| Plan Review Stops For Permit 05021151 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-02-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-02-24 |
Time |
10:39 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2005-02-24 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2005-02-24 00:00:00 | | | | | | | PROVISO | | | ~~~~~~~ | | | | | | PLEASE NOTE ARTICLE 230.70 CITY OF WEST | | | PALM BEACH AMMENDMENTS REQUIRE A | | | DISCONNECTING MEANS GROUPED WITH THE | | | METER IF MORE THAN 8' OF CONDUCTORS ARE | | | INSIDE THE HOUSE UNPROTECTED TO THE | | | FIRST BREAKER (OVERCURRENT PROTECTION). | | | IF THIS CONDITION EXISTS A DISCONNECT | | | BMUST BE ADDED AND THE PLANS REVISED | | | PRIOR TO INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-02-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-22 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-22 |
Time |
13:46 |
Sent To |
E |
|
| Notes |
| 2005-02-22 00:00:00 | TO "E" BOX |
|
|
|