Plan Review Details - Permit 05020987
Plan Review Stops For Permit 05020987
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-11-20 Cont ID  
Sent By alange Date 2006-11-20 Time 10:52 Rev Time 0.00
Received By alange Date 2006-11-20 Time 10:52 Sent To  
Notes
2006-11-20 10:52:38CLOSET REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-05-15 Cont ID  
Sent By alange Date 2006-05-15 Time 16:15 Rev Time 0.50
Received By alange Date 2006-05-15 Time 16:15 Sent To  
Notes
2006-05-15 00:00:00ROOF REVISION OK FROM TILE TO SHINGLE

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-09-27 Cont ID  
Sent By alange Date 2005-09-27 Time 14:08 Rev Time 1.25
Received By alange Date 2005-09-27 Time 13:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-08-30 Cont ID  
Sent By alange Date 2005-08-30 Time 09:56 Rev Time 1.00
Received By alange Date 2005-08-30 Time 09:17 Sent To  
Notes
2005-08-30 00:00:00DENIED
  
 1. PRODUCT APPROVALS SUBMITTED ARE VERY
 INCOMPLETE AND ARE MISSING SECOND
 COPIES, QUALITY ASSURANCE REPORTS AND
 HAND WRITTEN NOA#S ON A STATE REPORT.
 THE FOLLOWING IS A BREAK DOWN FOR EACH
 INDIVIDUAL PRODUCT AND THE ITEMS
 REQUIRED.
  
 A.SIMPSON TIES CO. ARE OK SUBMIT A
 SECOND COMPLETE SET.
  
 B.ZION TILE IS OK.SUBMIT A SECOND
 COMPLETE SET.
  
 C. LINTELS, CAST-CRETE CO.SUBMIT 2
 COMPLETE COPIES OF PRODUCT APPROVALS
 WITH QUALITY ASSURANCE. NONE SUBMITTED.
 ONE COPY OF STATE PRODUCT APPROVAL
 SUBMITTED.SUBMIT A SECOND COPY.
  
 D.PELLA CORPORATION, SUBMIT A SECOND
 COMPLETE SET OF PRODUCT APPROVALS FOR
 CASEMENT WINDOW, FIXED WINDOW AND
 SWINGING DOOR.
  
 NOTE; ALL PRODUCT APPROVALS WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE
 PRODUCAT APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 2.DOOR AND WINDOW SCHEDULE IS MISSING
 FROM PLANS.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-19 Cont ID  
Sent By alange Date 2005-08-19 Time 09:31 Rev Time 1.25
Received By alange Date 2005-08-19 Time 09:19 Sent To  
Notes
2005-08-19 00:00:00 
 DENIED
 THIRD REVIEW:
  
 3.PRODUCT APPROVALS WITH QUALITY
 ASSURANCE REQUIRED FOR LINTELS.
  
 ** ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING STATE PRODUCT APPROVAL TO BE
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE AND REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-29 Cont ID  
Sent By alange Date 2005-06-29 Time 07:59 Rev Time 1.25
Received By alange Date 2005-06-29 Time 06:56 Sent To  
Notes
2005-06-29 00:00:00 
 DENIED
 SECOND REVIEW:
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS WITH QUALITY
 ASSURANCE REQUIRED FOR THE FOLLOWING.
 ROOFING, EXTERIOR DOORS, WINDOWS, IMPACT
 PROTECTION, STRAPS AND TIE-DOWNS AND
 LINTELS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 5.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUATION HAS BEEN REVISED TO
 $108821.00 ADDITIONAL PERMIT FEES OF
 $103.23 ARE DUE.
  
 9.FBC 3401.7.1.2.1 SHOW HOW SMOKE
 DETECTORS AND GFCI OUTLETS WILL COMPLY
 WITH THIS SECTION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE AND REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-14 Cont ID  
Sent By alange Date 2005-03-14 Time 10:42 Rev Time 1.33
Received By alange Date 2005-03-14 Time 09:36 Sent To  
Notes
2005-03-14 00:00:00 
 DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS WITH QUALITY
 ASSURANCE REQUIRED FOR THE FOLLOWING.
 ROOFING, EXTERIOR DOORS, WINDOWS, IMPACT
 PROTECTION, STRAPS AND TIE-DOWNS AND
 LINTELS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SUBMIT 2 COPIES OF ENERGY CALCS.
  
 5.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUATION HAS BEEN REVISED TO
 $108821.00 ADDITIONAL PERMIT FEES OF
 $103.23 ARE DUE.
  
 6.SQUARE FOOTAGE ON APPLICATION HAS
 BEEN REVISED TO MATCH PLANS.
  
 7.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS FBC 2309.6
  
 8.SAFTEY GLAZING REQUIRED FOR WINDOW
 "A"FBC 2405.2.1
  
 9.FBC 3401.7.1.2.1 SHOW HOW SMOKE
 DETECTORS AND GFCI OUTLETS WILL COMPLY
 WITH THIS SECTION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-17 Cont ID  
Sent By btrobaug Date 2006-10-17 Time 17:15 Rev Time 0.50
Received By btrobaug Date 2006-10-17 Time 15:49 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-16 Cont ID  
Sent By btrobaug Date 2005-08-16 Time 07:36 Rev Time 0.75
Received By btrobaug Date 2005-08-16 Time 06:53 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-16 Cont ID  
Sent By btrobaug Date 2005-06-16 Time 08:16 Rev Time 0.50
Received By btrobaug Date 2005-06-16 Time 07:27 Sent To M
Notes
2005-06-16 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM APPEARS TO INDICATE
 #1 CU. AND A #6 GROUND IN THE CONDUIT
 PRESUMABLY COMING FROM THE METER,
 ALTHOUGH THIS IS NOT CLEAR BECAUSE THE
 LINE LEAVING THE METER IS NOT LABLED AT
 ALL. THE #1 CONDUCTORS ARE TOO SMALL FOR
 A 200 AMP OCP. SEE 310.15(B)(6).ALSOTHE
 GEC NEEDS TO BE SHOWN SEPARATE FROM THE
 FEED, AND THE #2 WHILE NOT A VIOLATION,
 IS A RATED GEC FOR A 300 TO 500 AMP
 SERVICE. THE ELECTRICAL CONTRACTOR COULD
 FURNISH INSIGHT AS TO PRACTICAL
 INSTALLATION. REVISE DRAWING TO SHOW
 COMPLIANCE WITH 215.5. INDICATE THE
 CONDUIT AND WIRE SIZE FROM THE METER TO
 THE PANEL.
  
 2} THE FUTURE POOL HEATER IS CALCULATED
 AT 1200 VA. PLEASE VERIFY.
  
 3} THE GENERAL LIGHTING CIRCUIT BREAKERS
 ARE LISTED AS 4 POLE. PLEASE CLARIFY.
  
 4}PLEASE SUBMIT AIC RATINGS FOR ALL
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 5} 3} SHOW LIGHTING PER ARTICLE
 210.70(A)(1,2&3).
  
 4} SMOKE DETECTORS ARE REQUIRED PER
 8-1.4.1.6 NFPA-72.
  
 5} PER ARTICLE 3401.7.2.6 OF THE FLORIDA
 BUILDING CODE THE WIRING IN THE ENTIRE
 HOUSE, INCLUDING OUTSIDE RECEPTACLES,
 MUST BE MADE TO COMPLY WITH NFPA-70,
 2002, SHOW ON PLAN.
  
 6} SHW THE LOCATIONS OF ALL SERVICE
 EQUIPMENT ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-28 Cont ID  
Sent By btrobaug Date 2005-02-28 Time 15:46 Rev Time 0.50
Received By btrobaug Date 2005-02-28 Time 15:17 Sent To M
Notes
2005-02-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHOW THE LOCATION OF THE NEW SUB
 PANEL ON THE PLAN.
  
 2} IF EXISTING SERVICE AND SUBPANEL ARE
 ON THE SAME BUILDING WHY DOES THE
 SUBPANEL HAVE A GEC? COMPLY WITH 250.32.
  
 3} SHOW LIGHTING PER ARTICLE
 210.70(A)(1,2&3).
  
 4} SMOKE DETECTORS ARE REQUIRED PER
 8-1.4.1.6 NFPA-72.
  
 5} PER ARTICLE 3401.7.2.6 OF THE FLORIDA
 BUILDING CODE THE WIRING IN THE ENTIRE
 HOUSE, INCLUDING OUTSIDE RECEPTACLES,
 MUST BE MADE TO COMPLY WITH NFPA-70,
 2002, SHOW ON PLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 11:44 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 11:44 Sent To  
Notes
2006-11-17 11:46:04TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 18:19 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 18:19 Sent To E
Notes
2006-10-12 18:20:35TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 14:08 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 14:08 Sent To M
Notes
2006-08-01 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 16:02 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 16:02 Sent To M
Notes
2006-06-21 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-19 Time 10:57 Rev Time 0.00
Received By adarroug Date 2005-09-19 Time 10:57 Sent To B
Notes
2005-09-19 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 18:02 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 18:02 Sent To B
Notes
2005-08-23 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-15 Cont ID  
Sent By adarroug Date 2005-08-15 Time 13:50 Rev Time 0.00
Received By adarroug Date 2005-08-15 Time 13:50 Sent To E
Notes
2005-08-15 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-15 Time 13:45 Rev Time 0.00
Received By shill Date 2005-06-15 Time 13:45 Sent To E
Notes
2005-06-15 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 06:59 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 06:59 Sent To Z
Notes
2005-06-08 00:00:00TO 'Z' BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 10:26 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 10:26 Sent To E
Notes
2005-02-28 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 08:14 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 08:14 Sent To Z
Notes
2005-02-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-08-08 Cont ID  
Sent By tgordon Date 2006-08-08 Time 12:19 Rev Time 0.45
Received By tgordon Date 2006-08-08 Time 12:19 Sent To  
Notes
2006-08-08 00:00:00*** PROVISO ***
 1) RETURN AIR TRANSFER DUCT TO MASTER
 SUITE NEEDS TO BE 14", PER 2001 FBC/M
 601.4 .
 2) PROVIED COMBUSTION AND MAKE-UP AIR
 FOR GAS WATER HEATER, DUE TO CLOTHES
 DRYER EXHAUST, PER 2001 FBC/FG 614.5 AND
 304.4 .
 3) NO RETURN AIR GRILL PERMITED IN
 LAUNDRY ROOM DUE TO GAS APPLIANCES, PER
 2001 FBC/FG 304.4 AND 2001 FBC/R
 M1602.2(4) .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-06-22 Cont ID  
Sent By tgordon Date 2006-06-22 Time 10:42 Rev Time 0.45
Received By tgordon Date 2006-06-22 Time 10:42 Sent To  
Notes
2006-06-22 00:00:00*** DENIED ***
 1) BUILDING PLANS SHOW TOTAL SQ. FEET
 UNDER AIR AS 2834, THE ENERGY
 CALCULATIONS SHOW TOTAL SQ. FEET UNDER
 AIR AS 3056, THE TWO MUST COINCIDE
 PLEASE CORRECT.
  
 2) HAVE NEW ENERGY CAL'S. SIGNED BY
 OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2
  
 3) SUBMIT A COMPLETE SET OFMANUAL J
 CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1 .
  
 4) SHOW A/C SYSTEM'S SENSIBLE BTU'S AND
 TOTAL BTU'S ON MECH. SCHEDULE.
  
 5) MECH. PLANS ARE SHOWING TWO RETURN
 AIR GRILLS FOR EXISTING BEDROOM #2,
 PLEASE CORRECT AND SHOW CORRECT SIZE OF
 RETURN AIR DUCT.
  
 6) RETURN ARI TRANSFER DUCT TO EXISTING
 BEDROOM #3 IS TO SMALL, SEE NOTE #7.
  
 7) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-28 Cont ID  
Sent By pkrauss Date 2005-06-28 Time 15:18 Rev Time 0.35
Received By pkrauss Date 2005-06-28 Time 15:11 Sent To B
Notes
2005-06-28 00:00:00PROVISO:
 RETURN AIR FROM THE MASTER BEDROOM SHALL
 BE A MINIMUM OF 13" IN ACCORDANCE WITH
 2001 FBC(M)601.4 EXCEPTION #3.
  
 RETURN AIR FROM BEDROOM #2 SHALL BE A
 MINIMUM OF 8".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-01 Cont ID  
Sent By prafter Date 2005-03-01 Time 09:17 Rev Time 1.00
Received By prafter Date 2005-03-01 Time 09:17 Sent To P
Notes
2005-03-01 00:00:00MECH. PLAN REVIEW.
  
 1. BUILDING REQUIRES FLORIDA ENERGY
 EFFICIENCY REPORT.
 2. A/C PLAN DOES NOT REFLECT RETURN
 AIR TO A.U.H. OR R/A OUT OF BEDROOMS /
 DRYER VENT / AND BEDROOM 2. A/C.
 3. LOCATION OF CONDENSING UNIT NOT
 REFLECTED ON A/C PLAN.
 4. A.H.U. REQUIRES SAFE PAN UNDER UNIT
 W/ FLOAT S.W. . FBC/M 307.2.3AND
 CONDENSATE PIPING WITH TURMINATION POINT
 TO BE REFLECTED ON A/C PLAN.
  
 PAT RAFTER 561/805/6728 OR 805/6719.
 PLEASE CALL IF THEAR ANY QUESTION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-03-12 Cont ID  
Sent By kstevens Date 2005-03-12 Time 16:20 Rev Time 0.25
Received By kstevens Date 2005-03-12 Time 16:20 Sent To B
Notes
2005-03-12 00:00:00NO PLUMBING PLANS SUBMITTED FOR REVIEW

Review Stop Z ZONING
Rev No 2 Status P Date 2005-06-14 Cont ID  
Sent By mmclean Date 2005-06-14 Time 18:23 Rev Time 0.00
Received By mmclean Date 2005-06-14 Time 18:23 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-02-25 Cont ID  
Sent By mmclean Date 2005-02-25 Time 17:11 Rev Time 0.00
Received By mmclean Date 2005-02-25 Time 17:11 Sent To  
Notes
2005-02-25 00:00:00DENIED,
 1. THE ADDITION MUST MEET CURRENT CODE
 SETBACK OF 5FT ON THE SIDE.CALLED
 OWNER 2X NO ANSWER AND NO VOICE MAIL.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved