Plan Review Details - Permit 05021213
Plan Review Stops For Permit 05021213
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-05-25 Cont ID  
Sent By alange Date 2005-05-25 Time 15:50 Rev Time 1.00
Received By alange Date 2005-05-24 Time 15:51 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-04-29 Cont ID  
Sent By alange Date 2005-04-29 Time 08:11 Rev Time 1.50
Received By alange Date 2005-04-29 Time 07:15 Sent To  
Notes
2005-04-29 00:00:00DENIED
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5.1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.PLEASE SHOW A DETAIL ON PLANS.
  
 9. FBC 1801.1.3MINIMUM FOOTING DEPTH
 IS 12" SEE A-9 #6
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-17 Cont ID  
Sent By alange Date 2005-03-17 Time 10:25 Rev Time 2.50
Received By alange Date 2005-03-17 Time 09:02 Sent To  
Notes
2005-03-17 00:00:00DENIED
  
 1.BASED OM SBCCI BUILDING VALUATION
 DATA. THE VALUATION HAS BEEN CHANGED TO
 $325,246.00.ADDITIONAL PERMIT FEES OF
 $812.74 ARE DUE PRIOR TO ISSUING OF A
 PERMIT.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SHOW HOW SMOKE DETECTORS WILL COMPLY
 WITH FBC 905.2
  
 4.PRODUCT APPROVALS WITH QUALITY
 ASSURANCE REQUIRED FOR LINTELS, STRAPS
 AND TIE-DOWNS AND HARDI-PLANK SIDING.
 ALL PRODUCT APPROVALS SUBMITTED REQUIRE
 THE FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 5.1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.PLEASE SHOW A DETAIL ON PLANS.
  
 6.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS COMPLYING WITH FBC 2309.6
  
 7. A-9 #3 ROOF SHEATHING NAILING SHALL
 COMPLY WITH WPB AMMENDMENTS TO THE FBC
 SEC 2306.1
  
 8.INSULATION ON PLAN SHOW ROOF
 INSULATAION AT R-19 AND ENERGY CALS AT
 R-30.
  
 9. NOTE: A-9 #3 FOOTING AND GRADE SHOWN
 BOTH ARE AT MINIMUM REQUIREMENTS.
 12" FOOTING BELOW GRADE AND 4" FOR FF
 ABOVE GRADE.
  
 10. RAYNOR GARAGE DOOR IS SUBMITTED WITH
 STATE APPROVAL AND IS MISSING A PRODUCT
 APPROVAL WITH QUALITY ASSURANCE.
 (MIAMI-DADE) FOR EXAMPLE. PLEASE ATTACH
 2 COPIES TO STATE APPROVALS.
  
 11. ALL PGT WINDOWS SUBMITTED ARE
 MISSING STATE APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12. SQUARE FOOTAGE ON APPLICATION HAS
 BEEN REVISED TO MATCH SQUARE FOOTAGE ON
 PLANS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-08-09 Cont ID  
Sent By dpalmer Date 2006-08-09 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2006-08-09 Time 11:15 Sent To PC
Notes
2006-08-09 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE THE REVISED PANEL
 SCHEDULES AND LOAD CALCULATIONS DO NOT
 CORRELATE WITH THE ELECTRICAL PLANS ON
 FILE WITH THE NEW REVISED PANEL
 SCHEDULESAS THE NEW LOADS AND
 EQUIPMENT IS BEING NOTED, YET NOT ON
 PLANS.
  
 FBC 106.1.2
  
 2) NOTE: PLEASE BE SURE ARCHITECT PRINT
 LICENSE NUMBER ON PLANS/TITLE BLOCKS.
 FAC 61G1-16.004
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-07-26 Cont ID  
Sent By dpalmer Date 2006-07-26 Time 08:06 Rev Time 0.00
Received By dpalmer Date 2006-07-26 Time 07:02 Sent To PC
Notes
2006-07-26 00:00:00*** REDLINED ****
  
 1) NOTE: PLEASE SEE GROUNDING ELECTRODE
 AT MAINHOUSE STILL REQUIRED PER
 250.32,250.50
  
 2) NOTE: PLEASE SEE GARAGE SHOWS AN AHU,
 YET NO CU IS SHOWN? THIS MAY BE SPLIT
 FROM THE CU'S AT MAIN HOUSE, VERIFY.
 PLEASE ALSO SEE MAIN HOUSE SHOWS A THIRD
 A/C IN CLOSET OF UTILITY ROOM?? VERIFY.
 IS THIS ALSO AN ADDITIONAL A/C SPLIT
 FROM OTHERS?
  
 3) NOTE: PLEASE PANEL "B" SHOWS POOL
 HEATER , YET NO ELEC STUB OUT SHOWN OR
 FUTURE LOCATION SHOWN.
 THIS IS ALSO TO VERIFY.
  
 4) NOTE: PLEASE SEE SD IN MASTER BED RM
 SHALL BE MOVED TO BE WITHIN 12" OF THE
 HIGHEST POINT ON A FLAT CEILING.
 NFPA-72 11.8.3
  
  
 ** PLEASE VERIFY THE ABOVE AND MAKE ANY
 CHANGES NEEDED BEFORE ROUGH.
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-07-24 Cont ID  
Sent By dpalmer Date 2006-07-24 Time 19:28 Rev Time 0.00
Received By dpalmer Date 2006-07-19 Time 21:03 Sent To PC
Notes
2006-07-24 00:00:00*** NOTES ******
  
 1) NOTE CONTRACTOR TO SUBMIT TWO NEW E-1
 AND E-2. NO FEE , MAY BRING PLANS
 DIRECTLY BACK TO SEE DEWEY PALMER.
 PLANS E-1 AND E-2 HAVE BEEN VOIDED.
  
 2) NOTE: PLEASE SEE THAT THE LV PLANS
 SHALL BE SUBMITTED AS A REVSION UNDER LV
 PERMIT AND VALUE SHALL BE INCREASEDFOR
 COMPLETE SCOPE OF LV WORK.
 THE VALUE IS VERY LOW.
 FBC 108.3,106.3.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2006-07-19 00:00:00CALLED GC FOR INFORMATION ON PLANS.
 HOLDING PLANS TILL 7/20 FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-05-09 Cont ID  
Sent By dpalmer Date 2005-05-09 Time 10:36 Rev Time 0.50
Received By dpalmer Date 2005-05-09 Time 10:29 Sent To P
Notes
2005-05-09 00:00:00********* REDLINEDNOTES **********
  
 1)PLEASE SEE COOKTOP STILL SHOWN AS 8KW
 W/ 30A OCP.
 2)NOTE: MOVED GROUNDING ELECTRODE SYSTEM
 FOR "MAIN HOUSE" PANEL. SHOWN TO GARAGE
 PANEL, MOVED TO MAIN HOUSE PER 250.32
 3)ARC FAULT PROTECTION FOR BEDROOM
 CIRCUITS NOTED FOR RECEPTS AND LTS,
 PLEASE SEE 210.12 2002 NEC, "ALL
 OUTLETS" INCLUDING SD'S,FANS ETC TO BE
 ARC FAULT.
  
  
 THE ABOVE ITEMS WERE REDLINED ON BOTH
 SETS OF PLANS AND DO NOT NEED TO BE
 REVISED. IF REVISIONS ARE MADE TO PLANS
 AT ANY TIME DURING CONSTRUCTION, PLEASE
 MAKE THE ABOVE CORRECTIONS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-04-20 Cont ID  
Sent By dpalmer Date 2005-04-20 Time 13:03 Rev Time 1.50
Received By dpalmer Date 2005-04-20 Time 11:53 Sent To P
Notes
2005-04-20 00:00:00************ UNSAT ***************
  
 PLEASE SEE MANY NOTES FROM PREVIOUS
 REVIEW STILL HAVE NOT BEEN CORRECTED.
 PLEASE ALSO SEE SOME NEW NOTES DUE TO
 OTHER CHANGES IN PLANS.
  
 THESE NOTES ARE LISTED DIRECTLY IN
 NUMBERED ORDER FROM PREVIOUS REVIEW.
  
 1)NOTE: NOTE #1 NO, PLEASE SEE MOST OF
 NOTE HAS NOT BEEN CHANGED OR ADDRESSED.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO,
 PLEASE SEE GROUPING OF MAINS, MEANS OF
 DISCONNECT FOR DEATCHED BLDGS ETC.
 225.31-225.36, 250.32 ETC.
  
 4)NOTE: NOTE #4 NO, UNABLE TO VERIFY
 ACTUAL INSTALLATION OF SERVICE DUE TO
 MISSING INFORMATION, NOT CORRECTED
 INFORMATION.215.5, 250.50.250.32
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 NO, PLEASE SEE PANEL
 SCHEDULE(S), ITEMS STILL NEED TO BE
 ADDRESSED.
 SEE REDLINES.
  
 8)NOTE: NOTE #8 NO, SEE PANEL SCHEDULE,
 AND VERIFY LABLELING OF SMALL APPL AND
 ALSO LOAD FOR SM APPL. 210.11C1,220.16
 ETC.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 NO. SEE PREVIOUS.
  
 12)NOTE: NOTE #12 NO, PLEASE SEE MISSING
 TWO PER 210.52, REDLINED.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK, HOWEVER,SEE NEXT
 NOTE.
  
 15)NOTE: NOTE #15 OK, HOWEVER PLEASE SEE
 NOW BOTH AHU'S AHVE BEEN ADDED TO
 CLOTHES CLOSET. PLEASE SEE DISC MEANS
 SHALL CONTAIN NO OCP. ALL CLEARENCE
 REQUIREMENTSETC. PER 110.26??
 PLEASE VERIFY IF THESE ARE INSTALLED IN
 ATTIC SPACE.?
  
 16)NOTE: NOTE #16 NO.
 PLEASE ALSO SEE NOTE ADDED TO E-2 DOES
 NOT MEET 2002 NEC 210.12
 SEE SAME AS PREVIOUS REVIEW.
  
 17)NOTE: NOTE #17 OK , HOWEVER PLEASE
 VERIFY FIXTURE TYPE AND WATTAGE. PLEASE
 SEE "MOST" "AIR-TITE" CANS WHICH ARE
 REQUIRED UNDER FLORIDA ENERGY CODE
 CONTAIN A MAX OF 75W PER FIXTURE.
 PLEASE VERIFY.
  
 18)NOTE: NOTE #18, NO. NO CORRECTIONS
 MADE.
  
 19)NOTE: NOTE #19 OK.
  
 20)NOTE: NOTE #20 NO.
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 NO, PLEASE SEE NO GFI
 PROTECTION INDICATED. 680.24
  
 23)NOTE: NOTE #23 OK.
  
 24)NOTE: NOTE #24 NO. SEE PREVIOUS
 REVIEW.
  
 25)NOTE: NOTE #25 NO RESPONSE REQUIRED.
  
  
 *** NEW NOTES***
  
 1)NOTE: PLEASE SEE UNDER FBC
 DEFINITIONS, A BREEZEWAY OF THIS SIZE
 DOES NOT CONSIDER THIS TO BE "ONE" BLDG.
 PLEASE SEE NEC 225 ETC AS PREVIOUSLY
 NOTED ABOVE FOR DETACHED BLDGS.
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 THE DESIGN PROFESSIONAL.
 PLEASE BE INFORMED IF PLANS COME BACK
 WITH "ANY" OF THE NOTES FROM PREVIOUS
 TWO REVIEWS NOT ADDRESSED, A 4X FEE
 SHALL BE ACCESSED FOR PLAN REVIEW
 PORTION WHICH IS 30% OF PERMIT FEE TIMES
 4(FOUR).
 ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED FOR FILE AS ON PREVIOUS REVIEW.
  
  
 3)NOTE: PLEASE SEE MANY OF THE ABOVE
 ITEMS WERE REDLINED AS WAS DONE ON
 PREVIOUS REVIEW TOHELP WITH LOCATIONS
 OF COMMENTS.
  
 4)NOTE: PLEASE REMOVE ALL OLD/ VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE ONLY SUBMIT ONE SET OF VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-01 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 11:02 Rev Time 2.00
Received By dpalmer Date 2005-03-01 Time 09:05 Sent To M
Notes
2005-03-01 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PLANS/ PANEL
 SCHEDULE(S) AND RISER DIAGRAM.
 PLEASE SEE RISER MENTIONS 200A PANEL
 WITH SUB PANEL. NOTES MENTIONS 2-200A
 PANELS WITH 400A MCB AND 60A SUB POOL
 PANEL, HOWEVER PANELS AR BOTH SHOWN AS
 150A?
 PLEASE ALSO SEE #6'S FOR SUB PANEL, YET
 SUB PANEL IS 150A W/ 106A'S OF LOAD?
 PLEASE SEE PANEL "A" DOES NOT INDICATE
 ANY SUB-PANEL FEED?
 PLEASE SEE RISER ALSO SHOWS A 6/0 FOR
 EQUIPMENT GROUNDING CONDUCTOR.
 (MISPRINT)?
 ETC ETC.
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SHOW LOCATION OF ALL
 PANELS, DISCONNECTS ON PLANS.
 215.5
 PLEASE VERIFY IF GARAGE IS GOING TO HAVE
 A SUBPANEL?
  
 4)NOTE: PLEASE VERIFY IF FOOTER STEEL IS
 GOING TO BE BONDED FROM MAIN HOUSE FOR
 GROUNDING ELECTRODE SYSTEM.
 PER 250.50,250.32?
  
 5)NOTE: PLEASE LABEL PANELS ON RISER TO
 CORRELATE WITH PANELS.
  
 6)NOTE: PLEASE CORRELATE MECHANICAL
 PLANS WITH ELECTRICAL PLANS. MECH SHOWS
 BOTH HEAT-STRIPS AS 10KW, HOWEVER
 ELECTRICAL PLANS INDICATES 1-10KW AND
 1-5KW.
  
 7)NOTE: PLEASE SEE PANEL SCHEDULES,
 THERE ARE NUMEROUS ITEMS WHERE OCP, AWG
 AND KW/LOADS DO NOT MEET CODE.
 50A BRKR ON #12
 10A BRKR? W/ 5KW LOAD
 50A BRKR FOR SM APLL CIRCUITS.
 60A BRKR FOR 5KW HEAT.
 ETC ETC.
  
 8)NOTE: PLEASE SEE 210.11C1 AND 220.16
 FOR MIN TWO OR MORE SMALL APPLIANCE
 CIRCUITS.SEE PREVIOUS NOTE.
  
 9)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 10)NOTE: PLEASE SHOW ALL GARAGE RECEPTS
 AS GFI/GFI PROTECTED. 210.8
  
 11)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 MUST BE 20A AND #12
  
 12)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 THERE ARE NUMEROUS RECEPTS MISSING.
  
 13) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
 MISSING REAR, PLEASE ALSO INDICATE AS
 GFI.
  
 14)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 15)NOTE: PLEASE SEE MISSING A/C COND
 UNIT EQUIPMENT ON PLANS.
 PLEASE ALSO SHOW DISC'S PER 440.11
  
 16)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC.
  
 17)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 18)NOTE: PLEASE VERIFY SIZE OF SERVICE,
 INDICATES 200A SERVICE, HOWEVER LOAD
 CALCULATIONS AFTER ALL DERATING STILL
 INDICATES LOAD EXCEEDING RATING OF
 SERVICE.215.5/220.31
  
 19)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE BOTH MISSING LEADING TO FLOOR
 ABOVE.
  
 20)NOTE: PLEASE SEE GARAGE PLANS
 MENTIONS TO LT ABOVE ON SECOND LEVEL,
 HOWEVER NO 2ND FLR ELECTRICAL PLANS WERE
 SUBMITTED FOR REVIEW.
 PLEASE SUBMIT. 215.5
  
 21)NOTE: PLEASE SEE THERE ARE THREE
 GDO'S SHOWN ON PANEL SCHEDULE, HOWEVER
 PLANS ONLY INDICATES TWO DOORS AND TWO
 RECEPTS FOR GDO? PLEASE CORRELATE.
  
 22)NOTE: PLEASE SEE PANEL SCHEDUL
 INDICATES A "WHIRLPOOL" TUB? YET, PLANS
 DO NOT SHOW ANY HOT TUB? GFI? ETC?
  
 23)NOTE: PLEASE SEE E-1 AND M-SHEETS.
 THESE SHEETS ARE SIGNED WITH WHAT
 APPEARS TO BE A DIFFERENT SIGNATURE THAN
 OTHER SHEETS SIGNED BY ARCH. WE HAVE
 SIGNATURE ON FILE FOR MR. YECKES AND
 THESE SHEETS DO NOT MATCH.
 PLEASE SEE ONE SET OF THESE SHEETS ARE
 BEING RETAINED FOR FILE FOR THIS AND
 CODE COMPLIANCE REVIEW OF PLANS.
 PLEASE SEE THESE MAY BE REVIEWED BY THE
 FL BOARD OF ARCH'S.
  
 24)NOTE: PLEASE SEE IF SERVICE IS INDEED
 LARGER THAN THE 200A SHOWN, PLEASE SEE
 250.66 FOR SIZING OF GROUNDING ELECTRODE
 CONDUCTOR.
  
 25)NOTE: PLEASE SEE DUE TO THE EXTEND OF
 CODE CORRECTIONS NEEDED ON PLANS, PLEASE
 SEE THERE MAY BE OTHER COMMENTS FOR
 FUTURE PLANS.
 ONE SET IS RETAINED.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 14:06 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 14:06 Sent To M
Notes
2006-09-06 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 12:02 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 12:02 Sent To E
Notes
2006-08-03 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 11:59 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 11:59 Sent To M
Notes
2006-08-03 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 15:45 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 15:45 Sent To P
Notes
2006-07-27 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-07-20 Cont ID  
Sent By adarroug Date 2006-07-20 Time 18:13 Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 18:13 Sent To M
Notes
2006-07-20 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-04 Cont ID  
Sent By adarroug Date 2005-05-04 Time 14:43 Rev Time 0.00
Received By adarroug Date 2005-05-04 Time 14:43 Sent To E
Notes
2005-05-04 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 16:03 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 16:03 Sent To E
Notes
2005-04-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-08 Cont ID  
Sent By mmclean Date 2005-04-18 Time 15:27 Rev Time 0.00
Received By adarroug Date 2005-04-08 Time 09:50 Sent To Z
Notes
2005-04-08 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 15:36 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 15:36 Sent To E
Notes
2005-02-28 00:00:00TO "E" BOX/SFR

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-03-17 Time 09:43 Rev Time 0.00
Received By alange Date 2005-02-23 Time 10:20 Sent To Z
Notes
2005-02-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-09-11 Cont ID  
Sent By tgordon Date 2006-09-11 Time 09:35 Rev Time 0.45
Received By tgordon Date 2006-09-11 Time 09:35 Sent To  
Notes
2006-09-11 00:00:00MECH. REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-08-10 Cont ID  
Sent By tgordon Date 2006-08-10 Time 11:33 Rev Time 0.45
Received By tgordon Date 2006-08-10 Time 11:33 Sent To  
Notes
2006-08-10 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) ARCHITECT NEEDS TO SIGN AND DATE EACH
 CHANGE MADE TO PLANS AFTER HE SEALED
 THEM.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2 . ALSO NEED TO SUBMIT TWO
 COPYS OF THE ENERGY CALCULATIONS.
  
 3) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GAS HYDRONIC SPACE &
 WATER HEAT, AS INDICATED ON ENERGY CAL'S
 13A.
  
 4) PROVIDE COMBUSTION AIR FOR GAS WATER
 HEATER, AS INDICATED ON ENERGY CAL'S 14A
 & B, PER 2001 FBC/M 701 .
  
 5) SHOW LOCATION OF 5.3 GAL. WATER
 HEATER, AS INDICATED ON ENERGY CAL'S
 14B.
  
 6) 14X8 SUPPLY AIR TRUNK LINE TO AHU #1
 IS TO SMALL FOR A 4 TON A/C SYSTEM.
 PLEASE SUBMIT MANUAL D CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R
 M1601.1 AND FBC 13-610.1.ABC.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-07-21 Cont ID  
Sent By tgordon Date 2006-07-21 Time 09:44 Rev Time 0.45
Received By tgordon Date 2006-07-21 Time 09:44 Sent To  
Notes
2006-07-21 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) PLEASE SUBMIT NEW ENERGY CALCULATIONS
 SHOWING A/C UNIT #3 FOR BONUS ROOM OVER
 GARAGE, USE FORM 600A-2001 (2001).
  
 2) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .(SEE AHU #1 AND RETURN AIR GRILL SIZE).
  
 3) NEED TO SHOW THE SIZE OF THE SUPPLY
 AIR DUCT FROM AHU #1 TO THE FIRST FLOOR.
  
 4) BATHROOM IN BEDROOM #3 NEEDS AN
 EXHAUST FAN.
  
 5) BUILDING, ELECTRICAL, AND PLUMBING
 PLANS WILL ALSO NEED TO BE REVISED TO
 SHOW CHANGES TO GARAGE AND BONUS ROOM
 OVER GARAGE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-05-27 Cont ID  
Sent By pkrauss Date 2005-05-27 Time 15:13 Rev Time 0.35
Received By pkrauss Date 2005-05-27 Time 15:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-04-21 Cont ID  
Sent By prafter Date 2005-04-21 Time 10:45 Rev Time 1.50
Received By prafter Date 2005-04-21 Time 10:45 Sent To B
Notes
2005-04-21 00:00:00MECH. PLAN REVIEW.
 PROVISO:
 1. SECOND FLOOR MASTER BATH REQUIRES
 EXHAUST FAN IN MAIN ROOM AREA. 2003
 FBC/M 402.2.3.1 .
 2. FIRST FLOOR STUDY, REQUIRES NINE
 INCH DUCT R/AWITH A SUPPLY OF SEVEN
 INCH. 2003 FBC/M 601.4 EXCEPTION 1.
 BALLANCED RETURN AIR .
 3. AHU,S REQUIRE AUXILIARY DRANE PAN
 WITH OVERFLOW PROTECTION. 2001. FBC/M
 307.2.3 .
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-07 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 14:12 Rev Time 0.35
Received By pkrauss Date 2005-03-07 Time 19:20 Sent To P
Notes
2005-03-07 00:00:00DENIED:
 1.RETURN AIR DUCT AND GRILLES ARE NOT
 SIZE FOR THE SECOND FLOOR.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.
  
 3.SEE COMMENT#6 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-08-12 Cont ID  
Sent By jleech Date 2006-08-12 Time 14:25 Rev Time 0.00
Received By jleech Date 2006-08-12 Time 14:25 Sent To  
Notes
2006-08-12 00:00:00PLUMBING REVISION CHANGED BATHROOM ON
 2ND FLOOR.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-05-23 Cont ID  
Sent By kstevens Date 2005-05-23 Time 07:15 Rev Time 0.33
Received By kstevens Date 2005-05-23 Time 07:15 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-04-20 Cont ID  
Sent By kstevens Date 2005-04-20 Time 16:53 Rev Time 0.55
Received By kstevens Date 2005-04-20 Time 16:53 Sent To M
Notes
2005-04-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA STATUTES
  
 1) SHT A-4 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. FROM PREVIOUS REVIEW, ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS
 SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. SECTION 909.1 (THE SECOND
 FLOOR W/M IS DRAINING THROUGH THE WET
 VENT FOR FIRST FLOOR BATHROOM).
 B. NEW COMMENT, SHOWER NOT VENTED IN
 BATHROOM #3. SECTION 901.2.1.
 C. VENT FOR KITCHEN SINK SHOWN AS VENT
 THRU ROOF, BUT FLOOR PLAN SHOWN AS 1/2
 WALL. PLEASE CLARIFY. SEC 104.2.1.
 2) SEE EXAMPLES IN RED FOR A RISER THAT
 MEETS CODE REQUIREMENTS.
 3) SEE ELECTRICAL REVIEW AND ATTACHED
 SHEET CONCERNING FS 553.80(2)(B) AND THE
 DESIGN PROFESSIONAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-11 Cont ID  
Sent By gsalfeld Date 2005-03-11 Time 16:04 Rev Time 1.00
Received By gsalfeld Date 2005-03-11 Time 14:54 Sent To B
Notes
2005-03-11 00:00:003/11/05 DENIED GS
  
 FBC 2001 SEC 909
 1-ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN.ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT.
 2-DOWNSTAIRS WC AND SHR. NOT VENTED

Review Stop Z ZONING
Rev No 2 Status P Date 2005-04-18 Cont ID  
Sent By mmclean Date 2005-04-18 Time 10:57 Rev Time 0.00
Received By mmclean Date 2005-04-18 Time 10:57 Sent To I
Notes
2005-04-18 00:00:00DENIED,
 1. ELEVATIONS ARE NOT MATCHING. RIGHT
 ELEVATION IS OVER THE HEIGHT
 REQUIREMENT.ALL ELEVATION SHOULD
 MATCH.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
 APPROVED, RECEIVED THE CORRECT ELEVATION
 FOR RIGHT SIDE. 4/18/05

Review Stop Z ZONING
Rev No 1 Status F Date 2005-02-28 Cont ID  
Sent By mmclean Date 2005-02-28 Time 09:04 Rev Time 0.00
Received By mmclean Date 2005-02-28 Time 09:04 Sent To I
Notes
2005-02-28 00:00:00DENIED,
 1. OVER THE HEIGHT REQUIREMENT OF 33FT.
 PLANS SHOWS 35 1/2 FT.MUST REDUCE
 HEIGHT TO CONFORM WITH ZONING CODE
 REQUIREMENT OF 33FT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICES
 805-6720