Plan Review Details - Permit 05021053
Plan Review Stops For Permit 05021053
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-16 Cont ID  
Sent By rmcdouga Date 2005-05-16 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2005-05-16 Time 16:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-21 Cont ID  
Sent By rmcdouga Date 2005-04-21 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2005-04-21 Time 11:37 Sent To  
Notes
2005-04-21 00:00:00DENIED
  
 1) THE BUILDING AREA TABLE ON T1 HAS A
 HEADING THAT STATES 8-UNIT BUILDING.
  
 2) THE ENERGY CALCULATIONS FOR THE 2215
 SQFT MID UNIT DOES NOT APPLY TO THIS
 BUILDING. THE MID UNITS ARE 1448 SQFT.
 PLEASE REMOVE THEM FROM THE PACKAGE.
  
 3) THE UPLIFT GIVEN IN THE TRUSS
 DRAWINGS EXCEEDS THE CAPACITY OF THE
 CONNECTORS SPECIFIED FOR THE MG1
 TRUSSES.
  
 4) THE ARROW ON SHEET S4 INDICATING THE
 LOCATION OF THE HANGER SHOWN IN DETAIL
 10/S7 IS NOT CORRECT. CLARIFY THAT
 DETAIL 10/S7 IS TO BE USED FOR THE (2)
 MEMBER GR2 TRUSSES AS WELL AS THE (4)
 MEMBER GR1 TRUSSES AT THE INTERIOR
 WALLS.
  
 5) THE ANCHOR SCHEDULE LISTS A SIMPSON
 HDSA CONNECTOR. IS THIS A TYPO FOR A
 HD5A CONNECTOR? INDICATE HOW THE UPLIFT
 OF 8310# WAS DETERMINED FOR THIS
 CONNECTOR.
  
 6) SUBMIT THE MIAMI-DADE NOA
 (INSTALLATION INSTRUCTIONS) FOR THE ONE
 HOUR FIRE RATED GLASS BLOCK.
  
 7) SUBMIT THE INSTALLATION INSTRUCTIONS
 FOR THE ASPHALT ROOF SHINGLES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-02-25 Cont ID  
Sent By dpalmer Date 2005-02-25 Time 09:36 Rev Time 0.33
Received By dpalmer Date 2005-02-25 Time 09:36 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-02-22 Cont ID  
Sent By mamini Date 2005-02-22 Time 10:11 Rev Time 0.50
Received By mamini Date 2005-02-22 Time 10:11 Sent To  
Notes
2005-02-22 00:00:00PASSED:
  
 1. SEE PERMIT # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-25 Cont ID  
Sent By nmccray Date 2005-03-25 Time 14:59 Rev Time 0.00
Received By nmccray Date 2005-03-25 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 08:23 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 08:23 Sent To B
Notes
2005-05-03 00:00:00TO "RMCDOUGAL" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 08:58 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 08:58 Sent To  
Notes
2005-02-22 00:00:00TO "COMM" BD#38

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-03-12 Cont ID  
Sent By hmoser Date 2005-03-12 Time   Rev Time 0.00
Received By hmoser Date 2005-03-12 Time 12:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-04-21 Cont ID  
Sent By rmcdouga Date 2005-04-21 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2005-04-21 Time 11:43 Sent To  
Notes
2005-04-21 00:00:00PASSED BY K. STEVENS ON 3/12/05

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-21 Cont ID  
Sent By rmcdouga Date 2005-04-21 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2005-04-21 Time 11:38 Sent To  
Notes
2005-04-21 00:00:00OK PER E.SCHNEIDER ON 3/15/05