| Plan Review Stops For Permit 05021334 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
20 |
Status |
P |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2005-11-16 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2005-11-16 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
19 |
Status |
F |
Date |
2005-11-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-11-07 |
Time |
18:44 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-11-07 |
Time |
18:44 |
Sent To |
Z |
|
| Notes |
| 2005-11-07 00:00:00 | ****CORRECTIONS**** | | | ****PLAN REVIEW IN PROGRESS*** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)PROVIDE FOUNDATION OR ANCHORING | | | DETAIL FOR THE ATTENDANT BOOTH. | | | | | | 2.)PROVIDE A SITE PLAN SHOWING WHERE | | | THE ATTENDANT BOOTH WILL BE INSTALLED | | | | | | 3.)FEES DUE (REVISION, NOT A | | | SUBMITTAL). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
18 |
Status |
P |
Date |
2005-11-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-11-07 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-11-07 |
Time |
18:44 |
Sent To |
|
|
| Notes |
| 2005-11-07 00:00:00 | LIGHT POLE CALCS AND SPEC SHEETS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
17 |
Status |
F |
Date |
2005-10-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-10-03 |
Time |
16:28 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-10-03 |
Time |
16:28 |
Sent To |
PC |
|
| Notes |
| 2005-10-03 00:00:00 | ****CORRECTIONS**** | | | LIGHT POLE CALCS | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)THERE ARE STILL MANY REFERENCES TO | | | OTHER BUILDING CODES (INCLUDING A | | | NONEXISTANT ONE) - IBC, 2000FBC, UBC. | | | PLEASE REVISE AND HAVE ALL CODE | | | REFERENCES REFER TO THE APPLICABLE | | | SECTION OF THE FBC2001. | | | | | | 2.)A REQUEST WAS MADE FOR THE FIXTURE | | | CALCS AS WELL AS THE POLE CALCS.PLEASE | | | PROVIDE. | | | | | | 3.)ALL SUBMITTALS ARE TO BE REVIEWED | | | BY DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | TO THE CITY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
16 |
Status |
F |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-09-20 |
Time |
08:36 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-09-20 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2005-09-20 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)DOCUMENTS PREPARED BY AN ENGINEER | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED AND DATED ORIGINALS, | | | FAC61G15-23. | | | | | | 2.) A TITLE BLOCK INCLUDING ALL | | | INFORMATION REQUIRED BY FAC61G15-23.002 | | | IS REQUIRED.THE ADDRESS FOR ACCORD | | | INDUSTRIES DOES NOT MATCH THE DPBR | | | WEBSITE FOR THIS ENGINEER. | | | | | | 3.)THERE ARE SEVERAL REFERENCES TO THE | | | IBC.GOVERNING CODE IS FBC, PLEASE | | | EITHER PROVIDE EQUIVALENT IN FBC OR | | | INCLUDE SPECIFICATION OR DETAIL. | | | | | | 4.)NOTE 1 STATES THAT NO SOILS REPORT | | | WAS AVAILABLE.REMOVE THIS NOTE AS A | | | SOILS REPORT IS AVAILABLE, PLEASE | | | CONTACT GENERAL CONTRACTOR. | | | | | | 5.)NOTE 2, FBC1806.8.2.1 IS NOT IN THE | | | FBC. | | | | | | 6.)NOTE 5, THE FAC RULE REFERRED TO | | | HAS BEEN REPEALED. | | | | | | 7.)PLEASE NOTE THAT THE FIXTURE CALCS | | | ARE REQUIRED.THE DETAIL, DESIGN | | | CRITERIA AND CALCS WERE FOR THE POLE | | | ONLY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
15 |
Status |
P |
Date |
2005-09-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-09-16 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-09-16 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2005-09-16 00:00:00 | REVISED A2.1 DATED9/14/05 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
14 |
Status |
F |
Date |
2005-09-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-09-14 |
Time |
11:00 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-09-14 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2005-09-14 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)REVISE ALL SHEETS AFFECTED BY THE | | | REVISION SUBMITTED - SITE PLAN, A0.1, | | | ANY OTHER SHEETS AFFECTED BY THE | | | PROPOSED KIOSK OR RAMP DETAIL. | | | | | | 2.)8 1/2 X 11 SHEETS CAN BE SUBMITTED | | | AS SUPPLEMENTARY OR ALTERNATE DETAILS | | | BUT REVISIONS TO THE BUILDING PLANS | | | SHOULD REVISED ALL AFFECTED SHEETS. | | | | | | 3.)DIMENSIONS ON A0.1 SHOWING CODE | | | COMPLIANCE FOR THE RAMP WERE NOT ON THE | | | DETAIL PROVIDED.WHEN REVISING A0.1 | | | PLEASE INCLUDE ALL NECESSARY DIMENSIONS. | | | | | | 4.)SHOW THE MANEUVERING CLEARANCE FOR | | | THE BREAK ROOM DOOR, FBC11 FIGURE 25. | | | | | | 5.)PROVIDE OPENING WIDTH BETWEEN THE | | | BLOCK WALLS LEADING TO THE RAMP. | | | | | | 6.)SEPARATE PERMIT REQUIRED FOR THE | | | PREFAB KIOSK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
13 |
Status |
P |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-29 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-29 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2005-08-29 00:00:00 | DOOR HARDWARE SUBMITTAL | | | DOOR SHOPS AND PRODUCT APPROVALS | | | ONE SET REMOVED FROM PACKAGE AND FILED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
P |
Date |
2005-08-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-18 |
Time |
13:05 |
Rev Time |
0.25 |
| Received By |
shill |
Date |
2005-08-18 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2005-08-18 00:00:00 | ALTERNATE DOOR FRAME DETAIL PREPARED BY | | | PEDRO DE FIGUERIEREDO, REVIEWED BY EOR |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2005-08-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-18 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-18 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2005-08-18 00:00:00 | SOIL DENSITY REPORT | | | PREPARED BY NUTTING ENGINEERS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
F |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-10 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-10 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)THE WALL RAIL IS TO HAVE 18" | | | EXTENSIONS, FBC11-4.84.5(2).THE DETAIL | | | REFERS TO ADA; PLEASE NOTE THAT FLORIDA | | | USES FBC CHAPTER 11 WHICH IS MORE | | | STRINGENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-10 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-10 |
Time |
18:16 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | VARIOUS DETAILS 8/8/05 | | | | | | REVISED DOOR SCHEDULE | | | PIPING TRENCH REPAIR DETAIL | | | AD-1.4 | | | AD-1.5 | | | AD-1.6 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-10 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-10 |
Time |
17:55 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | REVISED A0.1 TO SERVE AS INDEX SHEET FOR | | | ENTIRE PLAN (CORRECTED DATE) | | | NEW A1.3 (NEW RAMP/ACCESSIBLE ENTRANCE) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-10 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-08-10 |
Time |
17:46 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | ****CORRECTIONS**** | | | DRAWING 05-245A PREPARED BY PEDRO DE | | | FIGUEIREDO PE | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)THE ENGINEER WHO PREPARED THIS | | | DETAIL ON SHEET A4.1 IS JIM NADASKAY, | | | PE.ANOTHER ENGINEER CANNOT MODIFY THIS | | | DESIGN UNLESS IT IS DELEGATED | | | ENGINEERING.EITHER HAVE THIS DETAIL | | | INCORPORATED INTO MR. NADASKAY'S PLAN OR | | | HAVE REVIEWED BY MR. NADASKAY, ENGINEER | | | OF RECORD. | | | | | | 2.)THE SUBMITTAL STATES "USE IN | | | CONJUNCTION WITH DRAWINGS 05-245".IF | | | YOU RESUBMIT THIS DETAIL, SUBMIT | | | REFERRED DRAWING. | | | | | | 3.)SHEET A-4.1 WAS NOT SIGNED AND | | | SEALED.PLEASE SUBMIT. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-10 |
Time |
17:35 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-08-10 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | ****CORRECTIONS**** | | | SOILS ENGINEERING | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.) SOILS REPORT TO BE REVIEWED BY | | | DESIGNER OF RECORD. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-07-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-23 |
Time |
21:37 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-07-23 |
Time |
21:35 |
Sent To |
|
|
| Notes |
| 2005-07-23 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)SHEET AD-1.1 IS TO HAVE A TITLE | | | BLOCK WITH ALL INFORMATION REQUIRED BY | | | FAC61G1-16. | | | | | | 2.)CA NUMBER REQUIRED FOR THE | | | ARCHITECT BUSINESS, FAC61G1-16. | | | | | | 3.)BLUNK DEMATTEI ASSOCIATES IS NOT | | | THE DOR FOR THIS JOB.MR. DEMATTEI IS | | | DOR AS AN INDIVIDUAL.IF YOU WOULD LIKE | | | TO CHANGE DOR TO THE COMPANY PLEASE READ | | | FAC61G1-18 AND ADDRESS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-20 |
Time |
09:57 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-07-20 |
Time |
09:57 |
Sent To |
PC |
|
| Notes |
| 2005-07-20 00:00:00 | REVISION DATED 6/30, CANOPY |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-05-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-31 |
Time |
11:28 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2005-05-31 |
Time |
10:06 |
Sent To |
P |
|
| Notes |
| 2005-05-31 00:00:00 | ***PROVISO*** | | | PROVIDE INDEX SHEET AND LETTER REGARDING | | | DATE ON PLANS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-05 |
Time |
15:19 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-05-05 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2005-05-05 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SHEET 1 ISN'T SEALED.IT SERVES | | | NOT ONLY AS A COVER SHEET BUT ALSO | | | DECLARES CODE COMPLIANCE FOR OCCUPANCY, | | | ETC. (PROJECT DATA). | | | | | | 2.)BUSINESSES PRACTICING ARCHITECTURE | | | IN FLORIDA ARE TO HAVE A CERTIFICATE OF | | | AUTHORIZATION NUMBER AND INCLUDE THIS | | | NUMBER ON THE TITLE BLOCK, FAC61G1-16. | | | | | | 3.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED IN ADDITION TO THE | | | TEST REPORTS PROVIDED, FAC9B72.SEE | | | WWW.FLORIDABUILDING.ORG. | | | | | | 10.)PRODUCT APPROVALS WERE NOT | | | PROVIDED FOR THE CANOPY STEEL ROOF DECK. | | | THE ENGINEER FOR THE ROOF DECK INDICATED | | | THAT THEY WOULD BE PROVIDED BUT THEY | | | WERE NOT INCLUDED IN THE PACKAGE. | | | FAC9B72. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-03-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-18 |
Time |
10:58 |
Rev Time |
4.00 |
| Received By |
shill |
Date |
2005-03-17 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2005-03-18 00:00:00 | PERMIT #05021334 | | | ****PAID PLAN CHECK**** | | | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION. | | | | | | 3.) THE OWNER IN OUR RECORDS | | | (PRESIDENTIAL MOTORS) CONFLICTS WITH THE | | | PERMIT APPLICATION. | | | | | | 4.) A0.1 REFERS TO ?WEST PALM BEACH | | | COUNTY BUILDING CODE?.GOVERNING CODE | | | IS FBC2001 WITH 2003 AMENDMENTS AND CITY | | | OF WEST PALM BEACH AMENDMENTS. | | | | | | 5.) CERTIFICATE OF AUTHORIZATION | | | REQUIRED FOR ENGINEERS AND ARCHITECTS; | | | TITLE BLOCKS TO BE IN COMPLIANCE WITH | | | BOARD RULES, FAC61G15-23.002, | | | FAC61G1-16.003,004.PLEASE CHECK ALL | | | SHEETS, INCLUDING CALCULATIONS. | | | | | | 6.) AWNING SHEETS (AB) AND CALCULATIONS | | | DECLARE A ?WIND LOAD? OF 130MPH; CITY OF | | | WEST PALM BEACH IS IN THE 140 MPH WIND | | | ZONE. | | | | | | 7.) C2, ACCESSIBLE PARKING IS TO COMPLY | | | WITH CITY OF WEST PALM BEACH STANDARDS, | | | SEE ATTACHED. | | | | | | 8.) A1.1 REFERS TO DETAIL 12-A1.2, | | | DUMPSTER ENCLOSURE PLAN.DETAIL IS NOT | | | WHERE NOTED. | | | | | | 9.) PROVIDE AREA CALCULATIONS; EXISTING, | | | PROPOSED, NEW TOTAL. | | | | | | 10.) FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED IN ADDITION TO TEST | | | REPORTS.WWW.FLORIDABUILDING.ORG. | | | STOREFRONT SYSTEM | | | IMPACT PROTECTION | | | STEEL ROOF DECK | | | EXTERIOR DOOR | | | | | | 11.) IF REMOVABLE SHUTTERS ARE USED IN | | | LIEU OF IMPACT GLASS, PROVIDE | | | INFORMATION IN REGARDS TO WHERE THE | | | SHUTTERS WILL BE STORED. | | | | | | 12.) PROVIDE WALL DIMENSION FOR DOOR 11, | | | SHEET A2.1, PUSH SIDE, SEE FBC CHAPTER | | | 11 TABLE 25 (A). | | | | | | 13.) DETAIL 3-A4.1, PROVIDE FASTENING OF | | | WOOD BLOCKING TO COLUMNS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2005-11-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-07 |
Time |
16:50 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-11-07 |
Time |
16:50 |
Sent To |
B |
|
| Notes |
| 2005-11-07 00:00:00 | REVISED LOAD CALCULATIONS TO DECREASE | | | SITE LIGHTING WATTAGE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
F |
Date |
2005-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-28 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-09-28 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2005-09-28 00:00:00 | ***** UNSAT ***** | | | | | | | | | | | | POLE CALCUALTIONS SUBMITTED STILL DO NOT | | | APPEAR TO MEET PREVIOUS REQUESTED | | | INFORMATION. | | | PLANS/ CALCS SUBMNITTED SENT TO BLDG | | | REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-19 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-09-19 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2005-09-19 00:00:00 | ********* UNSAT ***************** | | | | | | | | | | | | 1)NOTE: PLEASE SEE AS PREVIOUSLY | | | REQUESTED. PLEASE SUBMIT COMPLETE | | | SIGNED, DATED AND SEALED WIND LOADING | | | CALCULATIONS FOR NEW LT POLES AND | | | FXTURES. PLEASE SEE NO LT FIXTURES | | | INCLUDED IN CALCUALTIONS, AND | | | INFORMATION SUBMITTED WAS NOT SIGNED , | | | DATED OR SEALED. | | | FS 471.025, FAC 61G15-23.002 | | | | | | ** PLEASE NOTE** | | | WIND LOADING CALCS WILL BE REVIEWED BY | | | STRUCTUAL REVIEWER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | WIND LOAD CALCS SENT TO SH. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2005-09-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-03 |
Time |
09:47 |
Rev Time |
0.40 |
| Received By |
dpalmer |
Date |
2005-09-03 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2005-09-03 00:00:00 | ********* UNSAT *********** | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETE | | | WINDLOADING CALCULATIONS FOR ALL SITE | | | LIGHTING POLES AND FIXTURES. | | | THIS WAS REQUESTED ON PREVIOUS REVIEWS | | | AND REDLINED ON PREVIOUS SET. | | | PLEASE SEE THAT ALL MUST MEET FBC | | | 140MPH. | | | | | | 2)NOTE: PLEASE SEE THAT NEW KIOSK PANEL | | | SHALL AHVE A MCB FOR MEANS OF DISCONNECT | | | AS REQUIRD PER 225.31. | | | | | | 3)NOTE: PLEASE INDICATE GROUNDING AT | | | THIS DETACHED BLDG. | | | 250.32 | | | | | | 4)NOTE: PLEASE SEE SERVICE IS REQUIRED | | | TO UPGRADES FROM THE 400A SHOWN. | | | PLEASE SEE LOAD SHOWN AFTER TAKING | | | PERMITTED DE-RATING EXCEEDS RATING OF | | | SERVICE PROVIDED. | | | 240.4,310.16, 90.8 ETC. | | | | | | 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | PERTAINING TO KIOSK AND INFORMATION | | | REQUIRED FOR THIS BLDG. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-15 |
Time |
18:08 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-08-15 |
Time |
18:08 |
Sent To |
|
|
| Notes |
| 2005-08-15 00:00:00 | REV FOR PVC UNDERGROUND CONDUITS AND | | | AUTOMATED DOORS CUT SHEETS. | | | | | | REDLINED FBC 140 MPH FOR LT POLES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-06 |
Time |
10:46 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-07-06 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2005-07-06 00:00:00 | REV TO ADD POWER ACTUATED DOORS. | | | | | | | | | SEE A-SHEETS, DO NOT CONTAIN CA #'S PER | | | FAC 61G1-16.004, FS 481.219 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-05-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-05-27 |
Time |
12:26 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2005-05-27 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-04-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-20 |
Time |
14:36 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-04-20 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2005-04-20 00:00:00 | **** UNSAT 2ND REVIEW **** | | | | | | PLANS ONLY IN FOR "PLAN REVIEW" AND NOT | | | SUBMITTED FOR PERMIT. | | | | | | 1NOTE: NOTE #1, NO, PLEASE SEE SAME | | | ELECTRICAL SHEET WITH OUT ANY REFERENCE | | | TO FBC 140 MPH . PLEASE ALSO SEE WE | | | COULD NOT LOCATE WIND LOADING | | | CALCULATIONS. | | | | | | 2)NOTE: NOTE #2 OK. | | | | | | 3)NOTE: NOTE #3 OK. | | | | | | 4)NOTE:NOTE #4 OK. | | | | | | 5)NOTE: NOTE #5 NO, PLEASE SEE RISER | | | STILL SHOWS AN EQUIPMENT GROUNDING | | | CONDUCTOR INSTALLED BEFORE THE FIRST | | | MEANS OF DISCONNECT. 250.6,250.24. | | | | | | 6)NOTE: NOTE #6 OK. | | | OCP LOCATED AT PANEL. | | | | | | NEW NOTE: | | | 1)NOTE:PLEASE SEE ELECTRICAL REVIEW | | | PREVIOUS NOTES MENTIONS TO SEE OTHER ) | | | PERTAINING TO POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S). PLEASE SEE NOTE #5 | | | FROM PREVIOUS BLDG REVIEW WHICH | | | REFERENCE WAS GIVEN TO FAC 61G1-16.004 | | | AND FS 481.219 WITH INFORMATION REQUIRED | | | ON TITLE BLOCKS. | | | PLEASE SEE THIS IS REQUIRED ON ALL | | | SHEETS AND FOR ALL TRADES WHEATHER OR | | | NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | PLEASE SEE NONE OF THE TRADE SHEETS HAVE | | | HAD TITLE BLOCKS CORRECTED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-03-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-02 |
Time |
07:26 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-03-02 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2005-03-02 00:00:00 | ***** UNSAT ***** | | | | | | ** PLEASE SEE PLANS ARE IN AS PROJECT | | | FOR "PLAN REVIEW" ONLY NOT FOR PERMIT AT | | | THIS TIME. | | | | | | 1)NOTE: PLEASE SEE WIND LOADING FOR | | | POLES/ FIXTURES FOR SITE LIGHTING IS | | | REQUIRED AT THIS TIME FOR BLDG REVIEW. | | | MIN REQUIREMENTS FOR FBC 140 MPH. | | | | | | 2)NOTE:PLEASE SEE 300.22C FOR "AREAS | | | USED FOR RETURN AIR" | | | PLEASE SEE ALL UNDERGROUND CONDUITS | | | ENTERING EQUIPMENT ETC OF PVC TYPE ARE | | | NOT PERMITTED. | | | PLEASE SPECIFY ON PLANS TYPE OF | | | MATERIALS TO BE USED FOR CONDUIT ETC. | | | IT IS NOTED OF MATERIALS TO BE RATED FOR | | | PLENUM ABOVE CEILINGS. | | | | | | 3)NOTE: PLEASE PROVIDE RECEPTS ABOVE | | | "SHOW WINDOWS". 210.62 THIS IS TO | | | DISCOURAGE FLOOR RECEPTACLES AND | | | UNSIGHTLY EXTENSION CORDS LIKELY TO | | | CAUSE PHYSICAL INJURY, RECEPTACLES MUST | | | BE INSTALLED DIRECTLY ABOVE A SHOW | | | WINDOW, AND ONE RECEPTACLE IS REQUIRED | | | FOR EVERY 12 LINEAR FT OR ?MAJOR | | | FRACTION THEREOF? (6 FT OR MORE). SEE | | | 220.3(B)(7) AND 220.12(A) FOR | | | INFORMATION REGARDING LOAD COMPUTATIONS | | | FOR SHOW WINDOWS. | | | | | | 4)NOTE: PLEASE SEE HANDRAWN ITEMS ON | | | PLANS WHICH ARE SIGNED, DATED AND SEALED | | | BY AN ARCH OR ENG ARE NOT PERMITTED. | | | FS 471.025,481.221 | | | | | | 5)NOTE: PLEASE SEE THERE IS AN EQUIPMENT | | | GROUNDING CONDUCTOR SHOWN FROM METER TO | | | THE FIRST MEANS OF DISCONNECT. | | | PLEASE SEE 250.6,250.24, THIS IS NOT | | | PERMITTED . EQUIPMENT GRNDS ARE ONLY | | | INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNETC. | | | | | | 6)NOTE: PLEASE VERFIY DISCONNECTING | | | MEANS FOR WATER HEATER SHOWN UNDER SINK | | | DOES NOT CONTAIN OCP. | | | 110.26 WOULD APPLY IF OCP IS PROVIDED. | | | THIS IS ONLY A NOTE. DISC APPEARS NOT TO | | | CONTAIN OCP. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2005-04-12 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-04-12 |
Time |
14:41 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2005-04-12 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2005-03-03 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-03-03 |
Time |
09:56 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2005-03-03 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2005-03-03 00:00:00 | FAILED: | | | | | | 1.APPROACHES TO THE SITE MUST BE | | | CONSTRUCTED PER CITY OF WPB'S STANDARD | | | AND REQUIREMENTS; 6" CONCRETE, FROM THE | | | EDGE OF PAVEMENT TO THE PROPERTY LINE. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-01 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-01 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | DOOR AND HARDWARE SUBMITTAL 8/08/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-27 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-27 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2005-07-27 00:00:00 | ******PROVISO****** | | | | | | PLEASE SEE OTHER REVIEW COMMENTS IN | | | REGARDS TO FS AND FAC TITLE BLOCK | | | REQUIREMENTS FOR ALL SHEETS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-04-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-04-28 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-04-28 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2005-03-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-03-23 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-03-23 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2005-03-23 00:00:00 | 1) THE ADDRESS NUMBER MUST BE LOCATED ON | | | THE BUILDING NEAR THE FRONT ENTRANCE | | | DOOR. THE NUMBERS SHALL BE AT LEAST 6" | | | IN HEIGHT AND CONTRASTING TO THE | | | BACKGROUND. | | | | | | 2) PLEASE BE ADVISED THAT ALL LIFE | | | SAFETY MUST COMPLY WITH NFPA 101, 2003 | | | EDITION AFTER JAN. 1, 2005. | | | | | | | | | MIKE WENNERGREN, ACTING CAPTAIN | | | WPBFR(561) 835-2910. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
18 |
Status |
N |
Date |
2005-10-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-17 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-17 |
Time |
11:30 |
Sent To |
E |
|
| Notes |
| 2005-10-17 00:00:00 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
17 |
Status |
N |
Date |
2005-09-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-26 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-26 |
Time |
11:30 |
Sent To |
E |
|
| Notes |
| 2005-09-26 00:00:00 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2005-09-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-21 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-21 |
Time |
09:37 |
Sent To |
B |
|
| Notes |
| 2005-09-21 00:00:00 | TO "NMELICK" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2005-09-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-15 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-15 |
Time |
15:03 |
Sent To |
B |
|
| Notes |
| 2005-09-15 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2005-09-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-15 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-15 |
Time |
14:45 |
Sent To |
E |
|
| Notes |
| 2005-09-15 00:00:00 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2005-09-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-09-15 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-09-15 |
Time |
13:26 |
Sent To |
PC |
|
| Notes |
| 2005-09-15 00:00:00 | REVISION (#55 ON THE BOARD) PULLED AT | | | CONTRACTOR/ARCHITECT REQUEST |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2005-09-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-03 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2005-09-03 00:00:00 | TO COMM BOARD #55 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2005-08-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-11 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-11 |
Time |
16:51 |
Sent To |
B |
|
| Notes |
| 2005-08-11 00:00:00 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-10 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-10 |
Time |
16:50 |
Sent To |
B |
|
| Notes |
| 2005-08-10 00:00:00 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-09 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-09 |
Time |
14:31 |
Sent To |
B |
|
| Notes |
| 2005-08-09 00:00:00 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-09 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-09 |
Time |
08:55 |
Sent To |
B |
|
| Notes |
| 2005-08-09 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-09 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-09 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2005-08-09 00:00:00 | TO "COMM" BD#62 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-07-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-07 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-07 |
Time |
15:42 |
Sent To |
B |
|
| Notes |
| 2005-07-07 00:00:00 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-28 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-28 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2005-07-01 00:00:00 | TO "COMM" BD#29 | | 2005-06-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-05-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-20 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-20 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2005-05-31 00:00:00 | TO "COMM" BD#62 | | 2005-05-20 00:00:00 | IN INCOMING AWAITING SPACE ON "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-04-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-12 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-12 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2005-04-12 00:00:00 | TO "COMM" BD#51 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-03-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-29 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-29 |
Time |
08:27 |
Sent To |
Z |
|
| Notes |
| 2005-03-29 00:00:00 | TO "Z" BOX/TAKEN FROM BD#13 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-03-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-31 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-02-25 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2005-02-25 00:00:00 | TO "COMM" BD#13 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
N |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-11-16 |
Time |
10:34 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2005-11-16 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2005-11-16 00:00:00 | REVISION FOR THE KIOSK IN THE PARKING | | | GARAGE.WINDOW UNIT WILL BE INSTALLED | | | NO MECHANICAL PERMIT REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2005-08-26 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-08-26 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-08-26 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2005-08-26 00:00:00 | PLAN DENIED | | | NEED TWO SETS OF PLANS SIGNED AND SEALED | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-27 |
Time |
19:30 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2005-07-27 |
Time |
19:20 |
Sent To |
|
|
| Notes |
| 2005-07-27 00:00:00 | NO MECHANICAL REVISIONS SUBMITTED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2005-05-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-05-17 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2005-05-17 00:00:00 | SEE PROVISO FRON REVIEW ON 3/21/05 | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2005-03-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-03-21 |
Time |
09:05 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-03-21 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2005-03-21 00:00:00 | PROVISO: | | | 1.FRESH AIR INTAKES SHALL BE LOCATED A | | | MINIMUM OF 10 FT FROM PARKING LOTS PER | | | 2001 FBC/M 401.5.1. | | | | | | 2.RTU CURBS SHALL BE A MINIMUM OF 8" | | | ABOVE THE ROOF SURFACE IN ACCORDANCE | | | WITH 2001 FBC 1511.7. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
N |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2005-11-16 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2005-11-16 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2005-11-16 00:00:00 | NOT REQUIRED FOR BOOTH |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2005-07-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-07-22 |
Time |
13:29 |
Rev Time |
0.81 |
| Received By |
kstevens |
Date |
2005-07-22 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2005-07-22 00:00:00 | DENIED | | | REFERENCE: FLORIDA AMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL ARCHITECTURAL SHEETS. FOLLOWING | | | INFORMATION IS REQUIRED IN THE TITLE | | | BLOCK: | | | A FIRM NAME, ADDRESS, AND PHONE NUMBER. | | | FAC 61G1-16.004(4) AND FS 481.2055 | | | 2. PIPING TRENCH REPAIR DETAIL SHEETS. | | | THE FOLLOWING INFORMATION IS REQUIRED IN | | | THE TITLE BLOCK: | | | A. FIRM NAME | | | B. A SPACE FOR THE PRINTED NAME OF THE | | | PERSON SEALING THE DOCUMENT. | | | FAC 61G1-16.004(1)(6). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-06-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-01 |
Time |
09:22 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2005-06-01 |
Time |
09:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-05-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-05-02 |
Time |
11:36 |
Rev Time |
1.86 |
| Received By |
kstevens |
Date |
2005-05-02 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2005-05-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW: | | | THE COMMENT NUMBER WILL REMAIN THE SAME | | | AS THE PREVIOUS REVIEW: | | | 3) SHT DA2.1 DEMO KEYNOTES D8 NOT FOUND | | | ON SHEET. PLEASE CORRELATE NOTES WITH | | | FLOOR PLAN. SECTION 104.2.1. - RESPONSE | | | NOTED, BUT CHANGE TO BE MADE ON PLANS | | | NOT ONLY ON COMMENT REPLY RESPONSE | | | SHEET. | | | 5) SHT A2.3 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS PER | | | SECTIONS 1106, & 1107 AND ALL | | | SUBSECTIONS. SHOW LOCATION OF SECONDARY | | | DRAINS FOR SOUTH PORTION. SHOW SIZE OF | | | PRIMARY ROOF DRAINS AND SECONDARY ROOF | | | DRAINS/SCUPPERS. SHOW SIZE OF GUTTERS | | | AND DOWNSPOUTS AND INDICATE AREA BEING | | | DRAINED BY EACH GUTTER AND DOWNSPOUT. | | | SHOW SQUARE FOOTAGE FOR EACH ROOF AREA | | | AND SHOW 1/2 AREA OF VERTICAL WALLS | | | INCLUDING PARAPETS ADDED TO SF OF ROOF | | | IN CALCULATIONS. SHOW SLOPE OF GUTTERS | | | AND THE HIGH POINT ON EACH GUTTER. - | | | RESPONSE NOTED, BUT PLANS INDICATE THAT | | | THE GUTTERS AND DOWNSPOUTS SHALL BE | | | REPLACED, AND SIZE OF EACH SHALL BE | | | INDICATED AND CALCULATIONS SHALL BE | | | GIVEN TO MAKE SURE SIZE OF GUTTERS AND | | | DOWNSPOUTS IS CORRECT PER SECTIONS 1106 | | | AND 1107. | | | 8) SHT P1.1 PLUMBING NOTES: #13 AIR | | | CHAMBERS ARE NOT APPROVED. DELETE FROM | | | REFERENCE. SECTION 604.9. #14 DIELECTRIC | | | UNIONS ARE NOT APPROVED FOR DISTRIBUTION | | | WATER. DIELECTRIC COUPLINGS ARE | | | APPROVED. - RESPONSE NOTED AND ITS | | | CORRECT THAT 604.9 DOES NOT PROHIBIT THE | | | USE OF AIR CHAMBERS, THE CITY OF WEST | | | PALM BEACH DOES NOT APPROVE OF AIR | | | CHAMBERS UNLESS THEY HAVE A "BLEED OFF | | | VALVE ON TOP OF THE AIR CHAMBER, A SHUT | | | OFF VALVE AT THE BASE OF THE AIR CHAMBER | | | AND A DRAIN VALVE TO DRAIN THE WATER | | | FROM THE AIR CHAMBER TO RECHARGE THE AIR | | | CHAMBER PER ATTACHED SHEET FROM PDI-WH | | | 201 REPORT. ALSO AN ACCESS PANEL FOR | | | EACH SET OF AIR CHAMBERS WILL BE | | | REQUIRED FOR ACCESS TO THE VALVES ON THE | | | AIR CHAMBERS. PDI-WH 201. - COMMENT #14 | | | RESPONSE NOTED - DIELECTRIC UNIONS ARE | | | NOT MADE FOR WATER DISTRIBUTION WATER, | | | SO A DIELECTRIC COUPLING SHALL BE USED. | | | 11) SHT P3.1 WATER PIPING DIAGRAM, AIR | | | CHAMBERS ON BREAK ROOM SINK ARE NOT | | | APPROVED. SECTION 604.9 DELETE FROM | | | DIAGRAM. - RESPONSE NOTED. SEE COMMENT | | | #8 AND IF THE VALVES, (3 EACH AIR | | | CHAMBER), AND ACCESS PANEL WILL BE USED | | | THAN THE AIR CHAMBERS WILL BE ALLOWED. | | | PDI-WH 201. | | | 13) ALL SHEETS SIGNED/SEALED/DATED BY AN | | | ARCHITECT SHALL SHOW FIRM LICENSE NUMBER | | | CERTIFICATE OF AUTHORIZATION. FAC | | | 61G1-16.004(2) AND FS 481.219. - | | | RESPONSE NOTED, BUT THE CA OR BUSINESS | | | NUMBER IS NOT SHOWN IN THE TITLE BLOCK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-03-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-03-16 |
Time |
15:35 |
Rev Time |
3.25 |
| Received By |
kstevens |
Date |
2005-03-16 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2005-03-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT A0.1 SHEET INDEX SHOWS CAR WASH | | | DRAWINGS. THESE DRAWINGS WERE NOT | | | LOCATED. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | 2) SHT DA2.1 DEMO KEYNOTES D8 NOT FOUND | | | ON SHEET. PLEASE CORRELATE NOTES WITH | | | FLOOR PLAN. SECTION 104.2.1. | | | 3) SHT A2.1 SHOW CLEAR FLOOR SPACE FOR | | | ACCESSIBLE URINAL AND BREAK ROOM SINK. | | | (FORWARD APPROACH FOR SINK REQUIRED, | | | MAXIMUM 19" UNDERNEATH SINK) SECTIONS | | | 11-4.18.3 & 11-4.19.3. | | | 4) SHT A2.1 DRINKING FOUNTAIN REQUIRED | | | PER TABLE 403.1. | | | 5) SHT A2.3 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS PER | | | SECTIONS 1106 & 1107 AND ALL | | | SUBSECTIONS. SHOW LOCATION OF SECONDARY | | | DRAINS FOR SOUTH PORTION. SHOW SIZE OF | | | PRIMARY ROOF DRAINS AND SECONDARY ROOF | | | DRAINS/SCUPPERS. SHOW SIZE OF GUTTERS | | | AND DOWNSPOUTS AND INDICATE AREA BEING | | | DRAINED BY EACH GUTTER AND DOWNSPOUT. | | | SHOW SQUARE FOOTAGE FOR EACH ROOF AREA | | | AND SHOW 1/2 AREA OF VERTICAL WALLS | | | INCLUDING PARAPETS ADDED TO SF OF ROOF | | | IN CALCULATIONS. SHOW SLOPE OF GUTTERS | | | AND THE HIGH SPOT ON EACH GUTTER. | | | 6) SHT A9.1 THE FOLLOWING INFORMATION TO | | | BE SHOWN ON THE ACCESSABILITY DETAIL #12 | | | FLUSH CONTROLS 11-4.16.5 (W/C) AND | | | 11-4.18.4 (URINAL). | | | 7) SHT P1.1 PARTIAL PLUMBING SITE PLAN, | | | BACKFLOW SHALL BE AT LEAST THE SAME SIZE | | | AS THE LINE IN WHICH THEY ARE INSTALLED. | | | TABLE 603.1 FOOTNOTE "D". | | | 8) SHT P1.1 PLUMBING NOTES: #13 AIR | | | CHAMBERS ARE NOT APPROVED. DELETE FROM | | | REFERENCE. SECTION 604.9 - #14 | | | DIELECTRIC UNIONS ARE NOT APPROVED FOR | | | DISTRIBUTION WATER. DIELECTRIC UNIONS | | | APPROVED. | | | 9) SHT P1.1 KEY NOTES #11 IN THE REMOVAL | | | OF ANY PART OF A DRAINAGE SYSTEM, DEAD | | | ENDS SHALL BE PROHIBITED. SECTION 704.5. | | | 10) CONDENSATE DRAINING INTO THE GUTTER | | | FOR THE ROOF STORM WATER SHALL NOT | | | DISCHARGE INTO A STREET, ALLEY OR OTHER | | | AREAS SO AS TO CAUSE A SUISANCE. PLEASE | | | INDICATE IF THE DISCHARGE OF THE | | | DOWNSPOUST WILL BE INTO AREAS THAT WILL | | | PERCOLATE INTO THE GROUND. SECTION | | | M307.2.1(3) | | | 11) SHT P3.1 WATER PIPING DIAGRAM, AIR | | | CHAMBERS ON BREAK ROOM SINK ARE NOT | | | APPROVED. SECTION 604.9. DELETE FROM | | | DIAGRAM. - SHOW THE SHUT OFF VALVE FOR | | | THE HOSE BIBB. SECTION 606.2(2) - FULL | | | OPEN VALVE REQUIRED ON ALL WATER | | | DOWN-FEED PIPE. SECTION 606.1(4). | | | 12) SHT P3.1 SUBMIT MANUF. SPECIFICATION | | | SHEETS FOR INSTA-HOT WATER HEATER TO | | | SHOW LISTING. | | | 13) ALL SHEETS SIGNED/SEALED/DATED BY AN | | | ARCHITECT SHALL SHOW FIRM LICENSE NUMBER | | | CERTIFICATE OF AUTHORIZATION & PRINTED | | | NAME OF THE PERSON SEALING THE DOCUMENT. | | | FAC 61G1-16.004(2)(6) & FS 481.219 FS | | | 481.2055. | | | 14) ALL SHEETS SIGNED/SEALED/DATED BY AN | | | ENGINEER SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS, AND LICENSE NUMBER ON | | | EACH SHEET. IF PRACTICION THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS, LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS, AND CERTIFICATE | | | OF AUTHROIZATION NUMBER OF THE | | | ENGINEERING BUSINESS ON EACH SHEET. FAC | | | 61G15-23.002(2) & FS 471.2055 (PME | | | SHEETS OK) SEE C-1 & C-2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2005-11-14 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-11-14 |
Time |
11:39 |
Rev Time |
0.01 |
| Received By |
mmclean |
Date |
2005-11-14 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2005-11-14 00:00:00 | ZONING ALREADY REVIEWED AND APPROVE | | | PLANS ON 3/31/05, ONLY REVIEWERS NEEDED | | | IS BLDG & ELECTRICAL. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-03-31 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-03-31 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-03-31 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2005-03-31 00:00:00 | APPROVED BY GRACE JOYCE,PLANNER | | | 822-1447. |
|
|