| Plan Review Stops For Permit 05021306 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-04-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-04-21 |
Time |
11:15 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-04-21 |
Time |
11:15 |
Sent To |
PC |
|
| Notes |
| 2005-04-21 00:00:00 | PROVISO - SHUTTERS, IMPACT FRENCH DOOR | | | SEPARATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-04-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-04-21 |
Time |
09:42 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-04-21 |
Time |
09:42 |
Sent To |
PC |
|
| Notes |
| 2005-04-21 00:00:00 | ****CORRECTIONS**** | | | TRUSS ENGINEERING | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SEE ATTACHED FAC61G15-31.003.EACH | | | SHEET IS TO INCLUDE A TITLE BLOCK.SOME | | | SHEETS ARE LACKING A TITLE BLOCK; OTHERS | | | HAVE A DIFFERENT ENGINEER'S NAME. | | | | | | 2.)FAC61G15-31.003(5)(E), IF YOU ARE | | | USING A SEALED COVER/INDEX SHEET THE | | | INDEX IS TO BE A PART OF THAT | | | COVER/INDEX SHEET.THE INDEX IS NOT | | | SIGNED/SEALED AND IS NOT INCORPORATED | | | INTO THE FIRST PAGE WHICH IS | | | SIGNED/SEALED. | | | | | | 3.)THE TRUSS PLACEMENT DRAWING IS NOW | | | SIGNED BY THE ENGINEER, SW WARTER, BUT | | | AN INK SEAL IS NOT ACCEPTABLE.THE SEAL | | | IS TO BE A METAL-TYPE IMPRESSION SEAL, | | | FAC61G15-23.001. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-03-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-18 |
Time |
13:04 |
Rev Time |
4.00 |
| Received By |
shill |
Date |
2005-03-18 |
Time |
13:04 |
Sent To |
PC |
|
| Notes |
| 2005-03-18 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE SURVEY AND SITE PLAN DO NOT | | | MATCH. | | | | | | 2.)SEE FBC1005.4.5 IN REGARDS TO A | | | MEANS OF ESCAPE IN THE EVENT OF A STORM. | | | ALL DOORS ON THE PLAN ARE NON-IMPACT | | | GLASS.PROVIDE AT LEAST ONE MEANS OF | | | ESCAPE, INDICATE ON THE PLAN, AND | | | PROVIDE COMPLIANT PRODUCT APPROVAL. | | | | | | 3.)SEPARATE PERMIT REQUIRED FOR | | | SHUTTERS AS NO SHUTTER INFORMATION HAS | | | BEEN SUBMITTED AND IMPACT PROTECTION | | | REQUIRED FBC1606.1.4. | | | | | | 4.)PROVIDE FIRE RATING INFORMATION FOR | | | THE GLASS BLOCK IF INSTALLED 0'-3' FROM | | | THE PROPERTY LINE. | | | | | | 5.)THE FLORIDA STATE PRODUCT APPROVAL | | | SUBMITTED FOR THE "A & P CUSTOM WINDOW" | | | (FIXED) IS PENDING.PROVIDE A CURRENT, | | | APPROVED STATE OR LOCAL PRODUCT | | | APPROVAL. | | | | | | 6.)THE FASTENING FOR SOME OF THE | | | CONNECTORS ON A5.1 CONFLICTS WITH THE | | | PRODUCT APPROVAL.FASTENING MUST BE | | | CONSISTENT WITH THE PAPERWORK ON THE | | | STATE WEBSITE (WWW.FLORIDABUILDING.ORG) | | | OR APPLY FOR A LOCAL PRODUCT APPROVAL. | | | PLEASE FEEL FREE TO CONTACT ME IF YOU | | | HAVE ANY QUESTIONS OR NEED ASSISTANCE. | | | | | | REGARDING TRUSS ENGINEERING PACKAGE | | | (SPACE COAST TRUSS, INC.), SIGNED BY | | | STEPHEN WARTER, PE: | | | | | | 7.)NONCONCURRENT 10# LL FOR BOTTOM | | | CHORD OF TRUSSES CANNOT BE USED (MUST BE | | | CONCURRENT). NOTE 2 REFERS TO UBC94; | | | GOVERNING CODE IS FBC2001. | | | | | | 8.)THE TRUSS ENGINEERING (MITEK | | | SOFTWARE) INCLUDES A 1.25 INCREASE FOR | | | PLATES.THIS INCLUDES A STRESS INCREASE | | | FOR STEEL WHICH IS NOT CODE COMPLIANT | | | FBC1609.4.3(2). | | | | | | 9.)PLEASE REVIEW OTHER TRUSS PACKAGES | | | WHICH YOU MAY HAVE SUBMITTED ON OTHER | | | PROJECTS IN THE CITY AND ARE | | | NONCOMPLIANT, AND SUBMIT NEW ENGINEERING | | | WHICH IS CODE COMPLIANT. | | | | | | 10.)EITHER ALL SHEETS MUST BE SIGNED | | | AND SEALED FOR THE TRUSS ENGINEERING OR | | | AN INDEX SHEET IN COMPLIANCE WITH | | | FAC61G15-31.003(5)(A) THROUGH (E). | | | | | | 11.)THE SIGNATURE IS TO BE AN | | | ORIGINAL, | | | NOT A PHOTOCOPY, REQUIRES A DATE.TITLE | | | BLOCK ALSO REQUIRED, FAC61G15-23.002. | | | | | | 12.)TRUSS PLACEMENT IS TO BE SEALED BY | | | THE TRUSS SYSTEM ENGINEER, | | | FAC61G15-31.003(4). | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-01-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-01-25 |
Time |
17:42 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-01-25 |
Time |
17:01 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-01-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2006-01-21 |
Time |
08:22 |
Rev Time |
0.30 |
| Received By |
jleahy |
Date |
2006-01-21 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-12-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-12-19 |
Time |
12:17 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-12-19 |
Time |
12:16 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-03-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-03-04 |
Time |
11:48 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-03-04 |
Time |
08:19 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2005-03-18 |
|
|
Cont ID |
|
| Sent By |
gsalfeld |
Date |
2005-03-18 |
Time |
10:17 |
Rev Time |
1.00 |
| Received By |
gsalfeld |
Date |
2005-03-18 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2005-03-18 00:00:00 | REVIEW UNDER 05030368 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-01-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-13 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-13 |
Time |
10:48 |
Sent To |
E |
|
| Notes |
| 2006-01-13 00:00:00 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-12-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-14 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-14 |
Time |
16:32 |
Sent To |
E |
|
| Notes |
| 2005-12-14 00:00:00 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-04-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-18 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-18 |
Time |
16:07 |
Sent To |
B |
|
| Notes |
| 2005-04-18 00:00:00 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-04-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-12 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-12 |
Time |
16:45 |
Sent To |
Z |
|
| Notes |
| 2005-04-12 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-03-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-18 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-03-02 |
Time |
11:01 |
Sent To |
PC |
|
| Notes |
| 2005-03-02 00:00:00 | TO "E" BOX/SFR |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-02-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-03-18 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-02-24 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2005-02-24 00:00:00 | TO "Z" BOX. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-03-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-03-14 |
Time |
15:15 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2005-03-14 |
Time |
15:15 |
Sent To |
B |
|
| Notes |
| 2005-03-14 00:00:00 | COPY OF A/C DWG FAXED AND APPROVED | | | 3-6-05. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-03-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-03-07 |
Time |
19:54 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2005-03-07 |
Time |
19:53 |
Sent To |
P |
|
| Notes |
| 2005-03-07 00:00:00 | DENIED: | | | ONLY ONE MECHANICAL PLAN SUBMITTED FOR | | | REVIEW.CALL CONTRACTOR FOR ADDITIONAL | | | COPY. | | | | | | PLAN IS CODE COMPLIANT. | | | | | | IF YOU HVAE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2005-03-18 |
|
|
Cont ID |
|
| Sent By |
gsalfeld |
Date |
2005-03-18 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
gsalfeld |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2005-03-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-03-12 |
Time |
15:02 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-03-12 |
Time |
15:02 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-04-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-04-18 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-04-18 |
Time |
14:53 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-03-01 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-03-01 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-03-01 |
Time |
16:49 |
Sent To |
I |
|
| Notes |
| 2005-03-01 00:00:00 | DENIED, | | | 1. SURVEY & SITEPLAN DOES NOT MATCH | | | (SETBACKS).MUST PROVIDE THE CORRECT | | | LAYOUT OF HOUSE ON PROPERTY WITH | | | SETBACKS.CALLED CONTRACTOR | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|