Plan Review Details - Permit 05021334
Plan Review Stops For Permit 05021334
Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2005-11-16 Cont ID  
Sent By lmartine Date 2005-11-16 Time 10:24 Rev Time 0.00
Received By lmartine Date 2005-11-16 Time 10:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2005-11-07 Cont ID  
Sent By shill Date 2005-11-07 Time 18:44 Rev Time 0.50
Received By shill Date 2005-11-07 Time 18:44 Sent To Z
Notes
2005-11-07 00:00:00****CORRECTIONS****
 ****PLAN REVIEW IN PROGRESS***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE FOUNDATION OR ANCHORING
 DETAIL FOR THE ATTENDANT BOOTH.
  
 2.)PROVIDE A SITE PLAN SHOWING WHERE
 THE ATTENDANT BOOTH WILL BE INSTALLED
  
 3.)FEES DUE (REVISION, NOT A
 SUBMITTAL).

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2005-11-07 Cont ID  
Sent By shill Date 2005-11-07 Time 18:44 Rev Time 0.00
Received By shill Date 2005-11-07 Time 18:44 Sent To  
Notes
2005-11-07 00:00:00LIGHT POLE CALCS AND SPEC SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2005-10-03 Cont ID  
Sent By shill Date 2005-10-03 Time 16:28 Rev Time 0.50
Received By shill Date 2005-10-03 Time 16:28 Sent To PC
Notes
2005-10-03 00:00:00****CORRECTIONS****
 LIGHT POLE CALCS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THERE ARE STILL MANY REFERENCES TO
 OTHER BUILDING CODES (INCLUDING A
 NONEXISTANT ONE) - IBC, 2000FBC, UBC.
 PLEASE REVISE AND HAVE ALL CODE
 REFERENCES REFER TO THE APPLICABLE
 SECTION OF THE FBC2001.
  
 2.)A REQUEST WAS MADE FOR THE FIXTURE
 CALCS AS WELL AS THE POLE CALCS.PLEASE
 PROVIDE.
  
 3.)ALL SUBMITTALS ARE TO BE REVIEWED
 BY DESIGNER OF RECORD PRIOR TO SUBMITTAL
 TO THE CITY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status F Date 2005-09-20 Cont ID  
Sent By shill Date 2005-09-20 Time 08:36 Rev Time 0.50
Received By shill Date 2005-09-20 Time 08:36 Sent To  
Notes
2005-09-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER
 SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED AND DATED ORIGINALS,
 FAC61G15-23.
  
 2.) A TITLE BLOCK INCLUDING ALL
 INFORMATION REQUIRED BY FAC61G15-23.002
 IS REQUIRED.THE ADDRESS FOR ACCORD
 INDUSTRIES DOES NOT MATCH THE DPBR
 WEBSITE FOR THIS ENGINEER.
  
 3.)THERE ARE SEVERAL REFERENCES TO THE
 IBC.GOVERNING CODE IS FBC, PLEASE
 EITHER PROVIDE EQUIVALENT IN FBC OR
 INCLUDE SPECIFICATION OR DETAIL.
  
 4.)NOTE 1 STATES THAT NO SOILS REPORT
 WAS AVAILABLE.REMOVE THIS NOTE AS A
 SOILS REPORT IS AVAILABLE, PLEASE
 CONTACT GENERAL CONTRACTOR.
  
 5.)NOTE 2, FBC1806.8.2.1 IS NOT IN THE
 FBC.
  
 6.)NOTE 5, THE FAC RULE REFERRED TO
 HAS BEEN REPEALED.
  
 7.)PLEASE NOTE THAT THE FIXTURE CALCS
 ARE REQUIRED.THE DETAIL, DESIGN
 CRITERIA AND CALCS WERE FOR THE POLE
 ONLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2005-09-16 Cont ID  
Sent By shill Date 2005-09-16 Time 11:59 Rev Time 0.00
Received By shill Date 2005-09-16 Time 11:59 Sent To  
Notes
2005-09-16 00:00:00REVISED A2.1 DATED9/14/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2005-09-14 Cont ID  
Sent By shill Date 2005-09-14 Time 11:00 Rev Time 1.00
Received By shill Date 2005-09-14 Time 11:00 Sent To  
Notes
2005-09-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)REVISE ALL SHEETS AFFECTED BY THE
 REVISION SUBMITTED - SITE PLAN, A0.1,
 ANY OTHER SHEETS AFFECTED BY THE
 PROPOSED KIOSK OR RAMP DETAIL.
  
 2.)8 1/2 X 11 SHEETS CAN BE SUBMITTED
 AS SUPPLEMENTARY OR ALTERNATE DETAILS
 BUT REVISIONS TO THE BUILDING PLANS
 SHOULD REVISED ALL AFFECTED SHEETS.
  
 3.)DIMENSIONS ON A0.1 SHOWING CODE
 COMPLIANCE FOR THE RAMP WERE NOT ON THE
 DETAIL PROVIDED.WHEN REVISING A0.1
 PLEASE INCLUDE ALL NECESSARY DIMENSIONS.
  
 4.)SHOW THE MANEUVERING CLEARANCE FOR
 THE BREAK ROOM DOOR, FBC11 FIGURE 25.
  
 5.)PROVIDE OPENING WIDTH BETWEEN THE
 BLOCK WALLS LEADING TO THE RAMP.
  
 6.)SEPARATE PERMIT REQUIRED FOR THE
 PREFAB KIOSK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2005-08-29 Cont ID  
Sent By shill Date 2005-08-29 Time 10:32 Rev Time 0.00
Received By shill Date 2005-08-29 Time 10:19 Sent To  
Notes
2005-08-29 00:00:00DOOR HARDWARE SUBMITTAL
 DOOR SHOPS AND PRODUCT APPROVALS
 ONE SET REMOVED FROM PACKAGE AND FILED

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2005-08-18 Cont ID  
Sent By shill Date 2005-08-18 Time 13:05 Rev Time 0.25
Received By shill Date 2005-08-18 Time 13:05 Sent To  
Notes
2005-08-18 00:00:00ALTERNATE DOOR FRAME DETAIL PREPARED BY
 PEDRO DE FIGUERIEREDO, REVIEWED BY EOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2005-08-18 Cont ID  
Sent By shill Date 2005-08-18 Time 09:53 Rev Time 0.00
Received By shill Date 2005-08-18 Time 09:53 Sent To  
Notes
2005-08-18 00:00:00SOIL DENSITY REPORT
 PREPARED BY NUTTING ENGINEERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2005-08-10 Cont ID  
Sent By shill Date 2005-08-10 Time 18:19 Rev Time 0.00
Received By shill Date 2005-08-10 Time 18:19 Sent To  
Notes
2005-08-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE WALL RAIL IS TO HAVE 18"
 EXTENSIONS, FBC11-4.84.5(2).THE DETAIL
 REFERS TO ADA; PLEASE NOTE THAT FLORIDA
 USES FBC CHAPTER 11 WHICH IS MORE
 STRINGENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-08-10 Cont ID  
Sent By shill Date 2005-08-10 Time 18:16 Rev Time 0.00
Received By shill Date 2005-08-10 Time 18:16 Sent To  
Notes
2005-08-10 00:00:00VARIOUS DETAILS 8/8/05
  
 REVISED DOOR SCHEDULE
 PIPING TRENCH REPAIR DETAIL
 AD-1.4
 AD-1.5
 AD-1.6

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-08-10 Cont ID  
Sent By shill Date 2005-08-10 Time 17:55 Rev Time 0.00
Received By shill Date 2005-08-10 Time 17:55 Sent To  
Notes
2005-08-10 00:00:00REVISED A0.1 TO SERVE AS INDEX SHEET FOR
 ENTIRE PLAN (CORRECTED DATE)
 NEW A1.3 (NEW RAMP/ACCESSIBLE ENTRANCE)

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-08-10 Cont ID  
Sent By shill Date 2005-08-10 Time 17:46 Rev Time 0.00
Received By shill Date 2005-08-10 Time 17:46 Sent To  
Notes
2005-08-10 00:00:00****CORRECTIONS****
 DRAWING 05-245A PREPARED BY PEDRO DE
 FIGUEIREDO PE
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE ENGINEER WHO PREPARED THIS
 DETAIL ON SHEET A4.1 IS JIM NADASKAY,
 PE.ANOTHER ENGINEER CANNOT MODIFY THIS
 DESIGN UNLESS IT IS DELEGATED
 ENGINEERING.EITHER HAVE THIS DETAIL
 INCORPORATED INTO MR. NADASKAY'S PLAN OR
 HAVE REVIEWED BY MR. NADASKAY, ENGINEER
 OF RECORD.
  
 2.)THE SUBMITTAL STATES "USE IN
 CONJUNCTION WITH DRAWINGS 05-245".IF
 YOU RESUBMIT THIS DETAIL, SUBMIT
 REFERRED DRAWING.
  
 3.)SHEET A-4.1 WAS NOT SIGNED AND
 SEALED.PLEASE SUBMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-08-10 Cont ID  
Sent By shill Date 2005-08-10 Time 17:35 Rev Time 0.50
Received By shill Date 2005-08-10 Time 17:35 Sent To  
Notes
2005-08-10 00:00:00****CORRECTIONS****
 SOILS ENGINEERING
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) SOILS REPORT TO BE REVIEWED BY
 DESIGNER OF RECORD.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-07-23 Cont ID  
Sent By shill Date 2005-07-23 Time 21:37 Rev Time 1.00
Received By shill Date 2005-07-23 Time 21:35 Sent To  
Notes
2005-07-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SHEET AD-1.1 IS TO HAVE A TITLE
 BLOCK WITH ALL INFORMATION REQUIRED BY
 FAC61G1-16.
  
 2.)CA NUMBER REQUIRED FOR THE
 ARCHITECT BUSINESS, FAC61G1-16.
  
 3.)BLUNK DEMATTEI ASSOCIATES IS NOT
 THE DOR FOR THIS JOB.MR. DEMATTEI IS
 DOR AS AN INDIVIDUAL.IF YOU WOULD LIKE
 TO CHANGE DOR TO THE COMPANY PLEASE READ
 FAC61G1-18 AND ADDRESS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-20 Cont ID  
Sent By shill Date 2005-07-20 Time 09:57 Rev Time 0.50
Received By shill Date 2005-07-20 Time 09:57 Sent To PC
Notes
2005-07-20 00:00:00REVISION DATED 6/30, CANOPY

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-05-31 Cont ID  
Sent By shill Date 2005-05-31 Time 11:28 Rev Time 3.00
Received By shill Date 2005-05-31 Time 10:06 Sent To P
Notes
2005-05-31 00:00:00***PROVISO***
 PROVIDE INDEX SHEET AND LETTER REGARDING
 DATE ON PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-05 Cont ID  
Sent By shill Date 2005-05-05 Time 15:19 Rev Time 2.00
Received By shill Date 2005-05-05 Time 15:19 Sent To  
Notes
2005-05-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SHEET 1 ISN'T SEALED.IT SERVES
 NOT ONLY AS A COVER SHEET BUT ALSO
 DECLARES CODE COMPLIANCE FOR OCCUPANCY,
 ETC. (PROJECT DATA).
  
 2.)BUSINESSES PRACTICING ARCHITECTURE
 IN FLORIDA ARE TO HAVE A CERTIFICATE OF
 AUTHORIZATION NUMBER AND INCLUDE THIS
 NUMBER ON THE TITLE BLOCK, FAC61G1-16.
  
 3.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 TEST REPORTS PROVIDED, FAC9B72.SEE
 WWW.FLORIDABUILDING.ORG.
  
 10.)PRODUCT APPROVALS WERE NOT
 PROVIDED FOR THE CANOPY STEEL ROOF DECK.
 THE ENGINEER FOR THE ROOF DECK INDICATED
 THAT THEY WOULD BE PROVIDED BUT THEY
 WERE NOT INCLUDED IN THE PACKAGE.
 FAC9B72.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-18 Cont ID  
Sent By shill Date 2005-03-18 Time 10:58 Rev Time 4.00
Received By shill Date 2005-03-17 Time 15:01 Sent To  
Notes
2005-03-18 00:00:00PERMIT #05021334
 ****PAID PLAN CHECK****
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.) THE OWNER IN OUR RECORDS
 (PRESIDENTIAL MOTORS) CONFLICTS WITH THE
 PERMIT APPLICATION.
  
 4.) A0.1 REFERS TO ?WEST PALM BEACH
 COUNTY BUILDING CODE?.GOVERNING CODE
 IS FBC2001 WITH 2003 AMENDMENTS AND CITY
 OF WEST PALM BEACH AMENDMENTS.
  
 5.) CERTIFICATE OF AUTHORIZATION
 REQUIRED FOR ENGINEERS AND ARCHITECTS;
 TITLE BLOCKS TO BE IN COMPLIANCE WITH
 BOARD RULES, FAC61G15-23.002,
 FAC61G1-16.003,004.PLEASE CHECK ALL
 SHEETS, INCLUDING CALCULATIONS.
  
 6.) AWNING SHEETS (AB) AND CALCULATIONS
 DECLARE A ?WIND LOAD? OF 130MPH; CITY OF
 WEST PALM BEACH IS IN THE 140 MPH WIND
 ZONE.
  
 7.) C2, ACCESSIBLE PARKING IS TO COMPLY
 WITH CITY OF WEST PALM BEACH STANDARDS,
 SEE ATTACHED.
  
 8.) A1.1 REFERS TO DETAIL 12-A1.2,
 DUMPSTER ENCLOSURE PLAN.DETAIL IS NOT
 WHERE NOTED.
  
 9.) PROVIDE AREA CALCULATIONS; EXISTING,
 PROPOSED, NEW TOTAL.
  
 10.) FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO TEST
 REPORTS.WWW.FLORIDABUILDING.ORG.
 STOREFRONT SYSTEM
 IMPACT PROTECTION
 STEEL ROOF DECK
 EXTERIOR DOOR
  
 11.) IF REMOVABLE SHUTTERS ARE USED IN
 LIEU OF IMPACT GLASS, PROVIDE
 INFORMATION IN REGARDS TO WHERE THE
 SHUTTERS WILL BE STORED.
  
 12.) PROVIDE WALL DIMENSION FOR DOOR 11,
 SHEET A2.1, PUSH SIDE, SEE FBC CHAPTER
 11 TABLE 25 (A).
  
 13.) DETAIL 3-A4.1, PROVIDE FASTENING OF
 WOOD BLOCKING TO COLUMNS.
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2005-11-07 Cont ID  
Sent By dpalmer Date 2005-11-07 Time 16:50 Rev Time 0.50
Received By dpalmer Date 2005-11-07 Time 16:50 Sent To B
Notes
2005-11-07 00:00:00REVISED LOAD CALCULATIONS TO DECREASE
 SITE LIGHTING WATTAGE.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2005-09-28 Cont ID  
Sent By dpalmer Date 2005-09-28 Time 13:14 Rev Time 0.00
Received By dpalmer Date 2005-09-28 Time 13:16 Sent To  
Notes
2005-09-28 00:00:00***** UNSAT *****
  
  
  
 POLE CALCUALTIONS SUBMITTED STILL DO NOT
 APPEAR TO MEET PREVIOUS REQUESTED
 INFORMATION.
 PLANS/ CALCS SUBMNITTED SENT TO BLDG
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-09-19 Cont ID  
Sent By dpalmer Date 2005-09-19 Time 08:41 Rev Time 0.00
Received By dpalmer Date 2005-09-19 Time 08:51 Sent To  
Notes
2005-09-19 00:00:00********* UNSAT *****************
  
  
  
 1)NOTE: PLEASE SEE AS PREVIOUSLY
 REQUESTED. PLEASE SUBMIT COMPLETE
 SIGNED, DATED AND SEALED WIND LOADING
 CALCULATIONS FOR NEW LT POLES AND
 FXTURES. PLEASE SEE NO LT FIXTURES
 INCLUDED IN CALCUALTIONS, AND
 INFORMATION SUBMITTED WAS NOT SIGNED ,
 DATED OR SEALED.
 FS 471.025, FAC 61G15-23.002
  
 ** PLEASE NOTE**
 WIND LOADING CALCS WILL BE REVIEWED BY
 STRUCTUAL REVIEWER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
 WIND LOAD CALCS SENT TO SH.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 09:47 Rev Time 0.40
Received By dpalmer Date 2005-09-03 Time 09:43 Sent To  
Notes
2005-09-03 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SUBMIT COMPLETE
 WINDLOADING CALCULATIONS FOR ALL SITE
 LIGHTING POLES AND FIXTURES.
 THIS WAS REQUESTED ON PREVIOUS REVIEWS
 AND REDLINED ON PREVIOUS SET.
 PLEASE SEE THAT ALL MUST MEET FBC
 140MPH.
  
 2)NOTE: PLEASE SEE THAT NEW KIOSK PANEL
 SHALL AHVE A MCB FOR MEANS OF DISCONNECT
 AS REQUIRD PER 225.31.
  
 3)NOTE: PLEASE INDICATE GROUNDING AT
 THIS DETACHED BLDG.
 250.32
  
 4)NOTE: PLEASE SEE SERVICE IS REQUIRED
 TO UPGRADES FROM THE 400A SHOWN.
 PLEASE SEE LOAD SHOWN AFTER TAKING
 PERMITTED DE-RATING EXCEEDS RATING OF
 SERVICE PROVIDED.
 240.4,310.16, 90.8 ETC.
  
 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 PERTAINING TO KIOSK AND INFORMATION
 REQUIRED FOR THIS BLDG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-08-15 Cont ID  
Sent By dpalmer Date 2005-08-15 Time 18:08 Rev Time 0.30
Received By dpalmer Date 2005-08-15 Time 18:08 Sent To  
Notes
2005-08-15 00:00:00REV FOR PVC UNDERGROUND CONDUITS AND
 AUTOMATED DOORS CUT SHEETS.
  
 REDLINED FBC 140 MPH FOR LT POLES.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 10:46 Rev Time 0.30
Received By dpalmer Date 2005-07-06 Time 10:45 Sent To  
Notes
2005-07-06 00:00:00REV TO ADD POWER ACTUATED DOORS.
  
  
 SEE A-SHEETS, DO NOT CONTAIN CA #'S PER
 FAC 61G1-16.004, FS 481.219

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-05-27 Cont ID  
Sent By btrobaug Date 2005-05-27 Time 12:26 Rev Time 0.75
Received By btrobaug Date 2005-05-27 Time 12:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-04-20 Cont ID  
Sent By dpalmer Date 2005-04-20 Time 14:36 Rev Time 1.00
Received By dpalmer Date 2005-04-20 Time 14:09 Sent To  
Notes
2005-04-20 00:00:00**** UNSAT 2ND REVIEW ****
  
 PLANS ONLY IN FOR "PLAN REVIEW" AND NOT
 SUBMITTED FOR PERMIT.
  
 1NOTE: NOTE #1, NO, PLEASE SEE SAME
 ELECTRICAL SHEET WITH OUT ANY REFERENCE
 TO FBC 140 MPH . PLEASE ALSO SEE WE
 COULD NOT LOCATE WIND LOADING
 CALCULATIONS.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE:NOTE #4 OK.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE RISER
 STILL SHOWS AN EQUIPMENT GROUNDING
 CONDUCTOR INSTALLED BEFORE THE FIRST
 MEANS OF DISCONNECT. 250.6,250.24.
  
 6)NOTE: NOTE #6 OK.
 OCP LOCATED AT PANEL.
  
 NEW NOTE:
 1)NOTE:PLEASE SEE ELECTRICAL REVIEW
 PREVIOUS NOTES MENTIONS TO SEE OTHER )
 PERTAINING TO POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S). PLEASE SEE NOTE #5
 FROM PREVIOUS BLDG REVIEW WHICH
 REFERENCE WAS GIVEN TO FAC 61G1-16.004
 AND FS 481.219 WITH INFORMATION REQUIRED
 ON TITLE BLOCKS.
 PLEASE SEE THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
 PLEASE SEE NONE OF THE TRADE SHEETS HAVE
 HAD TITLE BLOCKS CORRECTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-02 Cont ID  
Sent By dpalmer Date 2005-03-02 Time 07:26 Rev Time 1.00
Received By dpalmer Date 2005-03-02 Time 06:56 Sent To  
Notes
2005-03-02 00:00:00***** UNSAT *****
  
 ** PLEASE SEE PLANS ARE IN AS PROJECT
 FOR "PLAN REVIEW" ONLY NOT FOR PERMIT AT
 THIS TIME.
  
 1)NOTE: PLEASE SEE WIND LOADING FOR
 POLES/ FIXTURES FOR SITE LIGHTING IS
 REQUIRED AT THIS TIME FOR BLDG REVIEW.
 MIN REQUIREMENTS FOR FBC 140 MPH.
  
 2)NOTE:PLEASE SEE 300.22C FOR "AREAS
 USED FOR RETURN AIR"
 PLEASE SEE ALL UNDERGROUND CONDUITS
 ENTERING EQUIPMENT ETC OF PVC TYPE ARE
 NOT PERMITTED.
 PLEASE SPECIFY ON PLANS TYPE OF
 MATERIALS TO BE USED FOR CONDUIT ETC.
 IT IS NOTED OF MATERIALS TO BE RATED FOR
 PLENUM ABOVE CEILINGS.
  
 3)NOTE: PLEASE PROVIDE RECEPTS ABOVE
 "SHOW WINDOWS". 210.62 THIS IS TO
 DISCOURAGE FLOOR RECEPTACLES AND
 UNSIGHTLY EXTENSION CORDS LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE A SHOW
 WINDOW, AND ONE RECEPTACLE IS REQUIRED
 FOR EVERY 12 LINEAR FT OR ?MAJOR
 FRACTION THEREOF? (6 FT OR MORE). SEE
 220.3(B)(7) AND 220.12(A) FOR
 INFORMATION REGARDING LOAD COMPUTATIONS
 FOR SHOW WINDOWS.
  
 4)NOTE: PLEASE SEE HANDRAWN ITEMS ON
 PLANS WHICH ARE SIGNED, DATED AND SEALED
 BY AN ARCH OR ENG ARE NOT PERMITTED.
 FS 471.025,481.221
  
 5)NOTE: PLEASE SEE THERE IS AN EQUIPMENT
 GROUNDING CONDUCTOR SHOWN FROM METER TO
 THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24, THIS IS NOT
 PERMITTED . EQUIPMENT GRNDS ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNETC.
  
 6)NOTE: PLEASE VERFIY DISCONNECTING
 MEANS FOR WATER HEATER SHOWN UNDER SINK
 DOES NOT CONTAIN OCP.
 110.26 WOULD APPLY IF OCP IS PROVIDED.
 THIS IS ONLY A NOTE. DISC APPEARS NOT TO
 CONTAIN OCP.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-04-12 Cont ID  
Sent By mamini Date 2005-04-12 Time 14:41 Rev Time 0.50
Received By mamini Date 2005-04-12 Time 14:41 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-03-03 Cont ID  
Sent By mamini Date 2005-03-03 Time 09:56 Rev Time 1.00
Received By mamini Date 2005-03-03 Time 09:56 Sent To  
Notes
2005-03-03 00:00:00FAILED:
  
 1.APPROACHES TO THE SITE MUST BE
 CONSTRUCTED PER CITY OF WPB'S STANDARD
 AND REQUIREMENTS; 6" CONCRETE, FROM THE
 EDGE OF PAVEMENT TO THE PROPERTY LINE.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-09-01 Cont ID  
Sent By mwennerg Date 2005-09-01 Time 11:08 Rev Time 0.00
Received By mwennerg Date 2005-09-01 Time 11:08 Sent To  
Notes
2005-09-01 00:00:00DOOR AND HARDWARE SUBMITTAL 8/08/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-07-27 Cont ID  
Sent By mwennerg Date 2005-07-27 Time 14:38 Rev Time 0.00
Received By mwennerg Date 2005-07-27 Time 14:38 Sent To  
Notes
2005-07-27 00:00:00******PROVISO******
  
 PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC TITLE BLOCK
 REQUIREMENTS FOR ALL SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-28 Cont ID  
Sent By mwennerg Date 2005-04-28 Time 10:47 Rev Time 0.00
Received By mwennerg Date 2005-04-28 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-23 Cont ID  
Sent By mwennerg Date 2005-03-23 Time 14:52 Rev Time 0.00
Received By mwennerg Date 2005-03-23 Time 14:52 Sent To  
Notes
2005-03-23 00:00:001) THE ADDRESS NUMBER MUST BE LOCATED ON
 THE BUILDING NEAR THE FRONT ENTRANCE
 DOOR. THE NUMBERS SHALL BE AT LEAST 6"
 IN HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 2) PLEASE BE ADVISED THAT ALL LIFE
 SAFETY MUST COMPLY WITH NFPA 101, 2003
 EDITION AFTER JAN. 1, 2005.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910.

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 11:30 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 11:30 Sent To E
Notes
2005-10-17 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 11:30 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 11:30 Sent To E
Notes
2005-09-26 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 09:37 Sent To B
Notes
2005-09-21 00:00:00TO "NMELICK" DESK

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 15:03 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 15:03 Sent To B
Notes
2005-09-15 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 14:45 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 14:45 Sent To E
Notes
2005-09-15 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-09-15 Cont ID  
Sent By shill Date 2005-09-15 Time 13:28 Rev Time 0.00
Received By shill Date 2005-09-15 Time 13:26 Sent To PC
Notes
2005-09-15 00:00:00REVISION (#55 ON THE BOARD) PULLED AT
 CONTRACTOR/ARCHITECT REQUEST

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 10:03 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2005-09-03 00:00:00TO COMM BOARD #55

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-08-11 Cont ID  
Sent By adarroug Date 2005-08-11 Time 16:51 Rev Time 0.00
Received By adarroug Date 2005-08-11 Time 16:51 Sent To B
Notes
2005-08-11 00:00:00TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 16:50 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 16:50 Sent To B
Notes
2005-08-10 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 14:31 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 14:31 Sent To B
Notes
2005-08-09 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 08:56 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 08:55 Sent To B
Notes
2005-08-09 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 08:47 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 08:47 Sent To  
Notes
2005-08-09 00:00:00TO "COMM" BD#62

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 15:42 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 15:42 Sent To B
Notes
2005-07-07 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 11:28 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 11:28 Sent To  
Notes
2005-07-01 00:00:00TO "COMM" BD#29
2005-06-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-20 Cont ID  
Sent By adarroug Date 2005-05-20 Time 11:13 Rev Time 0.00
Received By adarroug Date 2005-05-20 Time 11:13 Sent To  
Notes
2005-05-31 00:00:00TO "COMM" BD#62
2005-05-20 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 11:42 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 11:42 Sent To  
Notes
2005-04-12 00:00:00TO "COMM" BD#51

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 08:27 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 08:27 Sent To Z
Notes
2005-03-29 00:00:00TO "Z" BOX/TAKEN FROM BD#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 14:53 Rev Time 0.00
Received By mmclean Date 2005-02-25 Time 11:41 Sent To  
Notes
2005-02-25 00:00:00TO "COMM" BD#13

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2005-11-16 Cont ID  
Sent By pkrauss Date 2005-11-16 Time 10:34 Rev Time 0.20
Received By pkrauss Date 2005-11-16 Time 10:34 Sent To  
Notes
2005-11-16 00:00:00REVISION FOR THE KIOSK IN THE PARKING
 GARAGE.WINDOW UNIT WILL BE INSTALLED
 NO MECHANICAL PERMIT REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2005-08-26 Cont ID  
Sent By hmoser Date 2005-08-26 Time 13:44 Rev Time 0.00
Received By hmoser Date 2005-08-26 Time 13:44 Sent To  
Notes
2005-08-26 00:00:00PLAN DENIED
 NEED TWO SETS OF PLANS SIGNED AND SEALED
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-07-27 Cont ID  
Sent By pkrauss Date 2005-07-27 Time 19:30 Rev Time 0.20
Received By pkrauss Date 2005-07-27 Time 19:20 Sent To  
Notes
2005-07-27 00:00:00NO MECHANICAL REVISIONS SUBMITTED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2005-05-17 Time   Rev Time 0.00
Received By hmoser Date 2005-05-17 Time 16:55 Sent To  
Notes
2005-05-17 00:00:00SEE PROVISO FRON REVIEW ON 3/21/05
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-03-21 Cont ID  
Sent By pkrauss Date 2005-03-21 Time 09:05 Rev Time 0.55
Received By pkrauss Date 2005-03-21 Time 08:26 Sent To  
Notes
2005-03-21 00:00:00PROVISO:
 1.FRESH AIR INTAKES SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM PARKING LOTS PER
 2001 FBC/M 401.5.1.
  
 2.RTU CURBS SHALL BE A MINIMUM OF 8"
 ABOVE THE ROOF SURFACE IN ACCORDANCE
 WITH 2001 FBC 1511.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 5 Status N Date 2005-11-16 Cont ID  
Sent By lmartine Date 2005-11-16 Time 10:43 Rev Time 0.00
Received By lmartine Date 2005-11-16 Time 10:43 Sent To  
Notes
2005-11-16 00:00:00NOT REQUIRED FOR BOOTH

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-07-22 Cont ID  
Sent By kstevens Date 2005-07-22 Time 13:29 Rev Time 0.81
Received By kstevens Date 2005-07-22 Time 13:29 Sent To  
Notes
2005-07-22 00:00:00DENIED
 REFERENCE: FLORIDA AMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. FOLLOWING
 INFORMATION IS REQUIRED IN THE TITLE
 BLOCK:
 A FIRM NAME, ADDRESS, AND PHONE NUMBER.
 FAC 61G1-16.004(4) AND FS 481.2055
 2. PIPING TRENCH REPAIR DETAIL SHEETS.
 THE FOLLOWING INFORMATION IS REQUIRED IN
 THE TITLE BLOCK:
 A. FIRM NAME
 B. A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 FAC 61G1-16.004(1)(6).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-06-01 Cont ID  
Sent By kstevens Date 2005-06-01 Time 09:22 Rev Time 2.00
Received By kstevens Date 2005-06-01 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-05-02 Cont ID  
Sent By kstevens Date 2005-05-02 Time 11:36 Rev Time 1.86
Received By kstevens Date 2005-05-02 Time 11:36 Sent To  
Notes
2005-05-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 THE COMMENT NUMBER WILL REMAIN THE SAME
 AS THE PREVIOUS REVIEW:
 3) SHT DA2.1 DEMO KEYNOTES D8 NOT FOUND
 ON SHEET. PLEASE CORRELATE NOTES WITH
 FLOOR PLAN. SECTION 104.2.1. - RESPONSE
 NOTED, BUT CHANGE TO BE MADE ON PLANS
 NOT ONLY ON COMMENT REPLY RESPONSE
 SHEET.
 5) SHT A2.3 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS. SHOW LOCATION OF SECONDARY
 DRAINS FOR SOUTH PORTION. SHOW SIZE OF
 PRIMARY ROOF DRAINS AND SECONDARY ROOF
 DRAINS/SCUPPERS. SHOW SIZE OF GUTTERS
 AND DOWNSPOUTS AND INDICATE AREA BEING
 DRAINED BY EACH GUTTER AND DOWNSPOUT.
 SHOW SQUARE FOOTAGE FOR EACH ROOF AREA
 AND SHOW 1/2 AREA OF VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO SF OF ROOF
 IN CALCULATIONS. SHOW SLOPE OF GUTTERS
 AND THE HIGH POINT ON EACH GUTTER. -
 RESPONSE NOTED, BUT PLANS INDICATE THAT
 THE GUTTERS AND DOWNSPOUTS SHALL BE
 REPLACED, AND SIZE OF EACH SHALL BE
 INDICATED AND CALCULATIONS SHALL BE
 GIVEN TO MAKE SURE SIZE OF GUTTERS AND
 DOWNSPOUTS IS CORRECT PER SECTIONS 1106
 AND 1107.
 8) SHT P1.1 PLUMBING NOTES: #13 AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE. SECTION 604.9. #14 DIELECTRIC
 UNIONS ARE NOT APPROVED FOR DISTRIBUTION
 WATER. DIELECTRIC COUPLINGS ARE
 APPROVED. - RESPONSE NOTED AND ITS
 CORRECT THAT 604.9 DOES NOT PROHIBIT THE
 USE OF AIR CHAMBERS, THE CITY OF WEST
 PALM BEACH DOES NOT APPROVE OF AIR
 CHAMBERS UNLESS THEY HAVE A "BLEED OFF
 VALVE ON TOP OF THE AIR CHAMBER, A SHUT
 OFF VALVE AT THE BASE OF THE AIR CHAMBER
 AND A DRAIN VALVE TO DRAIN THE WATER
 FROM THE AIR CHAMBER TO RECHARGE THE AIR
 CHAMBER PER ATTACHED SHEET FROM PDI-WH
 201 REPORT. ALSO AN ACCESS PANEL FOR
 EACH SET OF AIR CHAMBERS WILL BE
 REQUIRED FOR ACCESS TO THE VALVES ON THE
 AIR CHAMBERS. PDI-WH 201. - COMMENT #14
 RESPONSE NOTED - DIELECTRIC UNIONS ARE
 NOT MADE FOR WATER DISTRIBUTION WATER,
 SO A DIELECTRIC COUPLING SHALL BE USED.
 11) SHT P3.1 WATER PIPING DIAGRAM, AIR
 CHAMBERS ON BREAK ROOM SINK ARE NOT
 APPROVED. SECTION 604.9 DELETE FROM
 DIAGRAM. - RESPONSE NOTED. SEE COMMENT
 #8 AND IF THE VALVES, (3 EACH AIR
 CHAMBER), AND ACCESS PANEL WILL BE USED
 THAN THE AIR CHAMBERS WILL BE ALLOWED.
 PDI-WH 201.
 13) ALL SHEETS SIGNED/SEALED/DATED BY AN
 ARCHITECT SHALL SHOW FIRM LICENSE NUMBER
 CERTIFICATE OF AUTHORIZATION. FAC
 61G1-16.004(2) AND FS 481.219. -
 RESPONSE NOTED, BUT THE CA OR BUSINESS
 NUMBER IS NOT SHOWN IN THE TITLE BLOCK.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-16 Cont ID  
Sent By kstevens Date 2005-03-16 Time 15:35 Rev Time 3.25
Received By kstevens Date 2005-03-16 Time 15:35 Sent To  
Notes
2005-03-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A0.1 SHEET INDEX SHOWS CAR WASH
 DRAWINGS. THESE DRAWINGS WERE NOT
 LOCATED. PLEASE CLARIFY. SECTION
 104.2.1.
 2) SHT DA2.1 DEMO KEYNOTES D8 NOT FOUND
 ON SHEET. PLEASE CORRELATE NOTES WITH
 FLOOR PLAN. SECTION 104.2.1.
 3) SHT A2.1 SHOW CLEAR FLOOR SPACE FOR
 ACCESSIBLE URINAL AND BREAK ROOM SINK.
 (FORWARD APPROACH FOR SINK REQUIRED,
 MAXIMUM 19" UNDERNEATH SINK) SECTIONS
 11-4.18.3 & 11-4.19.3.
 4) SHT A2.1 DRINKING FOUNTAIN REQUIRED
 PER TABLE 403.1.
 5) SHT A2.3 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW LOCATION OF SECONDARY
 DRAINS FOR SOUTH PORTION. SHOW SIZE OF
 PRIMARY ROOF DRAINS AND SECONDARY ROOF
 DRAINS/SCUPPERS. SHOW SIZE OF GUTTERS
 AND DOWNSPOUTS AND INDICATE AREA BEING
 DRAINED BY EACH GUTTER AND DOWNSPOUT.
 SHOW SQUARE FOOTAGE FOR EACH ROOF AREA
 AND SHOW 1/2 AREA OF VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO SF OF ROOF
 IN CALCULATIONS. SHOW SLOPE OF GUTTERS
 AND THE HIGH SPOT ON EACH GUTTER.
 6) SHT A9.1 THE FOLLOWING INFORMATION TO
 BE SHOWN ON THE ACCESSABILITY DETAIL #12
 FLUSH CONTROLS 11-4.16.5 (W/C) AND
 11-4.18.4 (URINAL).
 7) SHT P1.1 PARTIAL PLUMBING SITE PLAN,
 BACKFLOW SHALL BE AT LEAST THE SAME SIZE
 AS THE LINE IN WHICH THEY ARE INSTALLED.
 TABLE 603.1 FOOTNOTE "D".
 8) SHT P1.1 PLUMBING NOTES: #13 AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE. SECTION 604.9 - #14
 DIELECTRIC UNIONS ARE NOT APPROVED FOR
 DISTRIBUTION WATER. DIELECTRIC UNIONS
 APPROVED.
 9) SHT P1.1 KEY NOTES #11 IN THE REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD
 ENDS SHALL BE PROHIBITED. SECTION 704.5.
 10) CONDENSATE DRAINING INTO THE GUTTER
 FOR THE ROOF STORM WATER SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER
 AREAS SO AS TO CAUSE A SUISANCE. PLEASE
 INDICATE IF THE DISCHARGE OF THE
 DOWNSPOUST WILL BE INTO AREAS THAT WILL
 PERCOLATE INTO THE GROUND. SECTION
 M307.2.1(3)
 11) SHT P3.1 WATER PIPING DIAGRAM, AIR
 CHAMBERS ON BREAK ROOM SINK ARE NOT
 APPROVED. SECTION 604.9. DELETE FROM
 DIAGRAM. - SHOW THE SHUT OFF VALVE FOR
 THE HOSE BIBB. SECTION 606.2(2) - FULL
 OPEN VALVE REQUIRED ON ALL WATER
 DOWN-FEED PIPE. SECTION 606.1(4).
 12) SHT P3.1 SUBMIT MANUF. SPECIFICATION
 SHEETS FOR INSTA-HOT WATER HEATER TO
 SHOW LISTING.
 13) ALL SHEETS SIGNED/SEALED/DATED BY AN
 ARCHITECT SHALL SHOW FIRM LICENSE NUMBER
 CERTIFICATE OF AUTHORIZATION & PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT.
 FAC 61G1-16.004(2)(6) & FS 481.219 FS
 481.2055.
 14) ALL SHEETS SIGNED/SEALED/DATED BY AN
 ENGINEER SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICION THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE
 OF AUTHROIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.2055 (PME
 SHEETS OK) SEE C-1 & C-2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2005-11-14 Cont ID  
Sent By mmclean Date 2005-11-14 Time 11:39 Rev Time 0.01
Received By mmclean Date 2005-11-14 Time 11:39 Sent To  
Notes
2005-11-14 00:00:00ZONING ALREADY REVIEWED AND APPROVE
 PLANS ON 3/31/05, ONLY REVIEWERS NEEDED
 IS BLDG & ELECTRICAL.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-31 Cont ID  
Sent By mmclean Date 2005-03-31 Time 14:51 Rev Time 0.00
Received By mmclean Date 2005-03-31 Time 15:25 Sent To  
Notes
2005-03-31 00:00:00APPROVED BY GRACE JOYCE,PLANNER
 822-1447.