| Plan Review Stops For Permit 05020987 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2006-11-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-11-20 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-11-20 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2006-11-20 10:52:38 | CLOSET REVISION OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2006-05-15 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-05-15 |
Time |
16:15 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2006-05-15 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2006-05-15 00:00:00 | ROOF REVISION OK FROM TILE TO SHINGLE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2005-09-27 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-09-27 |
Time |
14:08 |
Rev Time |
1.25 |
| Received By |
alange |
Date |
2005-09-27 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2005-08-30 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-08-30 |
Time |
09:56 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2005-08-30 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2005-08-30 00:00:00 | DENIED | | | | | | 1. PRODUCT APPROVALS SUBMITTED ARE VERY | | | INCOMPLETE AND ARE MISSING SECOND | | | COPIES, QUALITY ASSURANCE REPORTS AND | | | HAND WRITTEN NOA#S ON A STATE REPORT. | | | THE FOLLOWING IS A BREAK DOWN FOR EACH | | | INDIVIDUAL PRODUCT AND THE ITEMS | | | REQUIRED. | | | | | | A.SIMPSON TIES CO. ARE OK SUBMIT A | | | SECOND COMPLETE SET. | | | | | | B.ZION TILE IS OK.SUBMIT A SECOND | | | COMPLETE SET. | | | | | | C. LINTELS, CAST-CRETE CO.SUBMIT 2 | | | COMPLETE COPIES OF PRODUCT APPROVALS | | | WITH QUALITY ASSURANCE. NONE SUBMITTED. | | | ONE COPY OF STATE PRODUCT APPROVAL | | | SUBMITTED.SUBMIT A SECOND COPY. | | | | | | D.PELLA CORPORATION, SUBMIT A SECOND | | | COMPLETE SET OF PRODUCT APPROVALS FOR | | | CASEMENT WINDOW, FIXED WINDOW AND | | | SWINGING DOOR. | | | | | | NOTE; ALL PRODUCT APPROVALS WITH QUALITY | | | ASSURANCE SHALL HAVE THE FOLLOWING STATE | | | PRODUCAT APPROVALS ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | | | | 2.DOOR AND WINDOW SCHEDULE IS MISSING | | | FROM PLANS. | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-08-19 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-08-19 |
Time |
09:31 |
Rev Time |
1.25 |
| Received By |
alange |
Date |
2005-08-19 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2005-08-19 00:00:00 | | | | DENIED | | | THIRD REVIEW: | | | | | | 3.PRODUCT APPROVALS WITH QUALITY | | | ASSURANCE REQUIRED FOR LINTELS. | | | | | | ** ALL PRODUCT APPROVALS REQUIRE THE | | | FOLLOWING STATE PRODUCT APPROVAL TO BE | | | ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE AND REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-29 |
Time |
07:59 |
Rev Time |
1.25 |
| Received By |
alange |
Date |
2005-06-29 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2005-06-29 00:00:00 | | | | DENIED | | | SECOND REVIEW: | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.PRODUCT APPROVALS WITH QUALITY | | | ASSURANCE REQUIRED FOR THE FOLLOWING. | | | ROOFING, EXTERIOR DOORS, WINDOWS, IMPACT | | | PROTECTION, STRAPS AND TIE-DOWNS AND | | | LINTELS. | | | ALL PRODUCT APPROVALS REQUIRE THE | | | FOLLOWING TO BE ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 4.PLEASE SIGN OWNER/AGENT ON ENERGY | | | CALCS. | | | | | | 5.BASED ON SBCCI BUILDING VALUATION | | | DATA THE VALUATION HAS BEEN REVISED TO | | | $108821.00 ADDITIONAL PERMIT FEES OF | | | $103.23 ARE DUE. | | | | | | 9.FBC 3401.7.1.2.1 SHOW HOW SMOKE | | | DETECTORS AND GFCI OUTLETS WILL COMPLY | | | WITH THIS SECTION. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE AND REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-03-14 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-03-14 |
Time |
10:42 |
Rev Time |
1.33 |
| Received By |
alange |
Date |
2005-03-14 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2005-03-14 00:00:00 | | | | DENIED | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.PRODUCT APPROVALS WITH QUALITY | | | ASSURANCE REQUIRED FOR THE FOLLOWING. | | | ROOFING, EXTERIOR DOORS, WINDOWS, IMPACT | | | PROTECTION, STRAPS AND TIE-DOWNS AND | | | LINTELS. | | | ALL PRODUCT APPROVALS REQUIRE THE | | | FOLLOWING TO BE ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 4.SUBMIT 2 COPIES OF ENERGY CALCS. | | | | | | 5.BASED ON SBCCI BUILDING VALUATION | | | DATA THE VALUATION HAS BEEN REVISED TO | | | $108821.00 ADDITIONAL PERMIT FEES OF | | | $103.23 ARE DUE. | | | | | | 6.SQUARE FOOTAGE ON APPLICATION HAS | | | BEEN REVISED TO MATCH PLANS. | | | | | | 7.SHOW SIZE AND LOCATION OF ATTIC | | | ACCESS FBC 2309.6 | | | | | | 8.SAFTEY GLAZING REQUIRED FOR WINDOW | | | "A"FBC 2405.2.1 | | | | | | 9.FBC 3401.7.1.2.1 SHOW HOW SMOKE | | | DETECTORS AND GFCI OUTLETS WILL COMPLY | | | WITH THIS SECTION. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-10-17 |
Time |
17:15 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-10-17 |
Time |
15:49 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-08-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-08-16 |
Time |
07:36 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2005-08-16 |
Time |
06:53 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-06-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-16 |
Time |
08:16 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-06-16 |
Time |
07:27 |
Sent To |
M |
|
| Notes |
| 2005-06-16 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE RISER DIAGRAM APPEARS TO INDICATE | | | #1 CU. AND A #6 GROUND IN THE CONDUIT | | | PRESUMABLY COMING FROM THE METER, | | | ALTHOUGH THIS IS NOT CLEAR BECAUSE THE | | | LINE LEAVING THE METER IS NOT LABLED AT | | | ALL. THE #1 CONDUCTORS ARE TOO SMALL FOR | | | A 200 AMP OCP. SEE 310.15(B)(6).ALSOTHE | | | GEC NEEDS TO BE SHOWN SEPARATE FROM THE | | | FEED, AND THE #2 WHILE NOT A VIOLATION, | | | IS A RATED GEC FOR A 300 TO 500 AMP | | | SERVICE. THE ELECTRICAL CONTRACTOR COULD | | | FURNISH INSIGHT AS TO PRACTICAL | | | INSTALLATION. REVISE DRAWING TO SHOW | | | COMPLIANCE WITH 215.5. INDICATE THE | | | CONDUIT AND WIRE SIZE FROM THE METER TO | | | THE PANEL. | | | | | | 2} THE FUTURE POOL HEATER IS CALCULATED | | | AT 1200 VA. PLEASE VERIFY. | | | | | | 3} THE GENERAL LIGHTING CIRCUIT BREAKERS | | | ARE LISTED AS 4 POLE. PLEASE CLARIFY. | | | | | | 4}PLEASE SUBMIT AIC RATINGS FOR ALL | | | NEW SERVICE EQUIPMENT BEING INSTALLED. | | | MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 5} 3} SHOW LIGHTING PER ARTICLE | | | 210.70(A)(1,2&3). | | | | | | 4} SMOKE DETECTORS ARE REQUIRED PER | | | 8-1.4.1.6 NFPA-72. | | | | | | 5} PER ARTICLE 3401.7.2.6 OF THE FLORIDA | | | BUILDING CODE THE WIRING IN THE ENTIRE | | | HOUSE, INCLUDING OUTSIDE RECEPTACLES, | | | MUST BE MADE TO COMPLY WITH NFPA-70, | | | 2002, SHOW ON PLAN. | | | | | | 6} SHW THE LOCATIONS OF ALL SERVICE | | | EQUIPMENT ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-02-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-02-28 |
Time |
15:46 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-02-28 |
Time |
15:17 |
Sent To |
M |
|
| Notes |
| 2005-02-28 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SHOW THE LOCATION OF THE NEW SUB | | | PANEL ON THE PLAN. | | | | | | 2} IF EXISTING SERVICE AND SUBPANEL ARE | | | ON THE SAME BUILDING WHY DOES THE | | | SUBPANEL HAVE A GEC? COMPLY WITH 250.32. | | | | | | 3} SHOW LIGHTING PER ARTICLE | | | 210.70(A)(1,2&3). | | | | | | 4} SMOKE DETECTORS ARE REQUIRED PER | | | 8-1.4.1.6 NFPA-72. | | | | | | 5} PER ARTICLE 3401.7.2.6 OF THE FLORIDA | | | BUILDING CODE THE WIRING IN THE ENTIRE | | | HOUSE, INCLUDING OUTSIDE RECEPTACLES, | | | MUST BE MADE TO COMPLY WITH NFPA-70, | | | 2002, SHOW ON PLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-17 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-17 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2006-11-17 11:46:04 | TO "ALANGE" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-12 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-12 |
Time |
18:19 |
Sent To |
E |
|
| Notes |
| 2006-10-12 18:20:35 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-08-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-01 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-01 |
Time |
14:08 |
Sent To |
M |
|
| Notes |
| 2006-08-01 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-06-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-21 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-21 |
Time |
16:02 |
Sent To |
M |
|
| Notes |
| 2006-06-21 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-19 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-19 |
Time |
10:57 |
Sent To |
B |
|
| Notes |
| 2005-09-19 00:00:00 | TO "ALANGE" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-23 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-23 |
Time |
18:02 |
Sent To |
B |
|
| Notes |
| 2005-08-23 00:00:00 | TO "ALANGE" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-08-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-15 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-15 |
Time |
13:50 |
Sent To |
E |
|
| Notes |
| 2005-08-15 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-06-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-15 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-15 |
Time |
13:45 |
Sent To |
E |
|
| Notes |
| 2005-06-15 00:00:00 | TO BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-06-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-06-08 |
Time |
06:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-06-08 |
Time |
06:59 |
Sent To |
Z |
|
| Notes |
| 2005-06-08 00:00:00 | TO 'Z' BOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-02-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-28 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-28 |
Time |
10:26 |
Sent To |
E |
|
| Notes |
| 2005-02-28 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-02-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-18 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-18 |
Time |
08:14 |
Sent To |
Z |
|
| Notes |
| 2005-02-18 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-08 |
Time |
12:19 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-08-08 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2006-08-08 00:00:00 | *** PROVISO *** | | | 1) RETURN AIR TRANSFER DUCT TO MASTER | | | SUITE NEEDS TO BE 14", PER 2001 FBC/M | | | 601.4 . | | | 2) PROVIED COMBUSTION AND MAKE-UP AIR | | | FOR GAS WATER HEATER, DUE TO CLOTHES | | | DRYER EXHAUST, PER 2001 FBC/FG 614.5 AND | | | 304.4 . | | | 3) NO RETURN AIR GRILL PERMITED IN | | | LAUNDRY ROOM DUE TO GAS APPLIANCES, PER | | | 2001 FBC/FG 304.4 AND 2001 FBC/R | | | M1602.2(4) . | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2006-06-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-22 |
Time |
10:42 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-06-22 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2006-06-22 00:00:00 | *** DENIED *** | | | 1) BUILDING PLANS SHOW TOTAL SQ. FEET | | | UNDER AIR AS 2834, THE ENERGY | | | CALCULATIONS SHOW TOTAL SQ. FEET UNDER | | | AIR AS 3056, THE TWO MUST COINCIDE | | | PLEASE CORRECT. | | | | | | 2) HAVE NEW ENERGY CAL'S. SIGNED BY | | | OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2 | | | | | | 3) SUBMIT A COMPLETE SET OFMANUAL J | | | CALCULATIONS, PER 2004 FBC | | | 13-607.1.ABC.1 . | | | | | | 4) SHOW A/C SYSTEM'S SENSIBLE BTU'S AND | | | TOTAL BTU'S ON MECH. SCHEDULE. | | | | | | 5) MECH. PLANS ARE SHOWING TWO RETURN | | | AIR GRILLS FOR EXISTING BEDROOM #2, | | | PLEASE CORRECT AND SHOW CORRECT SIZE OF | | | RETURN AIR DUCT. | | | | | | 6) RETURN ARI TRANSFER DUCT TO EXISTING | | | BEDROOM #3 IS TO SMALL, SEE NOTE #7. | | | | | | 7) BALANCED RETURN AIR. | | | THIS MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-28 |
Time |
15:18 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2005-06-28 |
Time |
15:11 |
Sent To |
B |
|
| Notes |
| 2005-06-28 00:00:00 | PROVISO: | | | RETURN AIR FROM THE MASTER BEDROOM SHALL | | | BE A MINIMUM OF 13" IN ACCORDANCE WITH | | | 2001 FBC(M)601.4 EXCEPTION #3. | | | | | | RETURN AIR FROM BEDROOM #2 SHALL BE A | | | MINIMUM OF 8". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-03-01 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-03-01 |
Time |
09:17 |
Rev Time |
1.00 |
| Received By |
prafter |
Date |
2005-03-01 |
Time |
09:17 |
Sent To |
P |
|
| Notes |
| 2005-03-01 00:00:00 | MECH. PLAN REVIEW. | | | | | | 1. BUILDING REQUIRES FLORIDA ENERGY | | | EFFICIENCY REPORT. | | | 2. A/C PLAN DOES NOT REFLECT RETURN | | | AIR TO A.U.H. OR R/A OUT OF BEDROOMS / | | | DRYER VENT / AND BEDROOM 2. A/C. | | | 3. LOCATION OF CONDENSING UNIT NOT | | | REFLECTED ON A/C PLAN. | | | 4. A.H.U. REQUIRES SAFE PAN UNDER UNIT | | | W/ FLOAT S.W. . FBC/M 307.2.3AND | | | CONDENSATE PIPING WITH TURMINATION POINT | | | TO BE REFLECTED ON A/C PLAN. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719. | | | PLEASE CALL IF THEAR ANY QUESTION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-03-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-03-12 |
Time |
16:20 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2005-03-12 |
Time |
16:20 |
Sent To |
B |
|
| Notes |
| 2005-03-12 00:00:00 | NO PLUMBING PLANS SUBMITTED FOR REVIEW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-06-14 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-06-14 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-06-14 |
Time |
18:23 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-02-25 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-02-25 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-02-25 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2005-02-25 00:00:00 | DENIED, | | | 1. THE ADDITION MUST MEET CURRENT CODE | | | SETBACK OF 5FT ON THE SIDE.CALLED | | | OWNER 2X NO ANSWER AND NO VOICE MAIL. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|