE WALL AT THE EXTERIOR STAIR.
  
 2.)SEE PREVIOUS LIST, ITEM #7,
 FBC1006.2.4.NOTE THE FOLLOWING:
  
 A. THE DOOR IS TO HAVE A CLOSER; "FIXED
 OR SELF-CLOSING OPENING PROTECTIVES."
  
 B. THE PLANS SPECIFY 2 HOUR FIRE RATED
 ENTRY DOORS.THE MINIMUM CODE
 REQUIREMENT IS A 45 MINUTE ASSEMBLY.IT
 IS ACCEPTABLE TO EXCEED CODE; HOWEVER, I
 AM BRINGING THIS TO YOUR ATTENTION.
  
 C. THE WINDOWS SPECIFIED ON THE PLAN ARE
 SINGLE HUNG.THIS DOES NOT COMPLY WITH
 THE REQUIREMENT "SHALL BE EQUIPPED WITH
 FIXED 3/4 HOUR ASSEMBLIES."
  
 D. SPECIFY FIRE RATING REQUIREMENT FOR
 THE WINDOWS.
  
 3.)THE ENERGY CALCS WHICH WERE
 PREVIOUSLY SUBMITTED ARE NO LONGER IN
 THE PACKAGE.
  
 4.)SEE PREVIOUS LIST, ITEM #10.
 POLICY IN REGARDS TO MISSILE IMPACT
 PROTECTION IS ATTACHED.THE PLAN NOW
 SPECIFIES ACCORDION SHUTTERS, BUT
 PRODUCT APPROVALS FOR GALVANIZED STEEL
 SHUTTERS WERE SUBMITTED.REMOVABLE
 SHUTTERS NOT ALLOWED FOR THE SECOND
 FLOOR, AND REMOVABLE SHUTTERS MUST BE
 APPROVED BY THE BUILDING OFFICIAL FOR
 THE FIRST FLOOR.ADDRESS.
  
 5.)COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE (SHUTTERS), OR PROVIDE ALL
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.
  
 6.)PRODUCT APPROVALS FOR JELD-WEN
 DOORS WERE SUBMITTED.THERE ARE THREE
 DIFFERENT PRODUCT APPROVALS IN THE
 BROCHURE.SUBMIT ONLY THE DOOR YOU WILL
 INSTALL.
  
 7.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED IN ADDITION TO NOAS
 SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 8.)SEE PREVIOUS LIST, ITEM #6.
 PROVIDE FIRE RATING INFORMATION FOR THE
 PRODUCT YOU ARE INSTALLING.THE PRODUCT
 APPROVALS FOR THE DOORS DO NOT INDICATE
 THAT THEY HAVE A FIRE RATING.
  
 9.)SEE PREVIOUS LIST, ITEM #6.THE
 ENTRY DOORS ARE TO BE APPROVED BY
 HISTORIC PRIOR TO RESUBMITTAL AS PER
 THEIR LETTER DATED 11/20/03, WHICH IS NO
 LONGER IN THE PACKAGE.
  
 10.)YOU HAVE DONE A CHANGE TO THE
 EXTERIOR OF THE BUILDING (ADDED
 ACCORDION SHUTTERS).THIS REQUIRES
 APPROVAL FROM HISTORIC PRESERVATION
 DEPARTMENT.
  
 11.)PRODUCT APPROVAL FOR TRACO SINGLE
 HUNG EGRESS WINDOW WAS SUBMITTED.THIS
 IS ACCEPTABLE FOR THE WINDOWS WHICH ARE
 NOT REQUIRED TO BE FIRE RATED; HOWEVER,
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72.PLEASE PROVIDE.
 WWW.FLORIDABUILDING.ORG
  
 12.)PRODUCT APPROVALS AND FIRE RATING
 INFORMATION FOR THE FIRE RATED WINDOWS.
  
 13.)SEE FBC905.2.2 IN REGARDS TO SMOKE
 DETECTOR REQUIREMENTS.
  
 14.)SEE PREVIOUS LIST, ITEM #20, IN
 REGARDS TO VALUATION.
  
 15.)SEE PREVIOUS TWO LISTS, ITEM #21,
 IN REGARDS TO ROOF DRAINS AND OVERFLOW
 DRAINS.SCUPPERS ARE SHOWN BUT NO
 INFORMATION PROVIDED IN REGARDS TO
 PRIMARY AND SECONDARY DRAINAGE SYSTEM.
 SEE FBC1503.4.
  
 16.)PROVIDE A DETAIL FOR THE PRIMARY
 AND SECONDARY SCUPPERS, FBC1503.4,
 FBC1503.4.2.
  
 17.)PROVIDE THE PARAPET WALL HEIGHT AS
 THIS INFORMATION IS REQUIRED TO
 DETERMINE DRAINAGE REQUIREMENTS.
  
 18.)REVISE THE PERMIT APPLICATION
 DESCRIPTION OF WORK.THIS IS NOT ONLY
 AN INTERIOR REMODEL.
  
 19.)SEE ELECTRIC REVIEW #2 AND THE
 ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE HAS BEEN CHARGED AS REQUIRED
 BY FLORIDA STATUTE.A RESUB FEE WILL
 NOT BE CHARGED.A BILL IS ATTACHED AND
 MUST BE PAID PRIOR TO RESUBMITTAL.THIS
 AMOUNT WILL CHANGE WHEN CORRECT
 VALUATION IS DETERMINED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-11 Cont ID  
Sent By shill Date 2005-06-11 Time 13:09 Rev Time 2.00
Received By shill Date 2005-06-11 Time 13:09 Sent To  
Notes
2005-06-11 00:00:00PERMIT #05021387
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)HOW WILL THE OCCUPANCY SEPARATION
 BETWEEN THE FIRST AND SECOND FLOOR BE
 MAINTAINED AT THE BEARING WALL ON THE
 FIRST FLOOR?
  
 THE FOLLOWING COMMENTS REMAIN FROM THE
 PREVIOUS REVIEW.YOUR RESPONSE LETTER
 STATING THAT THESE ITEMS WILL BE
 ADDRESSED UNDER A SEPARATE PERMIT IS
 ACKNOWLEDGED.THE BOARD ORDER IS TO
 BRING THE ENTIRE BUILDING UP TO CODE
 COMPLIANCE.THIS CANNOT BE DONE UNDER
 SEPARATE PERMITS.IF THIS IS NOT
 ADDRESSED, THE DEMOLITION ORDER TO
 DEMOLISH THE BUILDING WILL BE REINSTATED
 AS PER BUILDING OFFICIAL.
  
 3.)THE APPLICATION 03111034 INCLUDING
 ALL WORK TO BE PERFORMED TO BRING THE
 BUILDING UP TO CODE (FBC3401.7.2.6) HAS
 EXPIRED.THIS APPLICATION IS TO INCLUDE
 ALL WORK REQUIRED BY THE BOARD ORDER AND
 FBC3401.7.2.6.AS THE EXTERIOR IS NOT
 CURRENTLY CODE COMPLIANT, THIS CANNOT BE
 "INTERIOR RENOVATION ONLY" AS STATED ON
 THE APPLICATION AND PLANS.
  
 4.)PROVIDE A FLOOR PLAN FOR THE FIRST
 FLOOR - ***NOTE***TO BE DONE AT A FUTURE
 DATE AS A TENANT BUILDOUT 8/8/05***
  
 5.)THE EXTERIOR STAIR IS TO COMPLY
 WITH FBC1006.2.4.PROVIDE ELEVATIONS
 AND INDICATE, TO SCALE, ALL OPENINGS
 WHICH REQUIRE FIRE RESISTANCE.SHOW ONE
 HOUR RATING REQUIRED ON THE PLAN.
  
 6.)PROVIDE PRODUCT APPROVALS AND FIRE
 RATING INFORMATION FOR OPENINGS AFFECTED
 BY COMMENT #10.EXTERIOR DOORS ARE TO
 BE APPROVED BY HISTORIC PRESERVATION
 DEPARTMENT AS PER LETTER DATED 11/20/03.
  
 7.)THE ENTRY DOOR IS REQUIRED TO HAVE
 A FIRE RATING AND A CLOSER, 1006.2.4.
  
 8.) PROVIDE A SURVEY FOR THIS PROPERTY.
 CHECK FOR FBC TABLE 600 COMPLIANCE
 BEFORE RESUBMITTAL.
  
 9.) BEDROOMS ARE REQUIRED TO HAVE
 EMERGENCY EGRESS, FBC1005.4.SHOW
 COMPLIANCE ON THE PLAN (WINDOW TYPE,
 SIZE AND SILL HEIGHT).
  
 10.) SEE ATTCHED IMPLEMENTATIN STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13.IMPACT GLASS IS REQUIRED FOR
 THE SECOND FLOOR.NON IMPACT WITH
 SHUTTERS CAN BE APPROVED BY THE BUILDING
 OFFICIAL.A PLAN MUST BE SUBMITTED FOR
 REVIEW.
  
 11.) SHOW TREAD AND RISER DIMENSIONS FOR
 THE EXTERIOR EGRESS STAIR, FBC1007.3.
 SHOW STAIR WIDTH.
  
 12.) SHOW VERTICAL RISE FOR THE EXTERIOR
 STAIR, FBC1007.4.
  
 18.) PROVIDE DETAILS FOR THE HANDRAIL
 AND GUARDRAIL, FBC1015, 1007.5.PROVIDE
 DESIGN CRITERIA FOR BOTH THE GUARDRAIL
 AND HANDRAIL FBC1608.2.DO NOT STATE
 CODE SECTION BY NUMBER; SPECIFY DESIGN
 CRITERIA.THIS COMMENT APPLIES TO BOTH
 THE HANDRAIL/GUARDRAIL AT THE STAIRS AND
 THE GUARDRAIL AT THE BALCONY.
  
 19.) STAIRWAYS SHALL HAVE HANDRAILS ON
 EACH SIDE, FBC1007.5.2.
  
 20.) ADJUST THE VALUE OF THE SCOPE OF
 WORK TO INCLUDE ALL WORK REQUIRED.
  
 21.) SHOW COMPLIANCE WITH FBC1503.4,
 ROOF DRAINS AND FBC1503.4.2, OVERFLOW
 DRAINS.YOUR STATEMENT THAT THE WORK
 HAS BEEN COMPLETED IS ACKNOWLEDGED, BUT
 PLEASE SHOW CODE COMPLIANCE AS THIS WORK
 HAS NOT BEEN PERMITTED.
  
 22.) THE PREVIOUS APPLICATION INCLUDED
 CONCRETE RESTORATION WORK.PROVIDE A
 SPECIFICATION AND LOCATION OF REPAIR
 WORK, OR INDICATE THAT THIS WORK IS NO
 LONGER NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-10 Cont ID  
Sent By shill Date 2005-03-10 Time 12:16 Rev Time 3.00
Received By shill Date 2005-03-09 Time 17:39 Sent To  
Notes
2005-03-10 00:00:00PERMIT #05021387
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)THE APPLICATION 03111034 INCLUDING
 ALL WORK TO BE PERFORMED TO BRING THE
 BUILDING UP TO CODE (FBC3401.7.2.6) HAS
 EXPIRED.THIS APPLICATION IS TO INCLUDE
 ALL WORK REQUIRED BY THE BOARD ORDER AND
 FBC3401.7.2.6.AS THE EXTERIOR IS NOT
 CURRENTLY CODE COMPLIANT, THIS CANNOT BE
 ?INTERIOR RENOVATION ONLY? AS STATED ON
 THE APPLICATION AND PLANS.
  
 3.)THE PERMIT ISSUED FOR THE ROOF
 FRAMING (04050602) HAS EXPIRED.APPLY
 FOR A NEW PERMIT.
  
 4.)NO INSPECTIONS HAVE BEEN DONE ON
 THE ROOF PERMIT ISSUED (04100264).THE
 WORK HAS BEEN COMPLETED AS PER
 CONVERSATION WITH THE CONTRACTOR.
 SCHEDULE INSPECTIONS AS REQUIRED BY
 FBC105(4).THIS PERMIT WILL EXPIRE
 APPROXIMATELY APRIL 7, 2005.
  
 5.)INFORMATIONAL ONLY; THERE IS ALSO
 AN OPEN WINDOW PERMIT ON THIS JOB,
 04070723.
  
 6.)SHEET 2 OF 5 SHOWS A CHANGE TO THE
 EXTERIOR (REMOVAL AND REPLACEMENT OF
 WINDOWS).APPROVAL REQUIRED FROM THE
 HISTORIC PRESERVATION DEPARTMENT.
  
 7.)DECLARE AN OCCUPANCY FOR THE FIRST
 FLOOR AND SECOND FLOOR, FBC CHAPTER 3.
  
 8.)SHOW REQUIRED FIRE SEPARATION FBC
 TABLE 704.1 BETWEEN THE FIRST AND SECOND
 FLOOR, EITHER AS A RATED ASSEMBLY OR
 CALCULATED FIRE RESISTANCE FBC709.
 PROVIDE DETAILS FOR PENETRATIONS THROUGH
 THE FIRE RATED ASSEMBLY FBC705.6.
  
 9.)PROVIDE A FLOOR PLAN FOR THE FIRST
 FLOOR.
  
 10.)THE EXTERIOR STAIR IS TO COMPLY
 WITH FBC1006.2.4.PROVIDE ELEVATIONS
 AND INDICATE, TO SCALE, ALL OPENINGS
 WHICH REQUIRE FIRE RESISTANCE.SHOW ONE
 HOUR RATING REQUIRED ON THE PLAN.
  
 11.)PROVIDE PRODUCT APPROVALS AND FIRE
 RATING INFORMATION FOR OPENINGS AFFECTED
 BY COMMENT #10.EXTERIOR DOORS ARE TO
 BE APPROVED BY HISTORIC PRESERVATION
 DEPARTMENT AS PER LETTER DATED 11/20/03.
  
 12.)THE ENTRY DOOR IS REQUIRED TO HAVE
 A FIRE RATING AND A CLOSER, 1006.2.4.
  
 13.) PROVIDE A SURVEY FOR THIS PROPERTY.
 CHECK FOR FBC TABLE 600 COMPLIANCE
 BEFORE RESUBMITTAL.
  
 14.) BEDROOMS ARE REQUIRED TO HAVE
 EMERGENCY EGRESS, FBC1005.4.SHOW
 COMPLIANCE ON THE PLAN (WINDOW TYPE,
 SIZE AND SILL HEIGHT).
  
 15.) WHERE WILL THE HURRICANE SHUTTERS
 BE STORED?
  
 16.) SHOW TREAD AND RISER DIMENSIONS FOR
 THE EXTERIOR EGRESS STAIR, FBC1007.3.
 SHOW STAIR WIDTH.
  
 17.) SHOW VERTICAL RISE FOR THE EXTERIOR
 STAIR, FBC1007.4.
  
 18.) PROVIDE DETAILS FOR THE HANDRAIL
 AND GUARDRAIL, FBC1015, 1007.5.PROVIDE
 DESIGN CRITERIA FOR BOTH THE GUARDRAIL
 AND HANDRAIL FBC1608.2.DO NOT STATE
 CODE SECTION BY NUMBER; SPECIFY DESIGN
 CRITERIA.THIS COMMENT APPLIES TO BOTH
 THE HANDRAIL/GUARDRAIL AT THE STAIRS AND
 THE GUARDRAIL AT THE BALCONY.
  
 19.) STAIRWAYS SHALL HAVE HANDRAILS ON
 EACH SIDE, FBC1007.5.2.
  
 29.) ADJUST THE VALUE OF THE SCOPE OF
 WORK TO INCLUDE ALL WORK REQUIRED.
  
 30.) SHOW COMPLIANCE WITH FBC1503.4,
 ROOF DRAINS AND FBC1503.4.2, OVERFLOW
 DRAINS.
  
 31.) THE PREVIOUS APPLICATION INCLUDED
 CONCRETE RESTORATION WORK.PROVIDE A
 SPECIFICATION AND LOCATION OF REPAIR
 WORK.
  
 32.) ENERGY CALCS REQUIRED, FBC13.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-23 Cont ID  
Sent By dpalmer Date 2006-08-23 Time 19:33 Rev Time 0.00
Received By dpalmer Date 2006-08-23 Time 18:40 Sent To  
Notes
2006-08-23 00:00:00*** 4TH REVIEW ***
  
 THIS PERMIT IS STILL UNDER THE 2001 FBC.
  
 1) NOTE: PLEASE CORRELATE ALL AIC
 RATINGS ON PLANS. PLEASE VERIFY THE
 AVAILABLE FAULT CURRENT AS THE NEW
 METER/COMBO IS BEING SHOWN AS 42K WHICH
 IS MENTIONED AS 80 FT AWAY FROM THE FPL
 TRANSFORMER.
 PLEASE KNOW, THE FURTHER AWAY, THE LESS
 THE AVAILABLE FAULT CURRENT IS. PLEASE
 SEE PLANS INDICATE THE PANEL UPSTAIRS AS
 22K NAD RISER SHOWS THIS PANEL AS 10K.
 PLEASE SEE A/C DISCONNECT IS BEING SHOWN
 AS 10K RATED. PLEASE KNOW, THE RATING OF
 THE A/C DISCONNECT IS NOT NEEDED.
 110.9,
 FBC 104.2.1
  
 2) NOTE: PLEASE SEE 210.21B3, PLEASE SEE
 A RANGE/STOVE RECEPT IS 50A RATED,
 PLEASE SEE PANEL SCHEDULE IS SHOWING A
 60A BRKR. PLEASE SEE CODE ABOVE, NO MORE
 THAN 50A OCP IS PERMITTED.
  
 3) NOTE: PLEASE KNOW, IT IS UNDERSTOOD
 FROM THIS OFFICE THE DOWNSTAIRS IS
 HAVING TO BE BROUGHT UP TO CODE AND MUST
 BE DONE AT THIS TIME. (EVEN IF FOR SHELL
 OF FUTURE OFFICE)
 PLEASE SHOW THE LOCATION OF THE NEW
 PANEL AND SHOW MIN LTS REQUIRED FOR
 EGRESS AND EXITING.
 PLEASE KNOW, WE ARE UNABLE TO VERIFY THE
 MIN CLEARENCES FOR THE PANEL PER 110.26
 AND LOCATION FOR PANEL PER 240.24.
 PLEASE SEE NFPA-101 2003 FOR MIN LTS FOR
 EXT AND EM LTS. 7.8, 7.9
  
 4) NOTE: PLEASE SEE LOAD CALCULATIONS
 ARE SHOWING LOAD FOR WHAT SEEMS TO BE
 DEDICATED RECEPTS OF SOME SORT YET THIS
 COULD NOT BE FOUND ON PANEL SCHEDULE.
 (3KW)? PLEASE SEE 500VA ALSO SHOWN FOR
 SD'S?
 PLEASE SEE ALL GEN LTS AND RECEPTS FOR
 UPPER SPACE SHALL BE INCLUDED IN THE MIN
 3VA PER SQ FT.
 220.31
  
 5) NOTE: PLEASE SEE THE PLANS SHALL
 INDICATE ALL THE RELEVANT CODES AT A
 MIN.
 2001 FBC, 2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101
  
 6) NOTE: PLEASE SEE A RESPONSE NOTE
 MENTIONS A CONFLICT IN ELECTRICAL REVIEW
 AND FIRE REVIEW FOR REQUIRMENT OF THE
 SD'S OUTSIDE SLEEPING ROOMS/ AND
 KITCHENS.
 PLEASE SEE NFPA-72 11.8.3, 11.5.1.1,
 SD'S ARE REQUIRED OUTSIDE ALL SLEEPING
 ROOMS AND IF WITHIN 20' OF COOKING
 APPLIANCES, THEN THE SD'S MUST BE
 RE-SETTING TYPE/PHOTO-ELECTRIC EYE.
  
 7) NOTE: PLEASE BE SURE THE ENERGY
 CALCULATIONS SUBMITTED CONTAIN AN
 ORIGINAL SIGNATURE, DATE AND SEAL FROM
 THE DESIGN PROFESSIONAL.
 FS471.025
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 14:29 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 13:17 Sent To  
Notes
2005-12-21 00:00:00*** UNSAT ***
  
 PLEASE SEE MANY NEW COMMENTS DUE TO
 CHANGES MADE TO PLANS.
 PLEASE ALSO SEE COMMENT FROM OTHER
 REVIEWS NOT ADDRESSED.
  
  
 1)NOTE: PLEASE SEE PLANS HAVE NOW
 DELETED TWO OF THE REQUIRED SD'S ON
 PLANS?
 NFPA-72 11.5.1.1
  
 2)NOTE: PLEASE ALSO PREVIOUS PLANS HAD
 MADE CORRECTIONS FOR SD'S TO BE ON AN
 ARC FAULT PROTECTED CIRCUIT AS REQUIRED
 PER 2002 210.12 AND NOTED ON PREVIOUS
 REVIEWS, HOWEVER PLEASE SEE THIS CIRCUIT
 AHS NOW REMOVED THE ARC FAULT
 PROTECTION.???
  
 3)NOTE: PLEASE SEE PLANS DO NOT SHOW THE
 NEW SERVICE LOCATION ON PLANS. PLEASE
 SEE PLANS ONLY INDICATE THE NEW METER.
 215.5
  
 4)NOTE: PLEASE NOW SEE THE NEW SERVICE
 RISER HAS COMPLETELY CHANGED WHICH IS
 INTRODUCING MANY NEW COMMENTS.
  
 PLEASE SEE CONDUCTORS ON RISER AND FOR
 FEEDERS TO PANELS ARE INDICATING SERVICE
 BEING A 3-PHASE SERVICE.PLEASE ADJUST
  
 PLEASE SEE RISER SHOWS A 200A FEED TO A
 200A PANEL , HOWEVER , PLEASE SEE NO
 PANEL SCHEDULE SUBMITTED TO CORRELATE
 WITH THIS. THE ONLY PANEL SCHEDULE SHOWN
 IS A 150A PANEL FOR UNIT UPSTAIRS.
  
 PLEASE SEE GROUNDING ELECTRODE CONDUCTOR
 IS NOW REQUIRED TO BE INCREADED PER
 250.66 AND SIZING OF SEC'S.
  
 5)NOTE: PLEASE SEE TWO CIRCUITS GOING TO
 THE SAME DEVICE IN BEDRMS. (SWITCHED
 RECEPT) PLEASE SEE THIS WOULD REQUIRE
 THE USE OF A TWO POLE BREAKER IN PANEL,
 HOWEVER PLEASE SEE THERE ARE THREE
 CIRCUITS SHARED IN THIS SCENERIO WHICH
 WOULD BE ABLE TO BE DONE.
  
 6)NOTE: PLEASE SEE NOW LOAD CALCUALTIONS
 SUBMITTED FOR FIRST FLOOR WHICH DO NO
 CORRELATE WITH THE NEC AND OFFICE OR
 MERCHANTILE OCCUPANCY AS INIDCATED ON
 THE PLANS.
 PLEASE SEE 220 OF THE NEC FOR CORRECTED
 LOAD CALCS.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
 ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%.
  
 ** PLEASE SEE ONE SET OF NEW PLANS AND
 OLD HAVE BEEN RETAINED FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-14 Cont ID  
Sent By dpalmer Date 2005-06-14 Time 05:55 Rev Time 1.00
Received By dpalmer Date 2005-06-13 Time 19:19 Sent To  
Notes
2005-06-14 00:00:00*********** UNSAT2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW NOTES.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 OK, HOWEVER PLEASE SEE
 LOWER AREA FOR STAIRS NOW SHOWS A
 PC(PULL CHAIN)? FOR CONTROL OF EGRESS
 LIGHTING. PLEASE SEE A 3-WAY WP SWITCH
 IS REQUIRED.
 210.70,LS 101 5-8
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE
 COUNTERSPACE. SCALE FOR ELECTRICAL PLANS
 NOT PROVIDED, HOWEVER IF USEING 1/8" MIN
 PER CODE THERE APPEARS TO BE MISSING PER
 210.52C1. PLEASE SEE REDLINED PLANS.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE 210.8A6
 AS NOTED ON PREVIOUS NOTE.
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE #9 NO, PREVIOUS.
  
 10)NOTE: NOTE #10 NO, NEW SERVICE SHOWN,
 YET NO INFORMATION PROVIDED FOR EXISTING
 SERVICE, MAINS, GROUPING ETC. A NEW
 SERVICE WILL NOT BE PERMITTED.
 230.2
 PLEASE SEE 110.9, AIC RATING PROVIDED
 FOR PANEL, HOWEVER RATING FOR MAIN ALSO
 REQUIRED.
  
 11)NOTE: NOTE #11OK.
  
 12)NOTE: NOTE #12 OK, HOWEVER SEE NEW
 NOTES FOR OUTSIDE RECEPT.
  
 13)NOTE: NOTE #13 NO.
 PLEASE SEE PREVIOUS AND PLEASE SEE FAC
 61G1-16.004 FOR ALL INFORMATION REQUIRED
 ON TITLE BLOCK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE NEW GFI RECEPT FOR
 A/C COND IS NOW SHOWN CIRCUITED ON
 KITCHEN SMALL APPLIANCE CIRCUIT.PLEASE
 SEE 210.52B
  
 2)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR BLDG AND SCOPE OF WORK BRINGING BLDG
 UP TO CODE PER FBC CHAPTER 34.
 THIS WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS AND WORK ALSO REQUIRED
 IN OTHER PARTS OF STRUCTURE.
  
 3)NOTE: PLEASE SEE THE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO THE
 DESIGN PROFESSIONAL AND REPEAT COMMENTS
 FOR THE SAME CODE ARTICLES.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.\
 PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-06-13 00:00:00NOTES TO FOLLOW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-28 Cont ID  
Sent By dpalmer Date 2005-02-28 Time 07:29 Rev Time 0.50
Received By dpalmer Date 2005-02-28 Time 07:29 Sent To  
Notes
2005-02-28 00:00:00******** UNSAT ***********
  
 1)NOTE: PLEASE PROVIDE OCCUPANCY FOR
 FIRST FLOOR AREA AND USE.
  
 2)NOTE: THE LAUNDRY CIRCUIT CALCULATION
 MUST COMPLY WITH 220.116(B).(1500 VA).
  
 3)NOTE: PLEASE SEE 210.70, LS 101 5-8,
 PLEASE VERIFY MEANS OF EGRESS LIGHTING
 FROM SECOND FLR TO GRADE LEVEL.
  
 3)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
  
 4)NOTE: PLEASE SEE 210.11C1, TWO SM APPL
 CIRCUITS MIN.
  
 5)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE.
  
 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 7)NOTE: PLEASE SEE 240.4B,310.16 FOR MIN
 SIZE AWG FOR RANGE ON A 2P-60A.
  
 8)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU. MIN 125%. PLEASE ALSO SEE
 310.16/240.4 FOR SIZING OF AWG.
 PLEASE SEE 8KW SHOWN ON 2P30A AND #10.
  
 9)NOTE: PLEASE SEE 210.52C3 FOR
 PENINSULAR GFI REQUIRED.
  
 10)NOTE: PLEASE VERIFY IF PANEL IS NEW
 OR EXSITING. SHOWN AS NEW ANDNOTES
 MENTIONS NEW GROUND RODS ?
 PLEASE INCLUDE RISER DIAGRAM FOR FEED TO
 NEW PANEL. MAIN, GROUPING, GROUNDING,
 CONDUCTORS ETC.
 215.5
 PLEASE ALSO SUBMIT AIC RATING FOR NEW
 EQUIPMENT. 110.9.
  
 11)NOTE: PLEASE INCLUDE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH A PANEL
 SCHEDULE.
  
 12)NOTE: PLEASE SHOW AHU/A/C UNITS ALONG
 WITH REQUIRED DISC'S PER 440-11.
 PLEASE ALSO SEE 210.63 FOR REQUIRED GFI
 FOR COND UNIT.
  
 13)NOTE: PLEASE CORRELATE ADDRESS ON
 PLANS AND APPLICATION. ONE MENTIONS, 800
 SAPPODILLA, AND THE OTHER 633 37TH ST?
 PLEASE ALSO SEE BLDG REVIEW COMMENTS FOR
 SUITE # OR EXTENSION TO BLDG.
  
 14)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 15)NOTE: PLEASE SEE NFPA-72 8-1.4.2, SD
 NOT PERMITTED IN KITCHEN.
 PLEASE ALSO SEE MIN DISTANCE SD IS
 REQUIRED TO BE FROM COOKING APPLIANCES
 WITH EXCEPTIONS.
 PLEASE ALSO SEE SD'S ARE ALSO REQUIRED
 TO BE A MIN OF 3' FROM BATH DOORS.
  
  
 PLEASE SEE OTHER POSSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-09-15 Cont ID  
Sent By mwennerg Date 2006-09-15 Time 14:56 Rev Time 0.00
Received By mwennerg Date 2006-09-15 Time 14:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-12-22 Cont ID  
Sent By mwennerg Date 2005-12-22 Time 14:55 Rev Time 0.00
Received By mwennerg Date 2005-12-22 Time 14:55 Sent To  
Notes
2005-12-22 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT REQUIRED SMOKE
 DETECTORS HAVE BEEN REMOVED FROM SHEETS.
 PLEASE SHOW LOCATIONS OF SMOKE DETECTORS
 IN ACCORDANCE WITH NFPA 101, SEC.
 24.3.4.2.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561)805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-06-15 Cont ID  
Sent By nmccray Date 2005-06-15 Time 11:37 Rev Time 0.00
Received By nmccray Date 2005-06-15 Time 11:37 Sent To  
Notes
2005-06-15 00:00:00DENIED
  
 1) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE, 2003 EDITION CH. 24.1.2
 MULTIPLE OCCUPANCIES.
  
 2) INTERIOR WALL AND CEILING FINISH
 MATERIALS COMPLYING WITH SECTION 10.2
 SHALL BE CLASS A, CLASS B, OR CLASS C.
  
 3) THE ENTRANCE DOOR THAT LEADS TO THE
 EXISTING STAIRS MUST COMPLY WITH NFPA
 101, SECTION 7.2.1.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-835-2935 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-03-23 Cont ID  
Sent By mwennerg Date 2005-03-23 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2005-03-23 Time 11:06 Sent To  
Notes
2005-03-23 00:00:001) PLEASE PROVIDE INFORMATION REGARDING
 OCCUPANCY USE FOR BOTH FLOORS OF THE
 BUILDING.
  
 2) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR WALLS AND CEILING.
  
 3) ABC TYPE FIRE EXTINGUISHERS MAY BE
 REQUIRED CONTINGENT ON ADDITIONAL
 OCCUPANCY INFORMATION.
  
 4)THE ENTRANCE DOOR THAT LEADS TO THE
 EXISTING STAIRS MUST COMPLY WITH NFPA
 101, SECTION 7.2.1.
  
 5) PLEASE BE ADVISED THAT ALL LIFE
 SAFETY MUST COMPLY WITH NFPA 101, 2003
 EDITION.
  
 6) PLEASE BE ADVISED THAT ALL
 DEMOLITION. RENOVATION AND CONSTRUCTURE
 SHALL BE IN ACCORDANCE WITH NFPA 241.
  
 7) PLEASE PROVIDE ADDITIONAL MEANS OF
 EGRESS INFORMATION ONCE THE EXISTING
 STAIRS ARE REACHED.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 16:44 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 16:44 Sent To  
Notes
2006-08-22 00:00:00TO "COMM" BD#16
2006-08-08 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 18:37 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 18:37 Sent To  
Notes
2005-12-09 00:00:00MOVED TO SPACE #55
2005-11-29 00:00:00TO "COMM" BD#60
2005-11-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-07 Cont ID  
Sent By mjacobs Date 2005-06-07 Time 07:20 Rev Time 0.00
Received By mjacobs Date 2005-06-07 Time 07:20 Sent To  
Notes
2005-06-07 00:00:00TO COMM BD#32 RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-27 Cont ID  
Sent By adarroug Date 2005-05-27 Time 14:33 Rev Time 0.00
Received By adarroug Date 2005-05-27 Time 14:33 Sent To  
Notes
2005-05-27 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-25 Cont ID  
Sent By adarroug Date 2005-02-25 Time 15:49 Rev Time 0.00
Received By adarroug Date 2005-02-25 Time 15:49 Sent To  
Notes
2005-02-25 00:00:00TO "COMM" BD#15

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date 2006-10-02 Cont ID  
Sent By hmoser Date 2006-10-02 Time 16:08 Rev Time 0.00
Received By hmoser Date 2006-10-02 Time 16:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-02 Cont ID  
Sent By hmoser Date 2006-10-02 Time 16:04 Rev Time 0.00
Received By hmoser Date 2006-10-02 Time 16:04 Sent To  
Notes
2006-10-02 00:00:00PASS PRIVISO
 PLEASE REFER TO SECTION 602.2.1 FBD(M)
 2004 MATERIALS EXPOSED WITHIN PLENUMS.
 PLAN REVIEW BY HAROLD MOAER 561-805-6732
2006-08-23 00:00:00NEW SHEETS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-21 Cont ID  
Sent By hmoser Date 2005-06-21 Time 08:20 Rev Time 0.00
Received By hmoser Date 2005-06-21 Time 08:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By pkrauss Date 2005-03-21 Time 07:56 Rev Time 0.40
Received By pkrauss Date 2005-03-21 Time 07:38 Sent To  
Notes
2005-03-21 00:00:00DENIED:
 1.PROVIDE DUCT SIZE ON THE SUPPLY
 BRANCH DUCTS.RETURN AIR JUMPERS SHALL
 BE A MINIMUM OF 1 1/2 TIMES GREATER THAN
 THE CROSS SECTIONAL AREA (SQAURE INCHES)
 OF THE SUPPLY AIR TO THAT ROOM. 2001
 FBC/M 601.4 EXCEPTION #1.
  
 2.PROVIDE GRILLE SIZES.
  
 3.PROVIDE INFORMATION & DETAILS FOR
 THE DRYER EXHAUST.INDICATE DUCT
 MATERIAL, SIZE, AND TERMINATION.
  
 4.PROVIDE SCHEDULE FOR THE EXHAUST FAN
 LOCATED IN THE BATHROOM.
  
 5.PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORDANCE WITH 2001 FBC
 CHAPTER 13 SUB-SECTION 600.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-09-05 Cont ID  
Sent By kstevens Date 2006-09-05 Time 09:49 Rev Time 0.00
Received By kstevens Date 2006-09-05 Time 09:49 Sent To  
Notes
2006-08-23 00:00:00NEW SHEETS

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-21 Cont ID  
Sent By pschmitz Date 2005-06-21 Time 07:59 Rev Time 0.00
Received By pschmitz Date 2005-06-21 Time 07:59 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-16 Cont ID  
Sent By kstevens Date 2005-03-16 Time 18:18 Rev Time 0.75
Received By kstevens Date 2005-03-16 Time 17:58 Sent To  
Notes
2005-03-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
 1) SHT 5 0F 5 SANITARY RISER DIAGRAM
 DOES NOT MEET CODE REQUIREMENTS, AND
 SHALL BE IN AN ISOMETRIC FORM SHOWING
 VENT CONNECTIONS.
 2) KITCHEN SINK IS NOT VENTED. SECTION
 901.2.1.
 3) TUB IN BATHROOM IS NOT VENTED.
 SECTION 901.2.1.
 4) WASH MACHINE SHALL NOT DRAIN THROUGH
 THE WET VENT OF THE BATHROOM FIXTURES,
 BUT SHALL DISCHARGE DOWNSTREAM OF THE
 BATHROOM FIXTURES. SECTION 909.1
 THE WASH MACHINE SHALL DISCHARGE INTO A
 STANDPIPE AND A CLEANOUT 4' ABOVE THE
 FLOOR IS REQUIRED. SECTIONS 1002.1 AND
 708.10.
 5) SEE ATTACHED SHEET FOR AN EXAMPLE OF
 AN ISOMETRIC THAT MEETS CODE
 REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By astelly Date 2006-09-11 Time 11:52 Rev Time 0.00
Received By astelly Date 2006-09-11 Time 11:52 Sent To  
Notes
2006-09-11 00:00:00PLEASE PROVIDE A RECENT SURVEY FOR THE
 SUBJECT PROPERTY.
  
 A CLASS B SPECIAL USE PERMIT WILL BE
 REQUIRED FOR THE ESTABLISHMENT OF ANY
 NEW COMMERCIAL USES IN ANY OF THE
 EXISTING COMMERCIAL SPACES ON THE
 PROPERTY.