Plan Review Details - Permit 05021273
Plan Review Stops For Permit 05021273
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-02-23 Cont ID  
Sent By ptjomsto Date 2005-02-23 Time 17:47 Rev Time 0.00
Received By ptjomsto Date 2005-02-23 Time 17:47 Sent To  
Notes
2005-02-23 00:00:00EXT REQUIRED FOR STE #850

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-29 Cont ID  
Sent By shill Date 2005-08-29 Time 08:54 Rev Time 0.50
Received By shill Date 2005-08-29 Time 08:11 Sent To  
Notes
2005-08-29 00:00:00REVISION A0, A1,A1.1, A2.0, A2.1, TI-1,
 TI-2 DATED 7/14/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-30 Cont ID  
Sent By shill Date 2005-06-30 Time 09:55 Rev Time 1.00
Received By shill Date 2005-06-30 Time 09:55 Sent To  
Notes
2005-06-30 00:00:00REVISION #2 DATED 5/25
 A1.0, A1.1, A2.0, A2.1, TI1,TI2, CS1
 THROUGH CS4
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-03-18 Cont ID  
Sent By shill Date 2005-03-18 Time 15:45 Rev Time 1.00
Received By shill Date 2005-03-18 Time 15:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-11-21 Cont ID  
Sent By dpalmer Date 2005-11-21 Time 08:35 Rev Time 0.25
Received By dpalmer Date 2005-11-21 Time 08:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-11-10 Cont ID  
Sent By dpalmer Date 2005-11-10 Time 19:57 Rev Time 0.00
Received By dpalmer Date 2005-11-10 Time 19:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-08-15 Cont ID  
Sent By dpalmer Date 2005-08-15 Time 19:46 Rev Time 0.60
Received By dpalmer Date 2005-08-15 Time 19:46 Sent To  
Notes
2005-08-15 00:00:00***** UNSAT***
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW.
  
  
 1)NOTE: PLEASE SEE VALUATION FOR SCOPE
 OF WORK WAS NOT UP DATED. NOTE ON REV
 COVER SHEET MENTIONS THIS WILL BE PAID
 UPON ISSUANCE. PLEASE SEE PERMIT WAS
 ISSUED PREVIOUSLY.
 PLEASE SEE BLDG VALUATION MAY BE
 ASSESSED BY BLDG PLANS REVIEW.
 FBC 104.6.5
 CITY OF WEST PALM BEACH AMENDMENTS.
  
 2)NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS
 REVIEW. PLEASE SEE RISER IS UNCLEAR FOR
 SCOPE OF WORK IN ADJACENT MECH/ELEC RM.?
 PLEASE SEE ORIG PLANS SUBMITTED AND
 THESE PLANS APPEAR TO SHOW ONLY
 "DARKENED" LINES ON RISER TO BE INCLUDED
 IN SCOPE OF WORK FOR THIS PERMITAND
 PROJECT. PLEASE SEE OTHER AREAS OF RISER
 ARE BEING REVISED ON EACH SUBMITTED
 REVISIONS?
 PLEASE SEE PREVIOUS PLANS SHOWED TWO
 DISC'S, ONE NEW, ONE FUTURE, HOWEVER
 THESE WERE NOT "DARKENED" AS NEW WORK IS
 NOTED. PLEASE SEE THIS REVISION NOW
 MENTIONS THIS WORK ON RISER AS
 "EXISTING".
 IT IS UNCLEAR HOW INFORMATION IS REVISED
 WHEN NOT INCLUDED IN THE SCOPE OF THIS
 PERMIT??
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED RESPONSE LTR TO CLARIFY:
 WHICH WORK ISBEING DONE UNDER THIS
 PERMIT?
 WHICH WORK IS NEW?
 WHICH IS EXSITING AND NOT INCLUDED IN
 THIS SCOPE.
  
 3)NOTE: PLEASE SEE LIGHTING LOADS DO NOT
 SEEMED TO HAVE BEEN INCREASED DUE TO
 ADDED SQ FT FOR TENANT.?
 220.3
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY SUBMITNEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD/VOIDED SHEETS MAY BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-27 Cont ID  
Sent By dpalmer Date 2005-06-27 Time 15:53 Rev Time 0.50
Received By dpalmer Date 2005-06-27 Time 15:30 Sent To  
Notes
2005-06-27 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE SEE VALUE FOR ADDED SCOPE
 OF WORK IS TO BE INCREASED. FBC 104.6.5
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE.
 215.5
  
 3)NOTE: PLEASE SEE SHEET E-3, WHICH DOES
 NOT INCLUDE ANY REV'S OR UPDATED CHANGES
 LABELED IN TITLE BLOCK.
 PLEASE SEE ALL REV'S, CHNAGES ARE TO BE
 SHOWN WITH CLOUDS, TRIANGLES.
  
 4)NOTE: PLEASE SEE AREA LOCATED ON RISER
 WHICH MENTIONS A NEW 100A DISC IN
 'ADJACENT MECH RM". PLEASE REMOVE THIS
 AS NEW IF NOT IN SCOPE OF WORK. IF IN
 SCOPE PLEASE SEE 240.21, TAPS SHALL NOT
 BE MADE FROM A TAP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-04-01 Cont ID  
Sent By dpalmer Date 2005-04-01 Time 16:31 Rev Time 0.30
Received By dpalmer Date 2005-04-01 Time 16:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-02 Cont ID  
Sent By dpalmer Date 2005-03-02 Time 05:55 Rev Time 0.25
Received By dpalmer Date 2005-03-01 Time 19:42 Sent To  
Notes
2005-03-02 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SHOW LOCATION OF NEW
 PANEL 850L? PLANS SHOW 850C?
  
 PLEASE SEE ANY POSSIBLE NOTES FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-11-10 Cont ID  
Sent By mcarsill Date 2005-11-10 Time 11:15 Rev Time 0.00
Received By mcarsill Date 2005-11-10 Time 11:15 Sent To  
Notes
2005-11-10 00:00:00DUCT DETECTORS SHALL ACTIVATE THE FIRE
 ALARM SYSTEM.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2005-08-31 Cont ID  
Sent By mwennerg Date 2005-08-31 Time 10:54 Rev Time 0.00
Received By mwennerg Date 2005-08-31 Time 10:54 Sent To  
Notes
2005-08-31 00:00:00******DENIED******
  
 1) FP SHEETS HAVE BEEN REMOVED FROM ONE
 SET OF PLANS. PLEASE KEEP ALL SHEETS
 TOGETHER UNTIL REVIEW HAS PASSED. AT
 THAT TIME, SEPARATE SHOP DRAWINGS AND
 PERMITS SHOULD BE APPLIED FOR. IT
 DOESN'T APPEAR THAT COMMENT #1 HAS BEEN
 ACKNOWLEDGED OR ADDRESSED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-07-05 Cont ID  
Sent By mwennerg Date 2005-07-05 Time 11:17 Rev Time 0.00
Received By mwennerg Date 2005-07-05 Time 11:17 Sent To  
Notes
2005-07-05 00:00:00******DENIED******
  
 1) IN ACCORDANCE WITH LOCAL FIRE CODE
 REQUIREMENTS, NEW DUCT SMOKE DETECTOR
 INSTALLATIONS SHALL BE WIRED INTO THE
 FIRE ALARM SYSTEM TO SOUND A GENERAL
 FIRE ALARM WHEN ACTIVATED.
  
 2) PLEASE NOTE THAT SHEETS FP-1 AND FP-2
 DON'T ILLUSTRATE ANY REVISIONS OR
 UPDATED CHANGES IN THE TITLE BLOCK.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-12 Cont ID  
Sent By mwennerg Date 2005-04-12 Time 15:44 Rev Time 0.00
Received By mwennerg Date 2005-04-12 Time 15:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-23 Cont ID  
Sent By mwennerg Date 2005-03-23 Time 16:11 Rev Time 0.00
Received By mwennerg Date 2005-03-23 Time 16:11 Sent To  
Notes
2005-03-23 00:00:001) PLEASE BE ADVISED THAT ANY NEW DUCT
 SMOKE DETECTOR INTALLATIONS MUST BE
 WIRED INTO THE BUILDING FIRE ALARM
 SYSTEM, AND SOUND A GENERAL FIRE ALARM
 WHEN ACTIVATED.
  
 2) PLEASE SUBMIT SEPARATE SHOP DRAWINGS
 FOR THE FIRE ALARM REMODEL.
  
 3) PLEASE SUBMIT SEPARATE SHOP DRAWINGS
 FOR THE FIRE SPRINKLER REMODEL.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 16:04 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 16:04 Sent To P
Notes
2005-12-27 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 10:57 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 10:57 Sent To M
Notes
2005-12-16 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-12-14 Cont ID  
Sent By adarroug Date 2005-12-14 Time 16:31 Rev Time 0.00
Received By adarroug Date 2005-12-14 Time 16:31 Sent To P
Notes
2005-12-14 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-11-18 Cont ID  
Sent By adarroug Date 2005-11-18 Time 11:26 Rev Time 0.00
Received By adarroug Date 2005-11-18 Time 11:26 Sent To  
Notes
2005-11-18 00:00:00TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 15:49 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 15:49 Sent To  
Notes
2005-10-19 00:00:00TO "COMM" BD#19
2005-10-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-05 Cont ID  
Sent By adarroug Date 2005-08-05 Time 13:29 Rev Time 0.00
Received By adarroug Date 2005-08-05 Time 13:29 Sent To  
Notes
2005-08-08 00:00:00TO "COMM" BD#35
2005-08-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-02 Cont ID  
Sent By adarroug Date 2005-06-02 Time 18:19 Rev Time 0.00
Received By adarroug Date 2005-06-02 Time 18:19 Sent To  
Notes
2005-06-02 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-01 Cont ID  
Sent By dpalmer Date 2005-04-01 Time 16:30 Rev Time 0.00
Received By dpalmer Date 2005-04-01 Time 16:30 Sent To  
Notes
2005-04-01 00:00:00SENT TO COMM BOARD #26
 M-2 SHEET NOT STAMPED ON EITHER SET.
 FP SHEETS NOT STAMPED BY FIRE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-30 Cont ID  
Sent By adarroug Date 2005-03-30 Time 14:05 Rev Time 0.00
Received By adarroug Date 2005-03-30 Time 14:05 Sent To E
Notes
2005-03-30 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 16:22 Rev Time 0.00
Received By dpalmer Date 2005-02-24 Time 13:57 Sent To  
Notes
2005-02-24 00:00:00TO "COMM" BD#32

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-12-16 Cont ID  
Sent By tgordon Date 2005-12-16 Time 14:03 Rev Time 0.30
Received By tgordon Date 2005-12-16 Time 14:03 Sent To  
Notes
2005-12-16 00:00:00MECH. REV. TO PLANS AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-11-14 Cont ID  
Sent By pkrauss Date 2005-11-14 Time 14:33 Rev Time 0.00
Received By pkrauss Date 2005-11-14 Time 14:33 Sent To  
Notes
2005-11-10 00:00:00NEW SHEETS/OR SHEETS NOT STAMPED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-07-19 Cont ID  
Sent By hmoser Date 2005-07-19 Time 15:52 Rev Time 0.00
Received By hmoser Date 2005-07-19 Time 15:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-04-14 Cont ID  
Sent By pkrauss Date 2005-04-14 Time 09:06 Rev Time 0.10
Received By pkrauss Date 2005-04-14 Time 09:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-03-24 Time   Rev Time 0.00
Received By hmoser Date 2005-03-24 Time 14:15 Sent To  
Notes
2005-03-24 00:00:00FAN SHUTDOWN TEST REQUIRED FOR FINAL
 INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-12-28 Cont ID  
Sent By mperson Date 2005-12-28 Time 14:34 Rev Time 1.25
Received By mperson Date 2005-12-28 Time 14:34 Sent To  
Notes
2005-12-28 00:00:00 
  
  
 REVISION - PROVISO
  
 SEWAGE PUMP SHALL BE LISTED. MANUF.
 SPECIFICATION SHEETS SHALL BE ON THE JOB
 AT THE TIME OF PLUMBING FINAL. SECTION
 303.4
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-12-15 Cont ID  
Sent By jleech Date 2005-12-15 Time 12:14 Rev Time 0.75
Received By jleech Date 2005-12-15 Time 12:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-11-21 Cont ID  
Sent By jleech Date 2005-11-21 Time 16:38 Rev Time 1.00
Received By jleech Date 2005-11-21 Time 16:22 Sent To  
Notes
2005-11-21 00:00:00DENIED;
 1.PAGE P-1 CLEAR FLOOR SPACE MUST BE A
 FORWARD APPROACH, PLAN INDECATE A SIDE
 APPROACH. SEE FBC-2001 CHAPTER 11
 SEC.11-4.24.5.
 2.RE-DUE INT. ELEVATION ON SHEET A-1.1
 SHOWING LOCATION OF NEW SEWAGE EJECTOR.
 NEW EQUIPMENT TO BE INSTALLED MUST NOT
 RESTRICT THE FORWARD APPROACH OR THE
 CLEAR FLOOR SPACE. SEE SEC. 11-4.24.3
 AND 11-4.24.5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-19 Cont ID  
Sent By kstevens Date 2005-09-07 Time 14:12 Rev Time 1.00
Received By kstevens Date 2005-09-07 Time 20:01 Sent To  
Notes
2005-12-19 00:00:00REVISION OK FOR SHEETS P-1 & P-2 ONLY

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-06 Cont ID  
Sent By kstevens Date 2005-07-06 Time 17:38 Rev Time 1.00
Received By kstevens Date 2005-07-06 Time 17:38 Sent To  
Notes
2005-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT A1.0 NO DEAD ENDS ALLOWED SECTION
 704.5. FIELD INSPECTOR SHALL INSPECT THE
 DEMO OF THE EXISTING SINK PRIOR TO
 COVERING.
 2. SHT A1.1 BREAK ROOM SINK SHALL BE
 ACCESSIBLE. PLEASE SHOW THE FOLLOWING ON
 THE FLOOR PLAN AND THE DETAIL:
 A. KNEE CLEARANCE 11-4.24.3
 B. SINK DEPTH 11-4.24.4
 C. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 PROVIDED FOR FORWARD APPROACH AND SHALL
 ENTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. ALSO NO CABINET DOORS SHALL BE
 ALLOWED IN THE CLEAR FLOOR SPACE FOR THE
 SINK.
 D. EXPOSED PIPES & SURFACES 11-4.24.6
 E. FAUCETS 11-4.24.7
 SHOW COMPLIANCE WITH ALL THE ABOVE.
 3. SHT P-1 WATER ISOMETRIC. WATER HAMMER
 ARRESTORS ARE REQUIRED FOR ALL QUICK
 CLOSING VALVES, SUCH AS ICE MAKERS, DISH
 WASHERS AND/OR WASH MACHINES. THEY SHALL
 BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING PER
 PDI-WH 201.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]