Plan Review Details - Permit 05021030
Plan Review Stops For Permit 05021030
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-08-07 Cont ID  
Sent By shill Date 2006-08-07 Time 14:32 Rev Time 0.00
Received By shill Date 2006-08-07 Time 14:32 Sent To Z
Notes
2006-08-07 00:00:00PORCH & GARAGE, REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-22 Cont ID  
Sent By shill Date 2005-07-22 Time 09:40 Rev Time 1.00
Received By shill Date 2005-07-22 Time 09:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 13:49 Rev Time 0.00
Received By shill Date 2005-07-21 Time 13:49 Sent To PC
Notes
2005-07-21 00:00:00****CORRECTIONS***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-22 Cont ID  
Sent By shill Date 2005-06-22 Time 10:38 Rev Time 0.50
Received By shill Date 2005-06-22 Time 10:38 Sent To PC
Notes
2005-06-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 NOTE - CHANGED PLAN TO BE ISSUED FROM
 MASTER #04031090
  
 1.)SHEET 5.1 DOES NOT MATCH THE PLANS
 SUBMITTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-08 Cont ID  
Sent By jgomez Date 2005-04-08 Time 15:33 Rev Time 5.00
Received By jgomez Date 2005-04-08 Time 15:33 Sent To PC
Notes
2005-04-08 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- ARCHITECT'S LOGO IS MISSING THE NAME
 OF THE ARCHITECT SIGNING AND SELAING THE
 PLANS AS REQUIRED BY CHAPTER 481 FLORIDA
 STATUTES.
  
 4- ARCHITECT TO PROVIDE IN DRAWINGS ALL
 INFORMATION AS REQUIRED BY SEC. 1606.1.7
 FBC 2001.
  
 5- SHEET A-1: A) WIND LOAD. WHERE IS
 VELOCITY PRESSURE OF 33PSF TAKEN FROM?.
 B) SPECIFY ROOF LIVE AND DEAD LOAD.
 C) SPECIFY ATTIC LIVE LOAD OF 30PSF OR
 10PSF AS REQ'D BY TABLE 1604.1 FBC 2001.
 D) WHAT ARE THE SHEAR (90PSI) AND
 BENDING (1200PSI) USED FOR IN THESE WIND
 LOAD CALCULATIONS.
 E) CLEARLY IDENTIFY DESIGN CRITERIA
 USED: CHAPTER 16 FBC 2001 OR ASCE 7-98
 AND EMPLOY CORRECT WIND LOAD ANALYSIS
 ACCORDINGLY.
 F) SPECIFY THE CALCULATED DESIGN
 PRESSURES FOR ALL EXTERIOR OPENINGS FOR
 DOORS AND WINDOWS.
  
 6- SHEET A-2:A) WINDOW AND DOOR
 STRUCTURAL BUCK DETAILS ARE FOR WOOD
 FRAMING CONSTRUCTION. HOUSE IS CONCRETE
 BLOCK CONSTRUCTION. REVISE AS REQ'D. AND
 SEE SEC. 1707.4.4.2FBC 2001 FOR PROPER
 BUCK ATTACHMENT.
 B) PROVIDE STRUCTURAL BUCK DETAIL FOR
 GARAGE DOOR. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 C) SPECIFY SIZE OF SLIDING GLASS DOOR.
 D) PROVIDE COMPLETE INFORMATION FOR
 STAIRWELL: *RISER AND TREAD SIZE.
 SEC.1007.3.1 (EXCEPTION #1) FBC 2001.
 **HANDRAILS. SEE SEC. 1007.5 FBC 2001.
 ***SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AS REQ'D BY SEC. 2305.1.4 FBC.
 ****SPECIFY DIMENSIONS.
 E) FIRST FLOOR BATHROOM TO HAVE DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 (NEED 2'-8" DOOR). SEC. 11-11 FBC 2001.
 F) SPECIFY SAFETY GLASS AT MASTER
 BATHROOM AND 2ND FLOOR BATHROOM. SEC.
 2405.2.1 FBC 2001.
 G) DESIGN CRITERIA: *CITING WRONG CODE.
 WE USE FLORIDA BUILDING CODE 2001. NOT
 STANDARD BUILDING CODE.
 **WHERE IS VELOCITY PRESURE TAKEN FROM?.
 THIS DOESN'T APPLY.
 H) NEED ATTIC ACCESS ABOVE GARAGE AND
 ABOVE 2ND F. SEC. 2309.6 FBC 2001.
 I) ENTRY DOOR TO PROVIDE 32" MIN. CLEAR
 OPENING. TABLE 1004 FBC 2001. REVISE
 DOOR SCHEDULE AS REQUIRED.
  
 7- SHEET A-3: WRONG ORIENTATION OF
 EXTERIOR ELEVATIONS. SEE COMMENTS.
  
 8- SHEET A-4: A) PROVIDE COMPLETE
 ENGINEERING ANALYSIS AND CALCULATIONS
 FOR BEAM SPECIFIED ON DETAIL 3/A-4. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B) CLARIFY HOW IS A/C DUCTWORK GOING TO
 PASS THRU SECOND FLOOR FRAMING IF THERE
 ARE TWO CONCRETE BEAMS BLOCKING THE WAY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 C) PROVIDECOLUMN, BEAM AND LINTEL
 SCHEDULE. SEC. 104.2.1.2 CITY AMENDMENTS
 D) SPECIFY FOOTING SIZES & REINFORCEMENT
 E) COORDINATE COLUMN DETAILS WITH
 FOUNDATION PLANS. CHECK SIZES, ETC.
 F) SPECIFY CONNECTORS AT THE ENDS OF
 GIRDER TRUSS AT STAIRWELL.
 G) CLARIFY WHY USING #2'S FOR REBAR
 TIES. SPECIFY WHICH ASTM STANDARD IS
 USED TO SPECIFY THIS SIZE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 H) CLARIFY WHY SPECIFYING DOUBLE 2X4 TOP
 CHORD IN FLOOR TRUSSES. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 I) FOOTING DETAIL DRAWN BETWEEN LIVING
 ROOM AND GARAGE IS WRONG. SHOW STEP.
 J) SPECIFY CONNECTORS AT THE END OF
 GIRDER TRUSS BY BEDROOM #4. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 K) SPECIFY FASTENERS FOR 2X6 WALL
 LEDGER. SEC. 104.2.1.2 CITY AMENDMENTS.
 L) SECOND FLOOR PLAN IS MISSING ALL
 COLUMNS AND OPENING SIZES, ETC.
 M) SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION ON SECOND FLOOR FRAMING PLAN.
 SEC. 2305.2.2 FBC 2001.
 N) SEE COMMENTS ON REVIEWED SET.
 O) SPECIFY CONNECTIONS AT THE ENDS OF
 CONCRETE BEAMS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 9- SHEET A-5: A) ROOF FRAMING PLAN ABOVE
 GARAGE NEED TO SHOW CRICKET. PROVIDE
 DETAIL/SPECS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B) PROVIDE TRUSS ANCHOR SCHEDULE AND
 SPECIFY THE CALCULATED UPLIFT LOADS IN
 THE ROOF FRAMING PLAN. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 **NOTE: SEE LATEST SIMPSON CONNECTOR
 SCHEDULE FOR PROPER NUMBER AND TYPE OF
 NAILS TO BE USED. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING CALCS FOR NUMBER
 AND TYPE OF NAILS THAT DIFFER FROM THOSE
 TESTED AND PUBLISHED.
 C) SPECIFY FASTENERS FOR METAL DROP
 CEILING AT SECOND FLOOR. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 D) CLEARLY SPECIFY SIZE OF BEAM BETWEEN
 LIVING AREA AND GARAGE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 E) CLARIFY WHY MONOLITHIC FOOTING AT THE
 PERIMETER OF THE HOUSE IS SHOWN WITH A
 HIGH RECESS. WHAT'S THE PURPOSE OF IT?
 ONLY 1 1/2" IS REQUIRED BY SECTION
 2111.1.9 CITY AMENDMENTS FBC 2001.
  
 10- SHEET A-7: A) CONNECTOR SPECIFY FOR
 DETAIL AT HANGER DOESN'T WORK. SEE
 SIMPSON SCHEDULE AND REVISE AS REQ'D.
 B) SPECIFY ROOF TILE FASTENING. SEE SEC.
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 C) UPDATE SIMPSON CONNECTORS. SEE LATEST
 CATALOGUE FOR TYPE AND NUMBER OF NAILS.
 D) SPECIFY NAILING FOR ROOF SHEATHING.
 SEE TABLE 2306.1 CITY AMENDMENTS TO FBC
 2001. FOR NAILING AT ZONE 3.
 E) CLARIFY WHY USING 3/16" PLYWOOD
 SOFFIT. SEC. 104.2.1.2 CITY AMENDMENTS.
 F) WINDOW #11 DOESN'T MATCH SIZE SHOWN
 ON PLANS. REVISE AS REQUIRED.
 G) DETAIL 2/A-6: WHAT'S A 2#24" DEEP
 TRUSS?. REVISE AS REQUIRED.
 H) WHY USING #2 REBAR TIES?. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 11- PROVIDE SURVEY SHOWING HOUSE LAYOUT.
  
 12- OWES $472.51 FOR UPDATED VALUATION
 AND RADON FEES.
  
 13- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS: *FLORIDA OR LOCAL
 PRODUCT APPROVAL. **KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE. SEE
 SAMPLE. ***CLEARLY MARK ON SHUTTER
 DRAWINGS SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING TO BE USED.
  
 14- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) ROOF TILE.
 B) SINGLE HUNG WINDOWS.
 C) GARAGE DOOR. NEED COPY OF THE SAME
 DWGS THAT WERE SUBMITTED FOR FLORIDA
 PRODUCT APPROVAL. NEED THE ENGINEER
 REPORT AND DRAWINGS. DADE COUNTY NOA WAS
 NOT PRESENTED FOR THEIR APPROVAL.
 D) SLIDING GLASS DOORS. NEED LEGIBLE
 DRAWINGS AND ARCHITECT'S CALCULATED
 DESIGN PRESSURES.
 E) ENTRY DOOR. PROVIDE PRODUCT APPROVAL
 ONLY FOR THE DOOR TO BE USED.
 NOTE: KEEP IN MIND THAT DOOR WILL BE
 USED FOR EGRESS. THEREFORE, SHUTTERS
 CAN'T BE INSTALLED ON IT.
 F) TRUSS CONNECTORS SPECIFIED ON PLANS.
  
 15- ENERGY CALCULATIONS: A) OWNER/AGENT
 TO SIGN AND DATE BOTTOM OF FORM.
 B) COMPLETE INFORMATION ON TOP OF FORM.
 BUILDER, PERMITTING OFFICE, PROJECT
 ADDRESS, ETC.
  
 16- SOIL TEST REPORT ASSUMPTION IS THAT
 THE HOUSE IS A SINGLE STORY BUILDING.
 ACTUAL BUILDING IS A TWO STORY . REVISE
 REPORT TO MATCH ACTUAL BUILDING AND MAKE
 PROPER FOUNDATION ASSUMPTIONS.
  
 17- REVISE ADDRESS SHOWN ON PLANS.
 CORRECT ADDRESS IS 615 39TH STREET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-01 Cont ID  
Sent By btrobaug Date 2006-08-01 Time 08:11 Rev Time 0.33
Received By btrobaug Date 2006-08-01 Time 08:03 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-24 Cont ID  
Sent By jleahy Date 2006-01-24 Time 14:42 Rev Time 0.30
Received By jleahy Date 2006-01-24 Time 14:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 13:48 Rev Time 0.00
Received By shill Date 2005-07-21 Time 13:48 Sent To  
Notes
2005-07-21 00:00:00SEE MASTER

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-02 Cont ID  
Sent By btrobaug Date 2005-06-02 Time 12:40 Rev Time 0.75
Received By btrobaug Date 2005-06-02 Time 12:19 Sent To M
Notes
2005-06-02 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 CIRCUITS 1,3 AND 5 INCORRECTLY HAVE #14
 WIRE ON A 20AMP BREAKER.310.16.
  
 A SMOKE DETECTOR IS REQUIRED IN THE HALL
 OUTSIDE OF THE BEDROOMS (2ND FL.) PER
 905.2.2 FBC.
  
 MAKE CORRECTIONS ON THE DRAWING AND
 RESUBMIT PRIOR TO ROUGH ELECTRICAL
 INSPECTION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-18 Cont ID  
Sent By btrobaug Date 2005-03-18 Time 10:19 Rev Time 0.50
Received By btrobaug Date 2005-03-17 Time 16:39 Sent To M
Notes
2005-03-18 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT A COMPLETE RISER DIAGRAM, LOAD
 CALCULATIONS, AND PANEL SCHEDULES PER
 215.5.
  
 2} SHOW CALCULATIONS AND GIVE RATING FOR
 FAULT CURRENT AT THE SERVICE PER 110.9 &
 10, AND AIC RATING OF THE EQUIPMENT .
  
 3} A RECEPTACLE IS REQUIRED AT THE REAR
 OF THE HOUSE PER 210.52(E).
  
 4} BOTH FRONT AND REAR RECEPTACLES MUST
 BE GFI PER 210.8(A)(3).
  
 5} GARAGE RECEPTACLES MUST COMPLY WITH
 210.8(A)(2), GFI.
  
 6} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH THE SPACING
 REQUIREMENTS OF 210.52(C).
  
 7} PLEASE SEE THAT THE SMOKE DETECTORS
 COMPLY WITH LOCATION REQUIREMENTS OF
 905.2.2 FBC & 8-1.4.1.6.2. NFPA-72.
  
 8} SEVERAL ROOMS DO NOT COMPLY WITH THE
 SPACING REQUIREMENTS OF 210.52.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 15:55 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 15:55 Sent To E
Notes
2006-07-31 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 18:17 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 18:17 Sent To P
Notes
2006-06-07 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-01-23 Cont ID  
Sent By adarroug Date 2006-01-23 Time 14:35 Rev Time 0.00
Received By adarroug Date 2006-01-23 Time 14:35 Sent To E
Notes
2006-01-23 00:00:00TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-07-15 Cont ID  
Sent By adarroug Date 2005-07-15 Time 11:21 Rev Time 0.00
Received By adarroug Date 2005-07-15 Time 11:21 Sent To M
Notes
2005-07-15 00:00:00TO "PKRAUSS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 14:10 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 14:10 Sent To Z
Notes
2005-07-06 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 08:29 Rev Time 0.00
Received By shill Date 2005-06-17 Time 08:29 Sent To B
Notes
2005-06-17 00:00:00TO SH DESK
  
 CHANGED PLAN TO BE ISSUED FROM MASTER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 15:51 Rev Time 0.00
Received By shill Date 2005-06-09 Time 15:51 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 09:30 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 09:30 Sent To E
Notes
2005-05-26 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-16 Cont ID  
Sent By adarroug Date 2005-03-16 Time 11:44 Rev Time 0.00
Received By adarroug Date 2005-03-16 Time 11:44 Sent To E
Notes
2005-03-16 00:00:00TO "SFR""E"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 15:07 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 15:07 Sent To Z
Notes
2005-03-14 00:00:00TO "Z"BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-17 Cont ID  
Sent By adarroug Date 2005-04-08 Time 14:23 Rev Time 0.00
Received By shill Date 2005-02-17 Time 14:23 Sent To Z
Notes
2005-02-17 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 13:48 Rev Time 0.00
Received By shill Date 2005-07-21 Time 13:48 Sent To  
Notes
2005-07-21 00:00:00SEE MASTER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-07-16 Cont ID  
Sent By hmoser Date 2005-07-16 Time 11:30 Rev Time 0.00
Received By hmoser Date 2005-07-16 Time 11:21 Sent To P
Notes
2005-07-16 00:00:00PLAN DENIED
 1) PLEASE SUBMIT TWO SETS OF ENERGY
 CALCULATIONS AND MANUAL J.
 2) RETURN AIR CANS IN BEDROOMS ARE TO
 SMALL FOR RETURN AIR DUCT.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2005-03-22 Time   Rev Time 0.00
Received By hmoser Date 2005-03-22 Time 17:52 Sent To B
Notes
2005-03-22 00:00:00PLAN DENIED
 1)REFER TO SECTION 601.4 BALANCED RETURN
 AIR 2001 FBC(M)
 2) PLANS NEED TO BE STAMPED BY ARCHITE
 WHO IS ON 1ST.SET OF PLANS.
 PLAN ERVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-10 Cont ID  
Sent By jleech Date 2006-06-10 Time 13:43 Rev Time 0.00
Received By jleech Date 2006-06-10 Time 13:43 Sent To  
Notes
2006-06-10 00:00:00REVISED RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 13:49 Rev Time 0.00
Received By shill Date 2005-07-21 Time 13:49 Sent To  
Notes
2005-07-21 00:00:00SEE MASTER

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-22 Cont ID  
Sent By gsalfeld Date 2005-03-22 Time 15:26 Rev Time 1.00
Received By gsalfeld Date 2005-03-22 Time 15:25 Sent To B
Notes
2005-03-22 00:00:003/22/05
 1-SAN RISER DIAGRAM DOES NOT REFLECT
 FLOOR PLAN NOR DOES IT MEET CODE
 REQUIREMENTS.
  
 2-SUBMIT RISER DIAGRAM IN ISOMETRIC FORM
 TO MATCH THE INSTALLATION OF PLUMBING.
 SEE FBC 2001 SEC 104.2.1-REQUIREMENTS

Review Stop Z ZONING
Rev No 5 Status P Date 2006-08-08 Cont ID  
Sent By mmclean Date 2006-08-08 Time 08:48 Rev Time 0.00
Received By mmclean Date 2006-08-08 Time 08:48 Sent To  
Notes
2006-08-08 00:00:00REVISION - ADDING AN ATTACHED GARAGE AND
 COVERED PORCH

Review Stop Z ZONING
Rev No 4 Status P Date 2005-07-14 Cont ID  
Sent By mmclean Date 2005-07-14 Time 13:58 Rev Time 0.00
Received By mmclean Date 2005-07-14 Time 13:58 Sent To I
Notes
2005-07-14 00:00:00NOTE: WALKWAY IS OMITTED FROM PERMIT

Review Stop Z ZONING
Rev No 3 Status F Date 2005-06-16 Cont ID  
Sent By mmclean Date 2005-06-16 Time 18:39 Rev Time 0.00
Received By mmclean Date 2005-06-16 Time 18:39 Sent To I
Notes
2005-06-16 00:00:00DENIED.
 1. NEED TO REDUCE DRIVEWAY/WALKWAY TO
 MEET THE ZONING REQUIREMENTS
 2. MUST PROVIDE THE WIDTH/LENGTH OF
 DRIVEWAY/WALKWAY.
 **MUST HAVE 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK**
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By mmclean Date 2005-03-15 Time 16:14 Rev Time 0.00
Received By mmclean Date 2005-03-15 Time 16:14 Sent To I
Notes
2005-03-15 00:00:00APPROVED BY SHIRLEY GRAHAM, ASSOC.
 PLANNER 822-1458

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-02 Cont ID  
Sent By mmclean Date 2005-03-02 Time 09:48 Rev Time 0.00
Received By mmclean Date 2005-03-02 Time 09:48 Sent To  
Notes
2005-03-02 00:00:00DENIED,
 1. NEED TO PROVIDE CORRECT SITEPLAN,
 SHOWING BUILDING ON BOTH SIDES WITH
 SETBACKS. CALLED CONTR FOR P/U FILE S.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICE
 805-6720