Plan Review Details - Permit 05020865
Plan Review Stops For Permit 05020865
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-29 Cont ID  
Sent By shill Date 2005-03-29 Time 10:27 Rev Time 0.50
Received By shill Date 2005-03-29 Time 10:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-18 Cont ID  
Sent By shill Date 2005-02-18 Time 13:48 Rev Time 0.50
Received By shill Date 2005-02-18 Time 13:47 Sent To  
Notes
2005-02-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE A SITE PLAN SHOWING WHERE
 THE GENERATOR WILL BE INSTALLED.
  
 2.)NO STRUCTURAL INFORMATION PROVIDED.
 IS THIS GOING ONTO AN EXISTING CONCRETE
 SLAB?

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-29 Cont ID  
Sent By dpalmer Date 2005-03-29 Time 09:15 Rev Time 0.50
Received By dpalmer Date 2005-03-29 Time 08:37 Sent To  
Notes
2005-03-29 00:00:00VALUE ADJUSTED PER CONTRACT.
  
 ELECTRICAL PLANS OK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-25 Cont ID  
Sent By dpalmer Date 2005-02-25 Time 07:20 Rev Time 0.30
Received By dpalmer Date 2005-02-25 Time 07:20 Sent To  
Notes
2005-02-25 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE PROVIDE PLANS /RISER FOR
 COMPLETE WIRING AND CONNECTIONS FOR
 GENERATOR.
 PLEASE SHOW CONDUCTORS, CONDUITS,
 GROUNDING ETC. 215.5
 PLEASE SEE FS 471.003(2)H1, PLANS
 REQUIRED TO BE SIGNED,DATED AND SEALED
 BY A PE.
  
 2)NOTE: PLEASE PROVIDE AREA/ENCLOUSURE
 FOR GUARDING OF GENERATOR AND
 PROTECTION.
  
 3)NOTE: PLEASE SEE BLDG AND ZONING
 NOTES; PLEASE PROVIDE SITE PLAN FOR
 LOCATION OF GENERATOR.
  
 4)NOTE: PLEASE SEE FBC 104.6.5, VALUE
 FOR SCOPE OF WORK IS INCLUDE ALL LABOR
 AND MATERIALS EVEN IF OWNER SUPPLIED.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICLA PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-06 Cont ID  
Sent By mwennerg Date 2005-04-06 Time 15:00 Rev Time 0.00
Received By mwennerg Date 2005-04-06 Time 15:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-03-11 Cont ID  
Sent By mcarsill Date 2005-03-11 Time 12:04 Rev Time 0.00
Received By mcarsill Date 2005-03-11 Time 12:04 Sent To  
Notes
2005-03-11 00:00:001. PLEASE PROVIDE DRAWINGS INDICATING
 THE PROPOSED LOCATION OF THE GENERATOR.
  
 2. PLEASE INDICATE ANY ADJACENT EXIT
 DOORS, WINDOWS, ETC. TO THE
 PROPOSED GENRATOR.
  
 3. PLEASE INDICATE WHAT THE PROPOSED
 GENERATOR WILL PROVIDE POWER TO.
  
 4. PLEASE DISPLAY ALL FIRE SAFETY
 EQUIPMENT LOCATED NEAR THE
 EMERGENCY
  
 5. PLEASE PROVIDE DETAILS ON
 POWER SOURCE FOR THE EMEREGNCY
 GENERATOR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2005-04-21 Cont ID  
Sent By kstevens Date 2005-04-21 Time 17:09 Rev Time 1.00
Received By kstevens Date 2005-04-21 Time 17:09 Sent To  
Notes
2005-04-21 00:00:00SEPARATE GAS PLANS/PERMIT REQUIRED AND
 WILL BE SUBMIITTED SEPARATELY.
 GENERATOR SPECIFICATIONS SHALL SHOW A
 GAS LISTING.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2005-03-11 Cont ID  
Sent By kstevens Date 2005-03-11 Time 16:09 Rev Time 0.50
Received By kstevens Date 2005-03-11 Time 16:09 Sent To  
Notes
2005-03-11 00:00:00NO GAS PLANS SUBMITTED. SEPARATE GAS
 PLANS/PERMIT REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-28 Cont ID  
Sent By adarroug Date 2005-03-28 Time 13:55 Rev Time 0.00
Received By adarroug Date 2005-03-28 Time 13:55 Sent To  
Notes
2005-03-28 00:00:00TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 13:06 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 13:06 Sent To  
Notes
2005-02-15 00:00:00TO "COMM" BD#20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-04-11 Cont ID  
Sent By pkrauss Date 2005-04-11 Time 16:09 Rev Time 0.20
Received By pkrauss Date 2005-04-11 Time 16:09 Sent To  
Notes
2005-04-11 00:00:00PROVISO:
 GENERATOR SHALL BE INSTALLED SO THE
 NOXIOUS FUMES FROM THE EXHAUST WILL NOT
 BE RECIRCULATED INTO FRESH AIR INTAKES,
 WINDOWS OR DOORS. 2001 FBC/M 401.5.1 &
 501.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-04-05 Cont ID  
Sent By eschneid Date 2005-04-05 Time 09:06 Rev Time 0.00
Received By eschneid Date 2005-04-05 Time 09:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-11 Cont ID  
Sent By eschneid Date 2005-03-11 Time 13:45 Rev Time 0.00
Received By eschneid Date 2005-03-11 Time 13:45 Sent To  
Notes
2005-03-11 00:00:00SITE PLAN IS REQUIRED SHOWING THE
 LOCATION OF THE GENERATOR.