Plan Review Details - Permit 05021051
Plan Review Stops For Permit 05021051
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-17 Cont ID  
Sent By rmcdouga Date 2005-05-17 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2005-05-17 Time 06:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-21 Cont ID  
Sent By rmcdouga Date 2005-04-21 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2005-04-21 Time 16:17 Sent To  
Notes
2005-04-21 00:00:00DENIED
  
  
 1) THE AREA TABLE ON SHEET T1 IS
 INCORRECTLY LABELED 8 UNIT BUILDING.
  
 2) ENERGY CALCS. WERE SUBMITTED FOR A
 2215 SQFT MID UNIT. THE MID UNITS FOR
 THIS BUILDING ARE 1448 SQFT. PLEASE
 REMOVE THE INCORRECT CALCS.
  
 3) THE GR3 TRUSS IS INDICATED AS A TWO
 MEMBER TRUSS ON THE TRUSS DRAWINGS AND A
 FOUR MEMBER TRUSS ON S4 OF THE PLANS.
  
 4) THE CONNECTOR SCHEDULE ON S4 LISTS A
 SIMPSON HDSA. SHOULD THIS BE A HD5A?
 INDICATE HOW THE UPLIFT VALUE FOR THIS
 CONNECTOR WAS DETERMINED.
  
 5) SPECIFY THE CONNECTORS FOR THE GR2
 TRUSSES AT THE INTERIOR WALLS.
  
 6) CLARIFY THAT DETAIL 10/S7 IS FOR ROOF
 TRUSSES, IN ADDITION TO THE FLOOR
 TRUSSES.
  
 7) THE REQUIRED UPLIFTS GIVEN IN THE
 TRUSS DRAWINGS FOR THE MG1 TRUSSES
 EXCEED THE CAPACITY OF THE SPECIFIED
 CONNECTORS.
  
 8) SUBMIT THE MIAMI-DADE NOA
 (INSTALLATION INSTRUCTIONS) FOR THE ONE
 HOUR FIRE RATED GLASS BLOCK.
  
 9) SUBMIT THE INSTALLATION INSTRUCTIONS
 FOR THE ASPHALT ROOF SHINGLES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-02-25 Cont ID  
Sent By dpalmer Date 2005-02-25 Time 09:37 Rev Time 0.33
Received By dpalmer Date 2005-02-25 Time 09:37 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-02-22 Cont ID  
Sent By mamini Date 2005-02-22 Time 10:16 Rev Time 0.50
Received By mamini Date 2005-02-22 Time 10:16 Sent To  
Notes
2005-02-22 00:00:00PASSED:
  
 1. SEE PERMIT # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-25 Cont ID  
Sent By nmccray Date 2005-03-25 Time 14:41 Rev Time 0.00
Received By nmccray Date 2005-03-25 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-02 Cont ID  
Sent By adarroug Date 2005-05-02 Time 10:14 Rev Time 0.00
Received By adarroug Date 2005-05-02 Time 10:14 Sent To B
Notes
2005-05-02 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 09:00 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 09:00 Sent To  
Notes
2005-02-22 00:00:00TO "COMM" BD#38

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-03-12 Time   Rev Time 0.00
Received By hmoser Date 2005-03-12 Time 11:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-03-12 Cont ID  
Sent By kstevens Date 2005-03-12 Time 05:39 Rev Time 0.50
Received By kstevens Date 2005-03-12 Time 05:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-15 Cont ID  
Sent By eschneid Date 2005-03-15 Time 09:24 Rev Time 0.00
Received By eschneid Date 2005-03-15 Time 09:24 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved